JOHNSON CONTROLS
8
FORM 100.50-SU3 (1207)
THERMOSTAT CONTROL – COOLING
Field Wiring
Connect the thermostat wiring to the fi eld wiring screw
connections on the Unit Controller
(see Appendix 1).
Misc. Connections
No additional connections required.
Programming
“COOLING MODE OPERATION ENABLED”
– Must
be set to ON using Parameter 53 under the PROGRAM
key on the Simplicity control board or under the
COOLING SETUP tab in the Simplicity PC software
package.
“CV OCCUPIED COOLING SETPOINT”
– Must be
set using Parameter 10 under the PROGRAM key on
the Simplicity control board or under the COOLING
SETUP tab in the Simplicity PC software package. For
thermostat operation this should be set to 99.0º F.
“CV UNOCCUPIED COOLING SETPOINT”
– Must
be set using Parameter 12 under the PROGRAM key
on the Simplicity control board or under the COOLING
SETUP tab in the Simplicity PC software package. For
thermostat operation this should be set to 99.0º F.
THERMOSTAT CONTROL – HEATING
Field Wiring
Connect the thermostat wiring to the fi eld wiring screw
connections on the Unit Controller
(see Appendix 1).
Misc. Connections
No additional connections required.
CONSTANT VOLUME UNITS
Programming
“HEATING MODE OPERATION ENABLED”
– Must
be set to ON using Parameter 54 under the PROGRAM
key on the Simplicity control board or under the
HEATING SETUP tab in the Simplicity PC software
package.
“CV OCCUPIED HEATING SETPOINT”
– Must be
set using Parameter 11 under the PROGRAM key on
the Simplicity control board or under the HEATING
SETUP tab in the Simplicity PC software package. For
thermostat operation this should be set to 45.0º F.
“CV UNOCCUPIED HEATING SETPOINT”
– Must
be set using Parameter 13 under the PROGRAM key
on the Simplicity control board or under the HEATING
SETUP tab in the Simplicity PC software package. For
thermostat operation this should be set to 45.0º F.
“STAGES OF HEATING AVAILABLE”
- Must be set
using Parameter 81 under the PROGRAM key on the
Simplicity control board or under the HEATING SETUP
tab in the Simplicity PC software package.
HARDWIRED OR COMMUNICATED SPACE SENSOR
CONTROL – COOLING
Field Wiring
Connect the space sensor wiring to the fi eld wiring screw
connections on the Unit Controller
(see Appendix 1).
Misc. Connections
No additional connections required.
Programming
“COOLING MODE OPERATION ENABLED”
– Must
be set to ON using Parameter 53 under the PROGRAM
key on the Simplicity control board or under the
COOLING SETUP tab in the Simplicity PC software
package.