JOHNSON CONTROLS
24
FORM 100.50-SU3 (1207)
PRE-OCCUPANCY PURGE
Field Wiring
No additional connections required.
Misc. Connections
No additional connections required.
Programming
“PRE-OCCUPANCY PURGE ENABLE”
– must be
turned ON under the SYSTEM OPTIONS tab in the
Simplicity PC software.
“PRE-OCCUPANCY PURGE TIME
(hours of day)”
– must be programmed under the SYSTEM OPTIONS
tab in the Simplicity PC software.
“PRE-OCCUPANCY PURGE TIME (minutes of day)”
– must be programmed under the SYSTEM OPTIONS
tab in the Simplicity PC software.
OUTDOOR AIR HEATING LOCKOUT
Field Wiring
No additional connections required.
Misc. Connections
No additional connections required.
Programming
“OUTDOOR AIR TEMP HEATING LOCKOUT”
– must be turned ON under the HEATING SETUP tab
in the Simplicity PC software.
HOT GAS BYPASS
Field Wiring
No additional connections required.
Misc. Connections
No additional connections required.
Programming
“ HOT GAS BY PASS PRESENT ON COMPRESSOR
#1”
– must be turned ON using Parameter 79 under
the PROGRAM key on the Simplicity control board
or under the COOLING SETUP tab in the Simplicity
PC software.
SPACE TEMPERATURE ALARM
Field Wiring
No additional connections required.
Misc. Connections
No additional connections required.
Programming
“SPACE TEMP TRENDING ALARM TEMP”
– must
be programmed under the SYSTEM OPTIONS tab in
the Simplicity PC software. 0% DISABLES.
“SPACE TEMP TRENDING ALARM TIME”
– must be
programmed under the SYSTEM OPTIONS tab in the
Simplicity PC software. 0 MINUTES DISABLES.
SAT ALARM FOR HEATING
Field Wiring
No additional connections required.
Misc. Connections
No additional connections required.
Programming