25
JOHNSON CONTROLS
FORM 100.50-SU3 (1207)
“SUPPLY AIR TEMP ALARM SETPOINT FOR
HEATING”
– must be programmed under the HEATING
SETUP tab in the Simplicity PC software. The range is
1.0º F – 120.0º F. Entering 0º F disables the feature.
SAT ALARM FOR COOLING
Field Wiring
No additional connections required.
Misc. Connections
No additional connections required.
Programming
“SUPPLY AIR TEMP ALARM SETPOINT FOR
COOLING”
– must be programmed under the
COOLING SETUP tab in the Simplicity PC software.
The range is 1.0º F – 80.0º F. Entering 0º F disables
the feature.
INTELLI-START
Field Wiring
No additional connections required.
Misc. Connections
No additional connections required.
Programming
“INTELLI-START OPERATION ENABLE”
– must be
turned ON under the SYSTEMS OPTION tab in the
Simplicity PC software.
SPACE SENSOR WITH SETPOINT ADJUSTMENT
Field Wiring
A connection must be made between the space Sensor
Reset Potentiometer and terminals SSO and GND on
the Simplicity control board
(see Appendix 1).
Misc. Connections
No additional connections required.
Programming
“SPACE SENSOR OFFSET RANGE”
– Must be
programmed using Parameter 56 under the PROGRAM
key on the Simplicity control board or under the
SYSTEMS OPTIONS tab in the Simplicity PC software.
The range is –5.0º F to +5.0º F. The default value is
0.0º F.
REMOTE CONTROL
Field Wiring
A 0 to 10 VDC signal must be connected to terminals
REM+ and REM- on the Simplicity control board
(see
Appendix 1).
Misc. Connections
No additional connections required.
Programming
“REMOTE CONTROL INPUT ENABLE FOR THIRD
PARTY BAS”
– Must be turned ON using Parameter 22
under the PROGRAM key on the Simplicity control
board or under the SYSTEMS OPTIONS tab in the
Simplicity PC software.
DIRTY FILTER
Field Wiring
No additional connections.
Misc. Connections
A dirty filter switch must be connected between
terminals 1 and 2 of the P22 connector on the Simplicity
control board.