RECYCLE OPERATION
When a flame is lost after the flame stabilization period, a
recycle operation occurs. If the unit fails after five recycle
attempts, the furnace is locked-out for one hour.
GAS HEATING OPERATION ERRORS
LOCK-OUT
A one-hour lockout occurs following three retries or five recy-
cles. During the one-hour lockout, flame detection, limit con-
ditions, and main valves are tested. Any improper results will
cause the appropriate action to occur. Recycling the low volt-
age power cancels the lock-out.
TEMPERATURE LIMIT
If the UCB senses zero volts from the high temperature limit,
the indoor blower motor is immediately energized. When the
UCB again senses 24 volts from the temperature limit, the
draft motor will perform a 15-second post-purge and the
indoor blower will be de-energized following the elapse of the
fan off delay for heating.
This limit is monitored regardless of unit operation status, i.e.
this limit is monitored at all times.
If the temperature limit opens three times within one hour, it
will lock-on the indoor blower motor and flash code is initiated
(See Table 80).
FLAME SENSE
Flame sensing occurs at all times. If “W1” is not present and
a flame is sensed for 2 seconds, the draft motor is energized
and the GV is kept off. The ICB halts any operation until a
flame is not detected. Once the flame detection is lost, the
ICB performs a post-purge. Normal operation is allowed con-
currently with the purge (i.e. this purge can be considered the
purge associated with a call for “W1”).
If “W1” is present, a flame is sensed, but the GV is not ener-
gized, the draft motor is energized until the flame detection is
lost. Normal operation is now allowed.
The flame detection circuitry continually tests itself. If the ICB
finds the flame detection circuitry to be faulty, the ICB will not
permit an ignition sequence and the draft motor is energized.
If this failure should occur during an ignition cycle the failure
is counted as a recycle.
GAS VALVE
The UCB and ICB continuously monitor the GV.
If the ICB senses voltage at the GV when not requested, the
ICB will energize the draft motor. The ICB will not operate the
furnace until voltage is no longer sensed at the GV. The draft
motor is stopped when voltage is not sensed at the GV.
Any time the UCB senses voltage at the GV without a call for
heat for a continuous five-minute period, the UCB will lock-on
the indoor blower and a flash code is initiated (Table 80).
When voltage is no longer sensed at the GV, the UCB will de-
energize the indoor blower following the elapse of the fan off
delay for heating.
If voltage has been sensed at the GV for at least 15 seconds
during the fan on delay for heating and GV voltage or “W1” is
lost, the indoor blower is forced on for the length of the fan off
delay for heating.
During a call for heat, if the UCB does not sense voltage at
the GV for a continuous five-minute period the UCB will ini-
tiate a flash code (Table 80). The indoor blower motor will not
be locked-on while there is no GV voltage.
SAFETY CONTROLS
The UCB monitors the temperature limit switch of gas heat units.
The control circuit includes the following safety controls:
LIMIT SWITCH (LS)
This control is located inside the gas heat compartment and
is set to open at the temperature indicated in the Gas Heat
Limit Control Settings Table 67. It resets automatically. The
limit switch operates when a high temperature condition,
caused by inadequate supply air flow occurs, thus shutting
down the heater and energizing the blower.
AUXILIARY LIMIT SWITCH (ALS)
This control is located inside the supply air compartment and
is set to open at the temperature indicated in the Gas Heat
Limit Control Settings Table 67. It resets manually. The limit
switch operates when a high temperature condition, caused
by inadequate supply air flow occurs, thus shutting down the
heater and energizing the blower.
The auxiliary limit switch is wired in series with the limit
switch. As such, the UCB cannot distinguish the auxiliary limit
and the gas heat limit switch operation except the auxiliary is
manual reset. Consequently, the control will respond in the
same manner as outlined above under “Limit Switch”.
TABLE 67: GAS HEAT LIMIT CONTROL SETTINGS
1
1.
Rollout = 300°F, Auxiliary Limit = 200°F.
Unit
Main Limit Setting
°F
Size
Opt.
DL -06
10
215
15
195
DL -07
10
165
15
165
DL -08
10
165
15
165
DL -10
15
195
20
160
DL -12
15
195
20
160
DU -06
10
165
15
165
DU -07
10
165
15
165
DU -08
10
165
15
165
DU -10
15
195
20
160
DU -12
15
195
20
160