167791-BIM-B-0606
Unitary Products Group
11
6.
Maintain level tolerance to 1/2” across the entire width
and length of unit.
RIGGING AND HANDLING
Exercise care when moving the unit. Do not remove any
packaging until the unit is near the place of installation. Rig
the unit by attaching chain or cable slings to the lifting holes
provided in the base rails. Spreader bars, whose length
exceeds the largest dimension across the unit,
MUST
be
used across the top of the unit.
Units may be moved or lifted with a forklift. Slotted openings
in the base rails are provided for this purpose.
LENGTH OF FORKS MUST BE A MINIMUM OF 60
INCHES.
Excessive exposure of this furnace to contaminated
combustion air may result in equipment damage or
personal injury. Typical contaminates include: per-
manent wave solution, chlorinated waxes and clean-
ers, chlorine based swimming pool chemicals, water
softening chemicals, carbon tetrachloride, Halogen
type refrigerants, cleaning solvents (e.g. perchloro-
ethylene), printing inks, paint removers, varnishes,
hydrochloric acid, cements and glues, antistatic fab-
ric softeners for clothes dryers, masonry acid wash-
ing materials.
If a unit is to be installed on a roof curb other than a
UPG roof curb, gasketing must be applied to all sur-
faces that come in contact with the unit underside.
Before lifting, make sure the unit weight is distrib-
uted equally on the rigging cables so it will lift evenly.
All panels must be secured in place when the unit is
lifted.
The condenser coils should be protected from rig-
ging cable damage with plywood or other suitable
material.
FIGURE 5 - UNIT 4 POINT LOAD
TABLE 3: UNIT WEIGHTS
Model
Shipping Weight
1
(lb.)
1.
54 kW heater.
Operating Weight
1
(lb.)
DL-06
1056
1041
DL-07
865
860
DL-08
880
875
DL-10
1131
1116
DL-12
1210
1195
DU-06
888
883
DU-07
895
890
DU-08
905
900
DU-10
1222
1207
DU-12
1212
1197
w/Econ.
85
84
w/ PE
150
148
w/Elec. Heat
49
49
w/Gas Heat
2
2.
8 Tube Heat Exchanger.
110
110
TABLE 4: 4 POINT LOAD WEIGHT
Model
Location (lbs.)
1
1.
Weights include largest gas heat option.
A
B
C
D
DL-06
228
195
285
333
DL-07
192
143
224
301
DL-08
195
146
228
306
DL-10
245
209
305
357
DL-12
262
224
327
382
DU-06
197
147
230
309
DU-07
199
148
232
311
DU-08
201
150
234
315
DU-10
265
226
330
386
DU-12
263
224
327
383
D
A
C
B
L E F T
F R O N T