condenser motor failure, (opens at 405 ± 10 psig or 440
± 10 psig depending on unit model).
3.
A low-pressure switch to protect against loss of refriger-
ant charge, (opens at 22 ± 5 psig or 45 ± 5 psig).
The above pressure switches are hard-soldered to the unit.
The refrigeration systems are independently monitored and
controlled. On any fault, only the associated system will be
affected by any safety/preventive action. The other refrigerant
system will continue in operation unless it is affected by the
fault as well.
The unit control board monitors the temperature limit switch
of electric heat units and the temperature limit switch and the
gas valve of gas furnace units.
COMPRESSOR PROTECTION
In addition to the external pressure switches, the compressors
also have inherent (internal) protection. If there is an abnormal
temperature rise in a compressor, the protector will open to
shut down the compressor. The UCB incorporates features to
minimize compressor wear and damage. An
Anti-Short Cycle
Delay (ASCD)
is utilized to prevent operation of a compressor
too soon after its previous run. Additionally, a minimum run
time is imposed any time a compressor is energized.
The ASCD is initiated on unit start-up and on any compressor
reset or lock-out.
FLASH CODES
The UCB will initiate a flash code associated with errors
within the system. Refer to UNIT CONTROL BOARD FLASH
CODES Table 80.
RESET
Remove the call for cooling, by raising thermostat setting
higher than the conditioned space temperature. This resets
any pressure or freezestat flash codes.
ELECTRIC HEATING SEQUENCE OF OPERATIONS
The following sequence describes the operation of the elec-
tric heat section.
Two-stage heating:
a.
Upon a call for first stage heat by the thermostat, the
heater relay (RA) will be energized. After completing
the specified fan on delay for heating, the UCB will
energize the blower motor. If the second stage of
heat is required, heater relay (RB) will be energized.
After completing the specified fan on delay for heat-
ing, the UCB will energize the blower motor.
b.
The thermostat will cycle the electric heat to satisfy
the heating requirements of the conditioned space.
ELECTRIC HEAT OPERATION ERRORS
TEMPERATURE LIMIT
If the UCB senses zero volts from the high temperature limit,
the indoor blower motor is immediately energized.
This limit is monitored regardless of unit operation status, i.e.
the limit is monitored at all times.
If the temperature limit opens three times within one hour, it
will lock-on the indoor blower motor and a flash code is initi-
ated (See Table 80).
SAFETY CONTROLS
The UCB monitors the temperature limit switch of electric
heat units.
The control circuit includes the following safety controls:
LIMIT SWITCH (LS)
This control is located inside the heater compartment and is
set to open at the temperature indicated in the Electric Heat
Limit Setting Table 64. It resets automatically. The limit switch
operates when a high temperature condition, caused by inad-
equate supply air flow occurs, thus shutting down the heater
and energizing the blower.
TABLE 64: ELECTRIC HEAT LIMIT SETTING
50” CABINET
UNIT (TONS)
VOLTAGE
HEATER
kW
LIMIT
SWITCH
OPENS °F
DL-06 (6.5)
208/230
9
150
DL-06, -10, -12 (6.5, 10, 12.5)
DU-10, -12 (10, 12.5)
18
150
DL-06, -10, -12 (6.5, 10, 12.5)
DU-10, -12 (10, 12.5)
24
150
DL-06, -10, -12 (6.5, 10, 12.5)
DU-10, -12 (10, 12.5)
34
150
DL, DU-10, -12 (10, 12.5)
54
130
DL-06 (6.5)
480
9
150
DL-06, -10, -12 (6.5, 10, 12.5)
DU-10, -12 (10, 12.5)
18
150
DL-06, -10, -12 (6.5, 10, 12.5)
DU-10, -12 (10, 12.5)
24
150
DL-06, -10, -12 (6.5, 10, 12.5)
DU-10, -12 (10, 12.5)
34
150
DL, DU-10, -12 (10, 12.5)
54
130
DL-06 (6,5)
600
9
150
DL-06, -10, -12 (6.5, 10, 12.5)
DU-10, -12 (10, 12.5)
18
150
DL-06, -10, -12 (6.5, 10, 12.5)
DU-10, -12 (10, 12.5)
24
150
DL-06, -10, -12 (6.5, 10, 12.5)
DU-10, -12 (10, 12.5)
34
150
DL, DU-10, -12 (10, 12.5)
54
130