167791-BIM-B-0606
46
Unitary Products Group
TABLE 47: DL-06 (6-1/2 TON) STANDARD MOTOR SIDE SHOT BLOWER PERFORMANCE
1
2
ESP
3
TURNS OPEN
4
0
1
2
3
4
5
CFM
W
5
BHP
CFM
BHP
CFM
W
BHP
CFM
W
BHP
CFM
BHP
CFM
BHP
0.4
-
-
-
-
-
-
3367
1216
1.30
3133
1067
1.14
2954
944
1.01
2701
819
0.88
0.6
-
-
-
3208
1239
1.33
2913
1068
1.15
2466
913
0.98
2350
789
0.85
1750
621
0.67
0.8
-
-
-
2651
1058
1.13
2317
894
0.96
1656
700
0.75
-
-
-
-
-
-
1.0
2186
998
1.07
1774
830
0.89
-
-
-
-
-
-
-
-
-
-
-
-
1.
Blower performance for gas heat includes maximum number of heat tubes available for each tonnage.
2.
Blower performance includes two-inch throwaway filters.
3.
ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been
deducted from the total static pressure of the blower.
4.
“Turns Open” refers to the setting of the variable pitch motor sheave, where “0 Turns Open” is fully closed.
5.
W = Watts
TABLE 48: DL-06 (6-1/2 TON) OPTIONAL MOTOR SIDE SHOT BLOWER PERFORMANCE
1
2
ESP
3
TURNS OPEN
4
0
1
2
3
4
5
CFM
W
5
BHP
CFM
W
BHP
CFM
W
BHP
CFM
BHP
CFM
W
BHP
CFM
W
BHP
0.6
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3597
1598
1.71
0.8
-
-
-
-
-
-
-
-
-
-
-
-
3503
1689
1.81
3172
1430
1.53
1.0
-
-
-
-
-
-
3406
1778
1.91
3032
1497
1.61
2248
1143
1.23
1.2
-
-
-
-
-
-
3327
1866
2.00
2926
1578
1.69
2160
1217
1.31
-
-
-
1.4
-
-
-
3270
1971
2.11
2537
1544
1.66
2043
1296
1.39
-
-
-
-
-
-
1.6
3196
2077
2.23
2460
1651
1.77
1858
1318
1.41
-
-
-
-
-
-
-
-
-
1.8
2426
1768
1.90
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1.
Blower performance for gas heat includes maximum number of heat tubes available for each tonnage.
2.
Blower performance includes two-inch throwaway filters.
3.
ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been
deducted from the total static pressure of the blower.
4.
“Turns Open” refers to the setting of the variable pitch motor sheave, where “0 Turns Open” is fully closed.
5.
W = Watts