background image

Y

ORK INTERNA

TIONAL

41

FORM 160.49-O1

SECTION 6

T

R

OUBLESHOO

TING

TABLE 1  –  CAUSES OF NORMAL AND SAFETY SYSTEM SHUTDOWNS IN ACCORDANCE WITH THE MICROCOMPUTER CONTROL, CENTER DISPLAY

SHUTDOWN CAUSE

GOVERNING CONTROL FUNCTION

CONTROL CENTER DISPLAY

OPERATING

PROGRAMMED

START-UP OF

PROBABLE CAUSE

DAY OF

TIME OF

CAUSE OF

METHOD OF

DESCRIPTION

POINT

SETPOINTS

SYSTEM AFTER

AND SERVICE

WEEK

DAY

SHUTDOWN

RESTART

ON

ON

BY OPERATOR

SHUTDOWN

REQUIRED

RISE

FALL

MON.

10:00 AM

Low Water

Autostart

Low Water

Chilled

4°F (2.2°C)

4°F (2.2°C) be-

Automatic Restart

System load is less

Temp.

(LWT)

water

below

low chilled water

when water reaches

than minimum capacity

setpoint

chiller

setpoint (If set

setpoint; if system is

water

to 40°F (4.4°C)

running and setpoint

setpoint

would be 36°F

is increased 4°F, sys-

(2.2°C)) (36°F

tem will continue to

(2.2°C) mini-

run, as LWT cutout

mum)

shifts to a fixed 36°F
for 10 minutes.

MON.

10:00 AM

Flow Switch

Autostart

Flow Switch

Automatic Restart

Lack of water flow.

when water flow is

Check operation of

Restored to close

chilled water pump

flow switch.

MON.

10:00 AM

System

Autostart

A remote com-

Automatic Restart

Contact-connected to

Cycling

mand (computer

upon remote

the Remote/Local

relay contact or

command.

cycling input of the

manual switch)

Digital input board

MON.

10:00 AM

Multi-Unit

Autostart

(Optional) Lead-

Automatic Restart

Contact-connected to

Lag Sequence

upon remote

the Multi-Unit cycling

Control

command.

input of the Digital
input board

MON.

10:00 AM

Internal

Autostart

Internal Clock

Daily Schedule

Will automatically

Pressing Compressor

Clock

Programmed to

restart when pro-

Start Switch over-

Shutdown Unit

grammed schedule

rides the program

permits

MON.

10:00 AM

AC under-

Autostart

<15% FLA for

Cycling shutdown occurs

voltage

25 continuous

when motor current is

seconds

>15% FLA for 25 seconds
during chiller operation

MON.

10:00 AM

Power Fault

Autostart

CM-2 Current

Will start automatic-

Motor Controller contacts

Module or

tically following

opening and closing in

Solid State

coastdown

less than 3 seconds due to

Starter

a power fault condition

Remote Stop

Energy manage-

Start up by start

Remote Stop Contact

ment  System

signal from remote

Closure

start switch

MON.

Anti-Recycle,

Anti-Recycle

Will not start

Will restart when

Min. Time between

20 Min. Left

timer

until 30 Min.

time left = 00 Min.

successive compres-

timer is timed

sor starts is 30 min.

MON.

10:00 AM

Low Evap.

Low Evap.

54..3 PSIG 54.4 PSIG

To restart press com-

See OPERATION

Pressure

Pressure

(374.4 kPa)

(375 kPa)

pressor switch from

ANALYSIS TABLE 2

Transducer

(R-22)

(R-22)

STOP/RESET to

Symptom 2.

(LEP)

25 PSIG

25.1 PSIG

START position.

(172.4 kPa)

(173 kPa)

(R-134a)

(R-134a)

(Continued on Page 42)

Содержание CodePak YK L1 L1 G4

Страница 1: ...ONL R 134a COOLING ONL R 134a COOLING ONL R 134a COOLING ONLY Y Y Y Y WITH MICROCOMPUTER CONTROL CENTER P WITH MICROCOMPUTER CONTROL CENTER P WITH MICROCOMPUTER CONTROL CENTER P WITH MICROCOMPUTER CO...

Страница 2: ...er 160 49 PW5 Wiring Diagram With Solid State Starter 160 49 PW6 STYLES A B YK N2 N1 H1 CX A DESIGN LEVEL A or B POWER SUPPLY for 60 Hz 5 for 50 Hz COMPRESSOR CODE G4 H0 H1 H2 J1 J2 J3 J4 CONDENSER CO...

Страница 3: ...y packaged YORK Solid State Starter op tional In operation a liquid water or brine to be chilled flows through the CodePak cooler where boiling refrigerant absorbs heat from the water The chilled liqu...

Страница 4: ...chilled liquid tempera ture leaving the cooler Prerotation vanes PRV lo cated at the entrance to the compressor impeller com pensate for variation in load See Fig 2 Detail A The position of these vane...

Страница 5: ...r action may be required to correct the interference Additionally any electronic equipment can generate EMI electromagnetic interference which depending upon the installation and magnitude may affect...

Страница 6: ...r alphanumeric display The system setpoints are CHILLED LIQUID TEMPERATURE LCWT INTRODUCTION CURRENT LIMIT PULLDOWN DEMAND LIMIT CLOCK TIME OF DAY DAILY SCHEDULE 7 DAY TIME CLOCK PROGRAM MING HOLIDAY...

Страница 7: ...R VICE 1 Service allows manual PRV control with visual display readout of PRV operation 2 Local allows manual compressor start from the COMPRESSOR switch on the Control Center front 3 Program allows o...

Страница 8: ...c display message EVAP XXX X PSIG COND XXX X PSIG To Display OIL PRESSURE Use OIL PRESSURE display key as described on page 7 to produce the following alphanumeric dis play message OIL PRESSURE XXXX X...

Страница 9: ...tional printers To Display MOTOR CURRENT Press the MOTOR CURRENT display key as described above to display motor current as a per cent of Full Load Amps FLA The message is as follows MOTOR CURRENT XXX...

Страница 10: ...liday see description under HOLIDAY setpoint and the Con trol Center can be programmed usually DAILY SCHED ULE setpoint to automatically start and stop the chiller on those days so designated The oper...

Страница 11: ...435 415 335 362 454 453 440 480 370 400 524 523 550 600 460 502 655 654 SupplyVoltage NONE 0 NONE 0 Range Disabled NOTE The value displayed is the actual LCWT set point For example the value displayed...

Страница 12: ...ribed in the beginning of this section to produce the following message S_ M_ T_ W_ T_ F_ S_ HOLIDAY NOTED BY NOTE On the days that are designated by an the chiller will automatically start and stop p...

Страница 13: ...ed by pressing the ACCESS CODE key again the operator will have ac cess to the PROGRAM key for 10 minutes When 10 minutes have elapsed access to PROGRAM key will be automatically dis abled and the ope...

Страница 14: ...int Electro Mechanical Starter refer to Fig 7 1 Press and release CURRENT LIMIT setpoint key The following program prompt message is displayed CURRENT LIMIT XXX FLA 2 Use Entry keys to enter desired v...

Страница 15: ...INT To Enter CLOCK Setpoint Refer to Fig 9 1 Assure Micro Board Program jumper J57 is in CLKON position 2 Press and release CLOCK setpoint key The fol lowing program prompt message is displayed TODAY...

Страница 16: ...PM key to change AM to PM or vice versa 3 Press and release ADVANCE DAY SCROLL key The following prompt message is displayed MON START XX XX AM STOP XX XX AM 4 Enter the desired start and stop time pe...

Страница 17: ...1 press CANCEL key and then press EN TER key PROGRAM MODE SELECT SETPOINT message is displayed To cancel one of the designated holidays perform Step 1 press ADVANCE DAY SCROLL key until the cursor app...

Страница 18: ...se this key to put the pre rotation vanes under LCWT control as long as the cur rent limit setpoint is not reached which causes the current limit function to override the LCWT control If system is run...

Страница 19: ...gain pressed and re leased Message No 3 is then displayed and updated every 2 seconds until either the DISPLAY DATA key is again pressed and released whereupon message No 1 is displayed or the DISPLAY...

Страница 20: ...10 The mode that has been previously selected will be displayed as follows LOCAL MODE SELECTED or SERVICE MODE SELECTED or REMOTE MODE SELECTED 11 Press ADVANCE DAY key to scroll to desired mode Each...

Страница 21: ...ing to maintain the leaving chilled water temperature set point or The operator has pressed the vanes OPEN key on the keypad SYSTEM RUN VANES CLOSING Displayed when the chiller is running the MicroCom...

Страница 22: ...that the system is not running but will start upon application of a start signal SYSTEM SHUTDOWN PRESS STATUS Displayed when chiller is shut down on a cycling shut down safety shutdown operator must...

Страница 23: ...y pressing the COMPRESSOR switch to the START position REMOTE STOP This message will be displayed when a remote device typically an Energy Management System has com manded the chiller to shut down The...

Страница 24: ...y the motor controller con tacts CM 1 opening and reclosing in one second If Solid State Starter application the shutdown could have been caused by any of the following reasons The ap propriate light...

Страница 25: ...key Or the message will be cleared by initiating a compressor start START SEQUENCE INITIATED Indicates that the Micro Board has received a local or remote start signal and has initiated the chiller st...

Страница 26: ...Auto Zeroing Sequence that occurs 10 seconds after a chiller start is initiated Message is displayed immedi ately after the Auto Zeroing sequence has completed This indicates that one of the transduce...

Страница 27: ...voltage in creases to greater than 19 7VDC MON XX XX AM AUX SAFETY SHUTDOWN The system is shut down because an external device connected to digital input boardTB1 31 Auxiliary Safety Shutdown Input h...

Страница 28: ...MANUAL OIL PUMP key to stop the operation of the oil pump for less than 10 minutes of operation 3 Pre Rotation Vanes To perform this test the starter interlock terminals 3 and 4 must be jump ered to...

Страница 29: ...late oil for a 50 second pre run to establish oil flow and adequate lubrication to all bearings gears and rotating sur faces within the compressor The high and low oil pressure transducers OP and the...

Страница 30: ...vent the Pre rotation Vanes from opening beyond the CURRENT LIMIT setting If the load continues to decrease after the Prerotation Vanes are entirely closed the CodePak will be shut down by the Low Wat...

Страница 31: ...load require ments 2 Be sure the oil pump is operating while unit is run ning 3 Check Oil Pressure display A gradual decrease in bearing oil pressure of 5 to 10 psi 34 5 to 69 kPa with constant sucti...

Страница 32: ...nd leaving chilled liquid tem peratures and evaporator pressure for comparison with job design conditions This can be accomplished by pressing the CHILLED LIQUID TEMPS key and the REFRIGERANT PRESSURE...

Страница 33: ...f auto restart programming jumper is not installed on the Micro Board Low Evaporator Pressure Low Oil Pressure High Condenser Pressure Evaporator Transducer or Probe Error High Discharge Temp High Oil...

Страница 34: ...lled water system chilled water pump and coils Open the drains on the cooler and condenser liquid heads to assure complete drainage If Solid State Starter drain water from starter cooling loop 3 Move...

Страница 35: ...RGE LINE PRE ROTATIONVANE ACTUATOR CONDENSER OIL COOLER OIL RESERVOIR PUMP SUB COOLER OIL PUMP STARTER 27073A 27073A COM PRESSOR ADAPTER MOTOR SUPPORT COVER MOTOR COOLER REFRIGERANT CHARGINGVALVE DEHY...

Страница 36: ...d system consists of the oil pump oil filter oil cooler and all interconnecting oil piping and passages There are main points within the motor compressor which must be supplied with forced lubrication...

Страница 37: ...or independent of the evaporator shell to en sure controlled alignment of the assembly Motor is mounted with final alignment at start up Motor drive shaft is directly connected to the com pressor shaf...

Страница 38: ...38 YORK INTERNATIONAL FIG 18 SCHEMATIC DRAWING YK COMPRESSOR LUBRICATION SYSTEM LD01079...

Страница 39: ...or with lock and key Electrical lugs for incoming power wiring are provided SECTION 5 OPERATIONAL MAINTENANCE OIL RETURN SYSTEM The oil return system continuously maintains the proper oil level in the...

Страница 40: ...nnection at the charging valve until after the air is forced out by pumping a few strokes of the oil pump This fills the lines with oil and prevents air from being pumped into the system 3 Open the oi...

Страница 41: ...of the manual switch Digital input board MON 10 00 AM Multi Unit Autostart Optional Lead Automatic Restart Contact connected to Lag Sequence upon remote the Multi Unit cycling Control command input of...

Страница 42: ...start up MON 10 00 AM Motor Con CM2 or Solid Reset the device CM2 or Solid State troller Ext State Starter that caused the shut Starter has shutdown Reset RT2 down Chiller will chiller start automatic...

Страница 43: ...tor Current Press compressor Check motor starter Malfunction 15 for 10 swc STOP RESET operation Motor current Detected with Control Cen switch and then value greater than 15 ter not calling for FLA mo...

Страница 44: ...normal with normal discharge temperature Temperature of chilled water too low with Insufficient load for Check prerotation vane motor opera with low motor amperes system capacity tion and setting of l...

Страница 45: ...me extremely noisy quantity 8 SYMPTOM OIL PRESSURE GRADUALLY DECREASES Noted by Observation of Daily Log Sheets Oil pressure noted when pressing OIL Oil filter is dirty Change oil filter PRESSURE disp...

Страница 46: ...electronic leak detector can be used to detect any leaks too small to be found by the soap test To test with R 22 proceed as follows 1 With no pressure in the system charge R 22 gas into the system t...

Страница 47: ...mosphere 14 696 PSIA 760 mm Hg absolute pressure at 32 F 29 921 inches Hg absolute at 32 F NOTES PSIA Lbs per sq in gauge pressure Pressure above atmosphere PSIA Lbs per sq in absolute pressure Sum of...

Страница 48: ...c tive method for evacuating and dehydrating a system in the field Although there are several methods of de hydrating a system we are recommending the follow ing as it produces one of the best results...

Страница 49: ...of the drum or cylinder must be admitted to the system pressure until the sys tem pressure is raised above the point corresponding to the freezing point of the cooler liquid For water the pressure cor...

Страница 50: ...ith the method shown under the Refrigerant Charging on page 49 The refrigerant level should be observed and the level recorded after initial charging HANDLING REFRIGERANT FOR DISMANTLING AND REPAIRS I...

Страница 51: ...YORK INTERNATIONAL 51 FORM 160 49 O1 FIG 24 MOTOR STATOR TEMPERATURE AND INSULATION RESISTANCES 110 43 3 100 37 8 90 32 2 80 26 7 70 21 1 60 15 6 50 10 0 40 4 4 TEMPERATURE F C LD01086...

Страница 52: ...pressure over a period of time accompanied by a steady rise in con densing temperature and noisy operation These symp toms may also be due to foul gas buildup Purging will remove the foul gas reveali...

Страница 53: ...nds of all tubes with water NOTE Do not use carbon tetrachloride for this pur pose since its fumes give the same flame discoloration that the refrigerant does 3 With nitrogen or dry air blow out the t...

Страница 54: ...icted oil lines passages or dirty oil fil ters If the unit is shutting down on HOT High Oil Temperature or Low Oil Pressure OP change the oil filter element Examine the oil filter element for the pres...

Страница 55: ...e maintained tight are systems that provide trouble free efficient opera tion COOLER AND CONDENSER The major portion of maintenance on the condenser and cooler will deal with the maintaining the water...

Страница 56: ...y not be changed If the set tings are changed without YORK s approval the warranty will be jeopardized 3 A 5 11 year life battery is part of the RTC Real Time Clock To replace refer to page 25 Proud S...

Отзывы: