![York CodePak YK L1 L1 G4 Скачать руководство пользователя страница 17](http://html1.mh-extra.com/html/york/codepak-yk-l1-l1-g4/codepak-yk-l1-l1-g4_operation-manual_3501885017.webp)
YORK INTERNATIONAL
17
FORM 160.49-O1
To Enter HOLIDAY Setpoint: (Refer to Fig. 11.)
1. Press and release HOLIDAY setpoint key. The fol-
lowing program prompt message is displayed:
S_ M_ T_ W_ T_ F_ S_ HOLIDAY NOTED BY
r
2. Press and release ADVANCE DAY/SCROLL key
to move cursor to the day that you wish to desig-
nate as a holiday.
3. Press and release
r
Entry key. An
r
will appear
next to the selected day.
4. After you have placed an
r
next to each of the
days that you wish to designate a holiday, press
ENTER key
PROGRAM MODE, SELECT SETPOINT
message is displayed.
To cancel all of the designated holidays: perform
Step 1, press CANCEL key, and then press EN-
TER key.
PROGRAM MODE, SELECT SETPOINT
message is displayed.
To cancel one of the designated holidays: perform
Step 1, press ADVANCE DAY / SCROLL key until
the cursor appears to the right of the desired day,
press the
r
key, then press the ENTER key.
FIG. 11 – KEYPAD – PROGRAMMING “HOLIDAY”
SETPOINT
To Enter REMOTE/ RESET TEMP RANGE Setpoint:
(Refer to Fig. 12.)
1. Press and release REMOTE/RESET TEMP RANGE
setpoint key. The following program prompt mes-
sage is displayed:
REMOTE TEMP SETPOINT RANGE = XX °F (°C)
2. Use Entry keys desired value (10° or 20°F) or (5.5°
or 11.1°C).
3. Press and release ENTER key.
PROGRAM MODE, SELECT SETPOINT
message is displayed.
FIG. 12 – KEYPAD – PROGRAMMING “REMOTE
RESET” TEMP RANGE
To Enter DATA LOGGER Setpoint:
Refer to Form 160.49-N2 for operation of this key.
LD01074
LD01075