FAULT/STATUS CODE OUTDOOR SYSTEM TROUBLE SHOOTING
TABLE 7:
Outdoor Control Faults/Status Code Display
Outdoor Control Description
LED
1
Outdoor Display Text
Left Triangle
Indication
(Outdoor Screen)
Right Triangle
Indication
(Outdoor Screen)
Control Fault
Outdoor Control Failure
RED
(solid)
CONTROL FAILURE
–
–
Operational Faults
High-pressure switch fault (not in lockout yet)
RED
(solid)
HPS - OPEN
–
X
System in high-pressure switch lockout (last
mode of operation was normal compressor)
RED
(solid)
HPS SOFT LOCKOUT - NORMAL
–
X
System in high-pressure switch lockout (last
mode of operation was normal compressor)
RED
(solid)
HPS HARD LOCKOUT - NORMAL
–
X
System in high-pressure switch lockout (last
mode of operation was defrost)
RED
(solid)
HPS SOFT LOCKOUT - DEFROST
–
X
System in high-pressure switch lockout (last
mode of operation was defrost)
RED
(solid)
HPS HARD LOCKOUT - DEFROST
–
X
Low Voltage (<19 VAC)
RED
(solid)
LOW VOLTAGE – BELOW 19VAC
–
–
Inverter Control Communications Fault
RED
(solid)
COMMUNICATIONS LOST -
INVERTER DRIVE
–
–
JCI RS-485 Communications Lost
RED
(solid)
COMMUNICATIONS LOST –
SYSTEM MASTER
–
–
Repair part tonnage selection does not match
the stored value programmed in the JCI factory
RED
(solid)
INVERTER CONFIGURATION ERROR
–
–
Inverter Model Number installed does not
match the stored tonnage in EEPROM
RED
(solid)
INVERTER MODEL INSTALLATION
ERROR – HARD LOCKOUT
–
–
Required Sensor or Switch Faults
Outdoor ambient sensor failure (short)
RED
(solid)
OUTDOOR AMBIENT SENSOR -
SHORT – SOFT LOCKOUT
–
–
Outdoor ambient sensor failure (open)
RED
(solid)
OUTDOOR AMBIENT SENSOR –
OPEN – SOFT LOCKOUT
–
–
Coil sensor failure (short) not in lockout yet
RED
(solid)
COIL TEMP SENSOR - SHORT
–
X
Coil sensor failure (short)
RED
(solid)
COIL TEMP SENSOR -
SHORT – SOFT LOCKOUT
–
X
Coil sensor failure (open) not in lockout yet
RED
(solid)
COIL TEMP SENSOR - OPEN
–
X
Coil sensor failure (open)
RED
(solid)
COIL TEMP SENSOR -
OPEN – SOFT LOCKOUT
–
X
Liquid line temperature sensor failure (short)
not in lockout yet
RED
(solid)
LIQUID TEMP SENSOR -
SHORT
–
X
Liquid line temperature sensor failure (short)
RED
(solid)
LIQUID TEMP SENSOR -
SHORT – SOFT LOCKOUT
–
X
Liquid line temperature sensor failure (open)
not in lockout yet
RED
(solid)
LIQUID TEMP SENSOR - OPEN
–
X
Liquid line temperature sensor failure (open)
RED
(solid)
LIQUID TEMP SENSOR -
OPEN – SOFT LOCKOUT
–
X
Discharge temperature sensor failure (short)
RED
(solid)
DISCHARGE TEMP SENSOR -
SHORT
–
X
Discharge temperature sensor failure (open)
not in lockout yet
RED
(solid)
DISCHARGE TEMP SENSOR - OPEN
–
X
Discharge temperature sensor failure (open)
RED
(solid)
DISCHARGE TEMP SENSOR –
OPEN – SOFT LOCKOUT
–
X
Suction temperature sensor failure (short) not
in lockout yet
RED
(solid)
SUCTION TEMP SENSOR - SHORT
X
–
Suction temperature sensor failure (short)
RED
(solid)
SUCTION TEMP SENSOR –
SHORT – SOFT LOCKOUT
X
–
Suction temperature sensor failure (open) not
in lockout yet
RED
(solid)
SUCTION TEMP SENSOR – OPEN
X
–
Continued on next page.