Table 11: ZXA7, 08 to 14 Standard Static Indoor Blower - Without Powered Convenience Outlet
Compressor 1
Compressor 2
Electric Heat Field
Installed Kit 2EK045*
4
Min Disconnect Rating
Min Disconnect Rating
/ Pwr Exh
Si
ze
(T
on
s)
N
om
in
al
U
ni
t V
ol
ta
ge
RLA LRA MCC RLA LRA MCC
OD Fan Motors (each)
Supply Blower Motor
Pwr Exh Motor
Pwr Conv Outlet
Model kW Stages Amps
1
MCA
(Amps)
2, 3
Min Fuse
/ Breaker
Size (Amps)
Max Fuse
/ Breaker
Size (Amps)
FLA LRA
MCA
w/Pwr Exh (Amps)
Min Fuse
/ Breaker
Size w/ Pwr Exh (Amps)
Max Fuse
/ Breaker
Size w/ Pwr Exh (Amps)
FLA LRA
None
-
-
-
58.8
60
70
62 371
61
70
70
65 381
11725 12
1
33.3
58.8
60
70
62 371
61
70
70
65 381
12525 18.6
1
51.6
75.6
80
80
70 371
78.4
80
80
72 381
13225 24
1
66.6
94.4
100
100
87 371
97.1
100 100 89 381
208-3-60 19.6 136 31 19.6 136
31
5.8
8.9
1.1
14225 31.8
2
88.3
121.5
125
125
112 371
124.3
125 125 114 381
None
-
-
-
57.5
60
70
60 370
59.5
60
70
63 375
11725 16
1
38.5
58.4
60
70
60 370
60.9
70
70
63 375
12525 24.8
1
59.7
84.9
90
90
78 370
87.4
90
90
80 375
13225 32
1
77
106.5
110
110
98 370
109
110 110 100 375
230-3-60 19.6 136 31 19.6 136
31
5.2
8.2
1
14225 42.4
2
102
137.8
150
150
127 370
140.3
150 150 129 375
None
-
-
-
25.5
30
30
27 178
26.5
30
30
28 180
11746 16.5
1
19.8
29.9
30
30
27 178
31.1
35
35
29 180
12846 27.8
1
33.4
46.9
50
50
43 178
48.1
50
50
44 180
13346 33
1
39.7
54.8
60
60
50 178
56
60
60
52 180
460-3-60 8.2 66.1 13
8.2 66.1 13
2.9
4.1
0.5
14246 41.7
2
50.2
67.9
70
70
62 178
69.1
70
70
64 180
None
-
-
-
20.3
25
25
21 148
21.1
25
25
22 150
11758 17
1
16.4
24.5
25
25
23 148
25.5
30
30
23 150
14
(12.5)
575-3-60 6.6 55.3 10
6.6 55.3 10
2.2
3.2
0.4
13458 34
1
32.7
44.9
45
45
41 148
45.9
50
50
42 150
1
Minimum Circuit Ampacity.
2
Dual Element, Time Delay Type.
3
HACR type per NEC.
4
Non-fused Disconnect. Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field
installed electric heat kits may exceed the factory installed disconnect amperage rating.
INSTALLATION MANUAL ZX SERIES 6 - 12.5 Ton 60 Hertz R-410A
43
Johnson Controls Ducted Systems
Содержание ZX Series
Страница 2: ...2 INSTALLATION MANUAL ZX SERIES 6 12 5 Ton 60 Hertz R 410A Johnson Controls Ducted Systems ...
Страница 104: ...Start Up Sheet INSTALLATION MANUAL ZX SERIES 6 12 5 Ton 60 Hertz R 410A 104 Johnson Controls Ducted Systems ...
Страница 105: ...INSTALLATION MANUAL ZX SERIES 6 12 5 Ton 60 Hertz R 410A 105 Johnson Controls Ducted Systems ...
Страница 106: ...INSTALLATION MANUAL ZX SERIES 6 12 5 Ton 60 Hertz R 410A 106 Johnson Controls Ducted Systems ...
Страница 107: ...INSTALLATION MANUAL ZX SERIES 6 12 5 Ton 60 Hertz R 410A 107 Johnson Controls Ducted Systems ...
Страница 108: ...INSTALLATION MANUAL ZX SERIES 6 12 5 Ton 60 Hertz R 410A 108 Johnson Controls Ducted Systems ...
Страница 109: ...INSTALLATION MANUAL ZX SERIES 6 12 5 Ton 60 Hertz R 410A 109 Johnson Controls Ducted Systems ...