Table 6: ZXA7, 08 to 14 Standard Static Indoor Blower - With Powered Convenience Outlet
Compressor 1
Compressor 2
Electric Heat Field
Installed Kit 2EK045*
4
Min Disconnect Rating
Min Disconnect Rating
/ Pwr Exh
Si
ze
(T
on
s)
N
om
in
al
U
ni
t V
ol
ta
ge
RLA LRA MCC RLA LRA MCC
OD Fan Motors (each)
Supply Blower Motor
Pwr Exh Motor
Pwr Conv Outlet
Model kW Stages Amps
1
MCA
(Amps)
2, 3
Min Fuse
/ Breaker
Size (Amps)
Max Fuse
/ Breaker
Size (Amps)
FLA LRA
MCA
w/Pwr Exh (Amps)
Min Fuse
/ Breaker
Size w/ Pwr Exh (Amps)
Max Fuse
/ Breaker
Size w/ Pwr Exh (Amps)
FLA LRA
None
-
-
-
51.5
60
60
55 304
53.7
60
60
57 314
11725 12
1
33.3
55.8
60
60
55 304
58.5
60
60
57 314
12525 18.6
1
51.6
78.6
80
80
72 304
81.4
90
90
75 314
13225 24
1
66.6
97.4
100
100
90 304
100.1
110 110 92 314
208-3-60 16 110 25 15.6 110
24
2.3
7
1.1
8.6
14225 31.8
2
88.3
124.5
125
125
115 304
127.3
150 150 117 314
None
-
-
-
51.7
60
60
55 306
53.7
60
60
57 301
11725 16
1
38.5
62.5
70
70
58 306
65
70
70
60 301
12525 24.8
1
59.7
89
90
90
82 306
91.5
100 100 84 301
13225 32
1
77
110.6
125
125
102 306
113.1
125 125 104 301
230-3-60 16 110 25 15.6 110
24
2.3
7.2
1
8.6
14225 42.4
2
102
141.9
150
150
131 306
144.4
150 150 133 301
None
-
-
-
26
30
30
28 149
27
30
30
29 145
11746 16.5
1
19.8
31.9
35
35
29 149
33.2
35
35
31 145
12846 27.8
1
33.4
48.9
50
50
45 149
50.2
60
60
46 145
13346 33
1
39.7
56.8
60
60
52 149
58.1
60
60
53 145
460-3-60 7.8 52
12
7.8 52
12
1.3
3.6
0.5
8.6
14246 41.7
2
50.2
69.9
70
70
64 149
71.2
80
80
65 145
None
-
-
-
19.4
20
25
21 107
20.2
25
25
22 104
11758 17
1
16.4
25.8
30
30
24 107
26.8
30
30
25 104
12 (10)
575-3-60 5.7 38.9
9
5.8 38.9
9
1.1
2.5
0.4
8.6
13458 34
1
32.7
46.2
50
50
42 107
47.2
50
50
43 104
None
-
-
-
63.1
70
80
67 375
65.3
70
80
69 385
11725 12
1
33.3
63.1
70
80
67 375
65.3
70
80
69 385
12525 18.6
1
51.6
81
90
90
75 375
83.8
90
90
77 385
13225 24
1
66.6
99.8
100
100
92 375
102.5
110 110 94 385
208-3-60 19.6 136 31 19.6 136
31
5.8
8.9
1.1
8.6
14225 31.8
2
88.3
126.9
150
150
117 375
129.6
150 150 119 385
None
-
-
-
61.8
70
80
65 374
63.8
70
80
68 379
11725 16
1
38.5
63.8
70
80
65 374
66.3
70
80
68 379
12525 24.8
1
59.7
90.3
100
100
83 374
92.8
100 100 85 379
13225 32
1
77
111.9
125
125
103 374
114.4
125 125 105 379
230-3-60 19.6 136 31 19.6 136
31
5.2
8.2
1
8.6
14225 42.4
2
102
143.1
150
150
132 374
145.6
150 150 134 379
None
-
-
-
27.7
30
35
29 180
28.7
30
35
31 182
11746 16.5
1
19.8
32.6
35
35
30 180
33.8
35
35
31 182
12846 27.8
1
33.4
49.6
50
50
46 180
50.8
60
60
47 182
13346 33
1
39.7
57.4
60
60
53 180
58.7
60
60
54 182
460-3-60 8.2 66.1 13
8.2 66.1 13
2.9
4.1
0.5
8.6
14246 41.7
2
50.2
70.6
80
80
65 180
71.8
80
80
66 182
None
-
-
-
22
25
25
23 150
22.8
25
25
24 152
11758 17
1
16.4
26.7
30
30
25 150
27.7
30
30
25 152
14
(12.5)
575-3-60 6.6 55.3 10
6.6 55.3 10
2.2
3.2
0.4
8.6
13458 34
1
32.7
47
50
50
43 150
48
50
50
44 152
1
Minimum Circuit Ampacity.
2
Dual Element, Time Delay Type.
3
HACR type per NEC.
4
Non-fused Disconnect. Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field
installed electric heat kits may exceed the factory installed disconnect amperage rating.
INSTALLATION MANUAL ZX SERIES 6 - 12.5 Ton 60 Hertz R-410A
28
Johnson Controls Ducted Systems
Содержание ZX Series
Страница 2: ...2 INSTALLATION MANUAL ZX SERIES 6 12 5 Ton 60 Hertz R 410A Johnson Controls Ducted Systems ...
Страница 104: ...Start Up Sheet INSTALLATION MANUAL ZX SERIES 6 12 5 Ton 60 Hertz R 410A 104 Johnson Controls Ducted Systems ...
Страница 105: ...INSTALLATION MANUAL ZX SERIES 6 12 5 Ton 60 Hertz R 410A 105 Johnson Controls Ducted Systems ...
Страница 106: ...INSTALLATION MANUAL ZX SERIES 6 12 5 Ton 60 Hertz R 410A 106 Johnson Controls Ducted Systems ...
Страница 107: ...INSTALLATION MANUAL ZX SERIES 6 12 5 Ton 60 Hertz R 410A 107 Johnson Controls Ducted Systems ...
Страница 108: ...INSTALLATION MANUAL ZX SERIES 6 12 5 Ton 60 Hertz R 410A 108 Johnson Controls Ducted Systems ...
Страница 109: ...INSTALLATION MANUAL ZX SERIES 6 12 5 Ton 60 Hertz R 410A 109 Johnson Controls Ducted Systems ...