Table 8: ZXA7, 08 to 14 High Static Indoor Blower - Without Powered Convenience Outlet
Compressor 1
Compressor 2
Electric Heat Field
Installed Kit 2EK045*
4
Min Disconnect Rating
Min Disconnect Rating
/ Pwr Exh
Si
ze
(T
on
s)
N
om
in
al
U
ni
t V
ol
ta
ge
RLA LRA MCC RLA LRA MCC
OD Fan Motors (each)
Supply Blower Motor
Pwr Exh Motor
Pwr Conv Outlet
Model kW Stages Amps
1
MCA
(Amps)
2, 3
Min Fuse
/ Breaker
Size (Amps)
Max Fuse
/ Breaker
Size (Amps)
FLA LRA
MCA
w/Pwr Exh (Amps)
Min Fuse
/ Breaker
Size w/ Pwr Exh (Amps)
Max Fuse
/ Breaker
Size w/ Pwr Exh (Amps)
FLA LRA
None
-
-
-
63.4
70
80
67 397
65.6
70
80
70 407
11725 12
1
33.3
63.4
70
80
67 397
65.6
70
80
70 407
12525 18.6
1
51.6
81.4
90
90
75 397
84.1
90
90
77 407
13225 24
1
66.6
100.1
110
110
92 397
102.9
110 110 95 407
208-3-60 19.6 136 31 19.6 136
31
5.8
13.5
1.1
14225 31.8
2
88.3
127.3
150
150
117 397
130
150 150 120 407
None
-
-
-
62.7
70
80
66 393
64.7
70
80
69 398
11725 16
1
38.5
64.9
70
80
66 393
67.4
70
80
69 398
12525 24.8
1
59.7
91.4
100
100
84 393
93.9
100 100 86 398
13225 32
1
77
113
125
125
104 393
115.5
125 125 106 398
230-3-60 19.6 136 31 19.6 136
31
5.2
13.4
1
14225 42.4
2
102
144.3
150
150
133 393
146.8
150 150 135 398
None
-
-
-
28.1
30
35
30 194
29.1
30
35
31 196
11746 16.5
1
19.8
33.1
35
35
30 194
34.4
35
35
32 196
12846 27.8
1
33.4
50.1
60
60
46 194
51.4
60
60
47 196
13346 33
1
39.7
58
60
60
53 194
59.3
60
60
55 196
460-3-60 8.2 66.1 13
8.2 66.1 13
2.9
6.7
0.5
14246 41.7
2
50.2
71.1
80
80
65 194
72.4
80
80
67 196
None
-
-
-
22.5
25
25
24 162
23.3
25
25
25 164
11758 17
1
16.4
27.3
30
30
25 162
28.3
30
30
26 164
14
(12.5)
575-3-60 6.6 55.3 10
6.6 55.3 10
2.2
5.4
0.4
13458 34
1
32.7
47.6
50
50
44 162
48.6
50
50
45 164
1
Minimum Circuit Ampacity.
2
Dual Element, Time Delay Type.
3
HACR type per NEC.
4
Non-fused Disconnect. Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field
installed electric heat kits may exceed the factory installed disconnect amperage rating.
INSTALLATION MANUAL ZX SERIES 6 - 12.5 Ton 60 Hertz R-410A
34
Johnson Controls Ducted Systems
Содержание ZX Series
Страница 2: ...2 INSTALLATION MANUAL ZX SERIES 6 12 5 Ton 60 Hertz R 410A Johnson Controls Ducted Systems ...
Страница 104: ...Start Up Sheet INSTALLATION MANUAL ZX SERIES 6 12 5 Ton 60 Hertz R 410A 104 Johnson Controls Ducted Systems ...
Страница 105: ...INSTALLATION MANUAL ZX SERIES 6 12 5 Ton 60 Hertz R 410A 105 Johnson Controls Ducted Systems ...
Страница 106: ...INSTALLATION MANUAL ZX SERIES 6 12 5 Ton 60 Hertz R 410A 106 Johnson Controls Ducted Systems ...
Страница 107: ...INSTALLATION MANUAL ZX SERIES 6 12 5 Ton 60 Hertz R 410A 107 Johnson Controls Ducted Systems ...
Страница 108: ...INSTALLATION MANUAL ZX SERIES 6 12 5 Ton 60 Hertz R 410A 108 Johnson Controls Ducted Systems ...
Страница 109: ...INSTALLATION MANUAL ZX SERIES 6 12 5 Ton 60 Hertz R 410A 109 Johnson Controls Ducted Systems ...