76-QD7913EN-00Y00-03.doc
31
Terminal Block Connecting Diagram
(13)
(14)
(15)
(16)
(17)
(18)
(19)
(20)
(21)
(22)
(23)
(24)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
9. Assignment of output relay and input terminal
* Current capacity available from DC 24V (Pin 1 and 2, 12) is max. 100mA in total.
* Since the Photocoupler is bi-directional, both interfaces, i.e. NPN (sink) and PNP (sourcing), are available
depending on the connection of COM.
* When connecting with NPN output, add the wire between No. 2 (+24V) and No. 3 (IN COM). See the left
figure below.
When connecting with PNP output, add the wire between No. 3 (IN COM) and No. 12 (24V return). See the
right figure below.
* Terminal block: Main unit: 163391000,
Wire connector: 1606740000, 1640030000 (manufactured by Weidmuller), one each used
No.
Pin assignment
Pin assignment
ピンアサイン
No.
13
RY1
+24V
1
14
RY1-RY2 COM
+24V
2
15
RY2
IN COM
3
16
RY3
IN 1
4
17
RY3-RY4 COM
IN 2
5
18
RY4
IN 3
6
19
RY5
IN 4
7
20
RY5-RY6 COM
IN 5
8
21
RY6
IN 6
9
22
RY7
IN 7
10
23
RY7-RY8 COM
IN 8
11
24
RY8
24V return
12
NPN connection
PNP connection