2-5
IM 01C50C05-01EN
2.7 Installation of Explosion Protected Type Transmitters
In this section, further requirements and differences and for explosion
protected type instrument are described. For explosion protected type
instrument, the description in this chapter is prior to other description in this
user’s manual.
CAUTION
To preserve the safety of explosion protected type instrument requires
great care during mounting, wiring.
Safety requirements also place restrictions on maintenance and repair
activities. Please read the following sections very carefully.
2.7.1 ATEX Certification
See Appendix.1 ATEX Installation drawing YTA70PQA01
2.7.2 FM Certification
See Appendix.2 FM Installation drawing YTA70PQF01
2.7.3 IECEx Certification
See Appendix.3 IECEx Installation drawing YTA70PQI01
2.7.4 CSA Certification
See Appendix.4 CSA Installation drawing YTA70PQC01
2.7.5 Label of Explosion Protected Type
See Appendix.5 Label of Explosion Protected Type
NOTE
The YTA70P is a single sensor input model.
Please ignore the loop construction of CH2.