background image

 

 IM 61A YHC1-E-A  

3rd Edition: May 2008  

Page 9 of 34 

 

1 Lockout:

 Indicates Enable / Disable status of Master Lockout feature. 

 
2 PV Prompt: 

In addition to the primary variable, multivariable HART devices have secondary,  

    tertiary, and sometimes more variables. When PV Prompt on the Lockout screen is  
   “Disabled” and a Save command is issued by the YHC, the handheld saves only the  
    primary variable. When PV Prompt is “Enabled” and a Save command is issued, the  
    handheld saves the HART parameter information for all variables present. The factory  
    default for PV Prompt on the Lockout screen is “Disabled”. 
 

3 View Details: 

This option takes the user to the 

Lockout Details

 screen listing all YHC parameters 

that can be protected by lockout (see above right). Individual functions can be locked or, if preferred, 
the lockout can be set to deny unauthorized access to all parameters. Press the number of the desired 
menu item to toggle between Enabled and Disabled. Once satisfied with the setting, press the 

Back

 

soft key to return to the 

Lockouts

 screen. 

 
To enable the lockout options selected, be sure the display reads “1 Lockout:    Enabled”. If it does not, press 
the 

Chng

 soft key to toggle from “Disabled” to “Enabled”.  A prompt will appear to “Enter Code:    0  0  0”. 

 

Lockout Code

  

At this point the user will be prompted to enter a 3-digit lockout code.  This code will be required to gain 
access and change any menu item previously locked out. 

The number keys of the YHC will not work 

here.

 Use the 

Inc

rement,

 Dec

rement

 

and 

Next

 Soft Keys to input a lockout code value.  Alternatively you 

may use the                       green keys for 

Inc

rement and 

Dec

rement functions. When you are satisfied with 

the lockout code value, press 

Store.

  

IMPORTANT: After the code is entered, the user must cycle the 

power to activate the lockout! 

BE SURE TO SAVE THIS CODE IN A SAFE PLACE IN THE EVENT YOU FORGET 

THE NUMBER. ACCESS TO LOCKED-OUT FEATURES WILL BE DENIED WITHOUT THE PROPER CODE.

 

 
Note: the YHC is shipped with a factory lockout code of 3 2 1. The user must enter this code the first time 
Lockout is used. 

 
Disable Lockout 

When you wish to use a function or edit a value that is protected by the lockout code, enter the three digit 
Lockout code when prompted and press 

Save

. You will now be able to use the function or edit the setting as 

normal. Entering an incorrect code will display the message “Incorrect Code” and allow you to try again.  
 

Changing the Lockout Code 

To change the lockout code, disable the lockout function for all the parameters selected, shut the unit off, and 
follow the procedures outlined above. 

 

4 Clock / Timers 

 

Clock Edit 

The Clock Edit option allows the user to correct the date and time of the YHC’s internal clock. To edit the 
clock, press the “4” key or scroll 

Down 

to 

Clock Edit

 and press the 

Chng

 soft key. 

 
Choose a clock or date option to adjust by scrolling 

Up

 or 

Down. 

Press 

Chng 

to choose that option.  Enter 

the correct value using the numeric keypad. You will be asked if you wish to save the new data.  Press 

Yes

 to 

accept the new value. Pressing 

No

 will take you back to the previous menu without making any changes to 

the YHC clock. When all the changes are complete, press 

Chng

to save the new value.                                                          

 

Содержание YHC 4150 Series

Страница 1: ...IM 61A YHC1 E A 3rd Edition May 2008 Users Manual YHC 4150X HART Communicator Model YHC 4150X Series HART Communicator...

Страница 2: ...Representatives and their contact information visit our web site at www yokogawa com HART is a registered trademark of the HART Communication Foundation Important information on the product is contai...

Страница 3: ...2 Applications 8 3 Lockouts Lockout PV Prompt setting View Lockout Details 8 Lockout Code 9 Disable Lockout 9 Changing Lockout Code 9 4 Clock Timers 9 1 Clock Edit 9 2 Backlight off timer 10 3 Off Tim...

Страница 4: ...Functions 21 DOF Memory Maintenance 22 Documenting HART Configurations with Yokogawa DMS Software 23 YHC 4150X Device Specific Generic HART Communication 23 Using Generic HART Communications 23 Updati...

Страница 5: ...ctions DISPLAY OVERVIEW The display of the YHC is a 128 x 128 pixel graphic display with backlight Viewable area is 2 6 x 2 6 for 13 viewable message lines The display provides three types of informat...

Страница 6: ...to facilitate data entry Soft key functions change depending on the operating mode Soft key definitions are displayed at the bottom of the LCD just above their respective gray soft keys The left hand...

Страница 7: ...d user preferences at any time and in any operating mode Pressing and holding this key cycles through all available contrast settings After adjusting Display Contrast wait at least five 5 seconds befo...

Страница 8: ...ns of these keys change depending on the operating mode of the YHC Present definitions are displayed at the bottom of the YHC display Whenever possible the two Soft Keys on left are used for navigatio...

Страница 9: ...optional AC adapter P N Z9B000007 the battery circuit is bypassed and a wall plug icon replaces the battery icon on the display header For AC power use the AC adapter is connected to the Communicatio...

Страница 10: ...PgDn soft key To retreat to the prior page press and then PgUp PgUp and PgDn soft keys remain active until the Up or Down soft key is used or until is pressed again 4 Numbered HART menus All HART disp...

Страница 11: ...changes to Device 0 Online 2 2 Select Online Setup if properly connected HART device is setup for Multidrop loop or Burst Mode operation device address 0 The YHC will respond with a statement and the...

Страница 12: ...nline HART device configurations create offline HART device configurations update the installed DOFs list HART device profiles or to update the YHC s operating firmware For example locking out the Con...

Страница 13: ...t and Next Soft Keys to input a lockout code value Alternatively you may use the green keys for Increment and Decrement functions When you are satisfied with the lockout code value press Store IMPORTA...

Страница 14: ...sponding free memory space and number of HART configurations saved with corresponding free memory space 2 Battery shows present battery setting and optimizes the battery life indicator for the battery...

Страница 15: ...found the YHC automatically asks for direction select Multi soft key to start a multi drop poll from address 1 15 or select Retry soft key to try to find address 0 again for more details see the HART...

Страница 16: ...s Do not mix alkaline batteries with each other or with other battery types Battery replacement is recommended when the Replace Batteries notice is posted on the display however the YHC will function...

Страница 17: ...onnection to the YHC s Dongle connector while in a hazardous area Use the connector Dongle only in non hazardous areas 2 HART Jacks Lead Set All YHC models are equipped with a standard size banana jac...

Страница 18: ...nt manufacturers DO NOT replace batteries while in explosive or hazardous atmospheres DO NOT use any battery type other than those listed on the Intrinsic Safe Control Document found in the Appendix o...

Страница 19: ...Three HART command types are used by the YHC to communicate with HART field devices First Universal Commands are primarily used to identify a field device by its model number and tag number and to rea...

Страница 20: ...blish HART communications this is the factory default Auto poll function When a device with address zero is found the YHC provides feedback to the user and starts the initial HART display for the conn...

Страница 21: ...he loop will be displayed on the YHC s screen The address of interest can be selected from the list to launch HART communication with that device This Digital Poll is for one power cycle only and can...

Страница 22: ...ices one at a time Use the soft key controls to move through the list Pressing the key changes soft key definitions Down and Up to PgUp and PgDn To quickly advance to the next page of a list press the...

Страница 23: ...ly the edited parameters MVar Primary Cfg for multivariable devices Primary Variable configuration MVar Sub Config for multivariable devices Sub configuration secondary tertiary fourth etc variables 3...

Страница 24: ...sult the device manual for menu structure details YHC features two unique online features for added convenience to the user 1 Live HART connection monitor YHC display lets you know from the Main navig...

Страница 25: ...DOFs link at http fibu yokogawa usa com yhc4150 html Sort the list by clicking on any column header For download instructions see the DOF Firmware Download Site section of this manual 2 The connected...

Страница 26: ...ory is free This indicates fragmentation To optimize DOF flash memory it is necessary to delete all DOFs and then reload them all in one session Connect the YHC to a host PC that has DPC Manager insta...

Страница 27: ...using Universal and Common Practice commands to poll configure and maintain HART devices Specific functions supported include most polling tagging device configuration and trim operations for analog...

Страница 28: ...ble by subscription A list of currently available DOF s for HART device communication can be viewed at the http fibu yokogawa usa com yhc4150 html Click on the Available DOFs link and sort the list by...

Страница 29: ...port C Dongle and RS 232 Cable are connected to the YHC and the unit is turned on Note HART communication cannot occur while communicating using the RS 232 connection D The AC power adapter is connect...

Страница 30: ...individual files for downloading from a list of downloadable files including DPC Manager Utility YHC Firmware and DOF s by locating the file name of interest with the PC mouse and clicking on the cor...

Страница 31: ...Advance Settings To report any difficulties with downloading operations please contact a Yokogawa Office Representative or Agent 8 Use the browser button to navigate to the location of the DOF files...

Страница 32: ...ly marked on the package being shipped back the unit will be returned at the shipper s expense This number will be provided by the Yokogawa Repair Department when you call fax or e mail your informati...

Страница 33: ...A alkaline batteries without backlight 27 hours using AA alkaline batteries with backlight TEMPERATURE SPECIFICATIONS Storage 40 F to 140 F 40 C to 60 C Operating 23 F to 122 F 5 C to 50 C CONNECTIONS...

Страница 34: ...YHC ACCESSORIES LIST Z4150 7G Protective green boot provides degree of protection against drop related damage slip on A900529 00014 HART Test Lead Kit included w YHC standard banana plugs mini grabbe...

Страница 35: ...IM 61A YHC1 E A 3rd Edition May 2008 Page 31 of 34 Intrinsic Safety Control Drawing...

Страница 36: ...Agency UL International DEMKO A S Testing Certification 0539 P O Box 514 Lyskaer 8 DK 2730 Herlev Denmark This Declaration is based on Compliance with the following Standards Regarding Hazardous Envi...

Страница 37: ...og Trim Menu 4mA Analog Trim 20mA Analog Trim DAC Trim Loop Test Scaled DAC Trim Revisions HART Revision Device Revision Software Revision Final Assbly Number Basic Info Tag Date Descriptor Message Pr...

Страница 38: ...Isolator Material Flange Size Number of Remote Universal Revision Transmitter Revision Software Tag Date Descriptor Message ASC Model Ext SW Mode Revisions Const Mats Device ID Polling Address Request...

Отзывы: