NORMAL OPERATING CONDITIONS
Ambient Temperature: 0 to 50°C
Ambient Humidity:
5 to 90% relative humidity
(non-condensing)
Operating environment: Area free of hydrogen sulfide
gas and other corrosive
gases and dust and where
the device is not exposed to
sea breeze or direct sunlight.
Continuous vibration: (at 5 to 9 Hz) Half amplitude of
1.5 mm or less
(at 9 to 150 Hz) 4.9m/s
2
or less,
1 oct/min for 90 minutes each
in the three axis directions
Impact: 49 m/s
2
or less, 11 ms, 3 axes, 6 directions, 3
times each
Installation altitude: 2,000 m or less above sea level
Warm-up time: 15 minutes or more after the power is
turned on
n
TRANSPORT AND STORAGE
CONDITIONS
Temperature: -25 to 70°C
Temperature change rate: 20°C per hour or less
Humidity: 5 to 95%RH (no condensation)
n
OPTIONS
/NHR: Without rack case (internal unit only)
/FBP:
Power supply fuse bypass
/LOCK: Power supply plug with lock
/WSW: With spring washer
/REK: Mount to same line with EK series rack
/TB:
With power supply terminal
/A2TB: 220V version with power supply terminal
/A2ER: 220V version with power supply plug
/FCAL: Fahrenheit range
n
TERMINAL CONNECTIONS
K
J
H
F
D
C
B
A
8
7
6
5
4
3
2
1
OUT
IN
Terminal arrangement
Terminal
Designation
Description
A
NC
Alarm output 1
B
COM
C
D
F
NC
Alarm output 2
(*5)
H
COM
J
NO
K
NO
Do not connect to the output terminal when the terminal is not in use.
*5:
For SALD-724 only.
Terminal
Designation
Description
SALD-1
, 2
SALD-3
1
+
Input 1
A
b
2
-
3
4
Input 1
5
6
(RJC block installation
terminal)
7
B
8
For SALD-7
, the connection depends on the selected sensor type (mV DC,
thermocouple or RTD).