3-4
IM 01B04K02-02E
Applicable Cables
(1) Signal circuit wiring
• Cross-sectional area of the cable conductor: 0.5 to 0.75 mm
2
• Examples of applicable cables: Single core PVC insulated flexible cable (VSF)
stranded wires (JIS C 3306); heat-resistant vinyl-insulated cable (UL style 1007)
(2) Alarm circuit wiring
• Cross-sectional area of the cable conductor: 0.5 to 1.25 mm
2
• Examples of applicable cables: 600 V PVC insulated cable (IV) stranded wires (JIS C
3307); PVC insulated cable for electric appliances (KIV) stranded wires (JIS C 3316);
heat-resistant vinyl-insulated cable (UL style 1007)
(3) Power supply wiring
• Cross-sectional area of the cable conductor: 1.25 to 2.00 mm
2
• Examples of applicable cables: 600 V PVC insulated cable (IV) stranded wires (JIS C
3307)
3.2 Example of Alarm Wiring