General
Specifications
Model SALD (Style S)
mV and Temperature Alarm Unit
GS 01B04K02-02E
GS 01B04K02-02E
©Copyright Sept. 2001(MC)
12th Edition, Sep. 2019(YK)
n
GENERAL
The SALD mV and Temperature Alarm Unit accepts a
mV DC, thermocouple or RTD input signal, compares
the input signal with an alarm setpoint, and outputs an
alarm signal. One or two absolute alarm outputs can
be provided on one input. Direct/reverse action can
also be set to each of the alarm setpoints. Alarm LED
is provided on the front panel for confirming alarm relay
action (when relay is energized).
The JHT200 Handy Terminal*
is used for setting the
Alarm Unit parameters. For the SALD with display
setter (SALD-
4), input indication and alarm setpoints
can be set on the front panel.
*:
When connecting the JHT200 Handy Terminal, the
adapter for modular- jack (model E9786WH) is required.
When using the BT200 BRAIN Terminal of YOKOGAWA
Electric Corporation, the communication cable of 5-pin
connector type (model F9182EE) and the adapter for
modular-jack (model E9786WH) are required.
n
STANDARD SPECIFICATIONS
Input Signals
Input: mV DC, thermocouple or RTD
Number of input: 1
Input Type
Measuring Range
mV DC
0 to 100 mV DC
Thermocouple
(*1)
Type K
–270.0 to 1372.0°C
Type T
–270.0 to 400.0°C
Type J
–210.0 to 1200.0°C
Type E
–270.0 to 1000.0°C
Type B
50.0 to 1820.0°C
Type R
–50.0 to 1768.0°C
Type S
–50.0 to 1768.0°C
Type N
(*3)
–270.0 to 1300.0°C
Type W3
(*3)
0 to 2315°C
Type W5
(*3)
0 to 2315°C
RTD
(*2)
JPt100
–200.0 to 510.0°C
Pt50
–200.0 to 649.0°C
Pt100
(ITS-90)
–200.0 to 850.0°C
Pt100
(IPTS-68)
–200.0 to 660.0°C
*1:
Thermocouple JIS C 1602
、
IEC 60584-1 (ITS-90)
TypeK, T, E, J, R, S, B, N, W3
(Note 1)
, W5
(Note 2)
Note 1: ASTM E988 Standard: W97Re3-W75Re25
(tungsten97% rhenium3%-tungsten75% rhenium25%)
Note 2:ASTM E988 Standard: W95Re5-W74Re26
(tungsten95% rhenium5%-tungsten74% rhenium26%)
*2:
RTD JIS C 1604, IEC 60751 (ITS-90) Pt100
JIS C 1604: 1989, DIN (IPTS-68) Pt100
JIS C 1604: 1989, JPt100
JIS C 1604: 1981, Pt50 JIS C 1604
*3:
For SALD-7 type only
Measurement unit: °C, °F, K, mV
Input/Output Resistance
mV DC, Thermocouple:
Input resistance
1 M
Ω
,
External input resistance 500
Ω
or less
RTD: Input leadwire resistance 10
Ω
/lead or less
Output Signals
Output: Relay contact
Contact Capacity:
100 V AC, 1 A (resistive load)
220 V AC, 0.5 A (resistive load)
30 V DC, 1 A (resistive load)
110 V DC, 0.1 A (resistive load)
Contact Life Expectancy: 600,000 times
Number of Outputs: 1 (SALD-
1
) or 2 (SALD-724)
Alarm Functions
Alarm Action: 1 input, 1 absolute alarm (SALD-
1
)
1 input, 2 absolute alarms (SALD-724)
Alarm Settings
Absolute Alarm Setpoint:
–19999 to +32000 (engineering unit)
Hysteresis: 0 to 32000 (engineering unit)
Alarm ON/OFF Delay:
0 to 999 sec.
Direction of Alarm Action: Direct/Reverse
SALD-
0 Selection by the parameter.
SALD-
4 Selection by the jumper switch.
Direction of Alarm Relay Action (at normal operation):
De-energized/Energized
Direction of Alarm Relay Action: De-energized setting at normal operation
Action Input value
Setpoint Setpoint
Input value
Direct
Relay de-energized
Relay energized
Reverse
Relay energized
Relay de-energized
Direction of Alarm Relay Action: Energized setting at normal operation
Action
Input value
Setpoint Setpoint
Input value
Direct
Relay energized
Relay de-energized
Reverse
Relay de-energized
Relay energized