2-4
IM 01B04K02-02E
2.3 Measurement Range and Accuracy Warranty
Input Type
Measuring Range Measuring Range (K) Measuring Range (°F)
(*6)
Input Accuracy
mV DC Input
0 to100 mVDC
±0.5% of measuring
range
(*1)
Thermocouple
Input
(*3)
Type K
-270.0 to 1372.0 °C
0.0 to 1640.0 K
-450.0 to 2500.0 °F
±0.5%
(*1)
of measuring
range + reference junction
compensation error
(*2)
Type T
-270.0 to 400.0 °C
0.0 to 670.0 K
-450.0 to 750.0 °F
Type J
-210.0 to 1200.0 °C
80.0 to 1470.0 K
-340.0 to 2300.0 °F
Type E
-270.0 to 1000.0 °C
0.0 to 1270.0 K
-450.0 to 1830.0 °F
Type B
50.0 to 1820.0 °C
330.0 to 2090.0 K
130.0 to 3300.0 °F
Type R
-50.0 to 1768.0 °C
230.0 to 2040.0 K
-50.0 to 3210.0 °F
Type S
-50.0 to 1768.0 °C
230.0 to 2040.0 K
-50.0 to 3210.0 °F
Type N
(*5)
-270.0 to 1300.0 °C
0.0 to 1570.0 K
-450.0 to 2400.0 °F
Type W3
(*5)
0 to 2315 °C
280 to 2580 K
32 to 4190 °F
Type W5
(*5)
0 to 2315 °C
280 to 2580 K
32 to 4190 °F
RTD
(*4)
JPt100
-200.0 to 510.0 °C
80.0 to 780.0 K
-320.0 to 940.0 °F
±0.5% of measuring
range
Pt50
-200.0 to 649.0 °C
80.0 to 920.0 K
-320.0 to 1200.0 °F
Pt100 (ITS-90)
-200.0 to 850.0 °C
80.0 to 1120.0 K
-320.0 to 1560.0 °F
Pt100 (IPTS-68) -200.0 to 660.0 °C
80.0 to 930.0 K
-320.0 to 1210.0 °F
*1: The accuracy is ±2.5% for a temperature range below -200 °C.
The accuracy is ±2.5% for a temperature range below 600 °C.
*2: Reference junction compensation error:
Above 0 °C: ±0.5% (except for TypeR, TypeS)
±1% (for TypeR, TypeS)
Below 0 °C: Multiply accuracy for temperatures over 0°C by K, where
K = (Thermocouple output change/°C near 0°C) / (Thermocouple output change/°C at
measurement temperature)
*3: Thermocouple JIS C 1602, IEC 60584-1 (ITS-90)
TypeK, T, E, J, R, S, B, N, W3(Note 1), W5(Note 2)
Note 1: ASTM E988 Standard: W97Re3-W75Re25
(tungsten97% rhenium3%-tungsten75% rhenium25%)
Note 2:ASTM E988 Standard: W95Re5-W74Re26
(tungsten95% rhenium5%-tungsten74% rhenium26%)
*4: RTD JIS C 1604, IEC 60751 (ITS-90) Pt100
JIS C 1604: 1989, DIN (IPTS-68) Pt100
JIS C 1604: 1989, JPt100
JIS C 1604: 1981, Pt50 JIS C 1604
*5: For SALD-7 type only
*6: Measuring range (°F) is displayed when the option /FCAL is specified.