4-3
IM 77V01B01-01EN
5th Edition: 2023.03.07-00
●
Recommended ferrule terminal lug
Manufacturer:
PHOENIX CONTACT
Crimping tool:
CRIMPFOX 6
Applicable terminal type
Product No. Applicable electric wire mm²
(AWG#)
Recommended stripping
length (mm²)
AI 0, 25-8 YE
3203037
0.25 (24)
10
AI 0, 34-8 TQ
3203066
0.3*
1
, 0.34 (22)
10
AI 0, 5-8 WH
3200014
0.5 (20)
11
AI 0, 75-8 GY
3200519
0.75 (18)
11
AI-TWIN 2X 0,5-10 WH
*2
3203309
0.5(20)
13
AI-TWIN 2X 0,75-10 GY
*2
3200975
0.75(18)
14
*1
JIS electric wire sizes
*2
Can only be used at the power supply terminal.
●
Cable specifications and recommended parts
Wiring
descriptions
Power supply, voltage input,
resistance temperature detector
0.2 to 0.82 mm² (AWG24 to 18)
*3
Use a rated cable that is matched to the intended application.
Thermocouple
0.2 to 0.5 mm² (AWG24 to 20)
Ethernet communication
100BASE-TX (Category 5e or higher recommended)
USB communication
VZ20X side USB connector shape: Type-C
Connection cable: Use a USB cable of USB 2.0 or higher.
*3
If twin ferrule terminals are not used when the power supply is transition-wired, the cable used is 0.2 to 0.5 mm²
(AWG24 to 20).
When the ferrule terminal is not used, length of the stripped wire should be 7 to 8 mm.
Also, use a power lead having a finished outer diameter of 3 mm or less. Further, if twin
ferrule terminals are not used when the power supply is transition-wired, adjust length of
the stripped wire so that the power lead is wired to the terminal block.
When transition-wiring the power supply, use power leads having the same cross-
sectional area.
Do not pre-soldering on the conductor when connecting the stranded wire. The contact
failure or the decreasing of the wire retention force (pullout force) may cause by
connecting the pre-soldered conductor.
In case of stray strands when connecting the stranded wire, twist properly before
connecting, but be careful not to twist strongly in order to connect the stranded wire to
be evenly.
Содержание VZ20X
Страница 1: ...User s Manual VZ20X Analog Sensing Unit User s Manual IM 77V01B01 01EN IM 77V01B01 01EN 5th Edition...
Страница 16: ...Contents 3 IM 77V01B01 01EN 5th Edition 2023 03 07 00 Revision Information 1...
Страница 17: ...Contents 4 IM 77V01B01 01EN 5th Edition 2023 03 07 00 Blank Page...
Страница 23: ...2 2 IM 77V01B01 01EN 5th Edition 2023 03 07 00 Blank Page...
Страница 29: ...3 6 IM 77V01B01 01EN 5th Edition 2023 03 07 00 Blank Page...
Страница 145: ...9 10 IM 77V01B01 01EN 5th Edition 2023 03 07 00 Blank Page...
Страница 149: ...App 4 IM 77V01B01 01EN 5th Edition 2023 03 07 00 Blank Page...