9-9
IM 77V01B01-01EN
5th Edition: 2023.03.07-00
Q8 In a USB connection, VZ Configurator can be connected but monitoring, input
adjustments and firmware update are not possible. What is the corrective action for
this?
A8
Check the power supply method.
When the shape of the USB connector on the PC side is other than a Type-C, supply
power from the power terminal.
Q9 Communication was disconnected when parameters were set. Is this normal
operation?
A9
Yes, this is normal operation.
In an Ethernet connection: Communication is disconnected when parameter setting
values are changed. Begin with a new connection.
In an USB connection: Communication is disconnected when communication related
parameters and time synchronization parameter setting values are changed. Begin
with a new connection.
Q10 Is there a way of making an Ethernet connection immediately after purchase?
A10
Communication by an Ethernet connection is immediately possible if there is a DHCP
server in the network.
When there is no DHCP server, set Ethernet related parameters by a USB connection.
When setting is completed, try communication by an Ethernet connection.
Содержание VZ20X
Страница 1: ...User s Manual VZ20X Analog Sensing Unit User s Manual IM 77V01B01 01EN IM 77V01B01 01EN 5th Edition...
Страница 16: ...Contents 3 IM 77V01B01 01EN 5th Edition 2023 03 07 00 Revision Information 1...
Страница 17: ...Contents 4 IM 77V01B01 01EN 5th Edition 2023 03 07 00 Blank Page...
Страница 23: ...2 2 IM 77V01B01 01EN 5th Edition 2023 03 07 00 Blank Page...
Страница 29: ...3 6 IM 77V01B01 01EN 5th Edition 2023 03 07 00 Blank Page...
Страница 145: ...9 10 IM 77V01B01 01EN 5th Edition 2023 03 07 00 Blank Page...
Страница 149: ...App 4 IM 77V01B01 01EN 5th Edition 2023 03 07 00 Blank Page...