<2. Overview>
2-2
IM 21B03D01-01E
Explosionproof Construction:
TIIS Explosionproof (/JF3):
Flameproof Exd II B+H
2
T6X
FM Explosionproof (/FF1):
Explosionproof for Class I, Division 1,
Groups B, C and D.
Dust ignitionproof for Class II/III, Division 1,
Groups E, F and G.
Temperature Class: T6.
Outdoor hazardous locations, NEMA 4X.
Dustproof Construction:
IEC IP54
Connections:
Air Connection: Rc1/4 or 1/4NPT female
Electrical Connection: G1/2, G3/4 female or
1/2NPT, 3/4NPT female
Mounting:
Vertical or horizontal 50mm (2-INCH) pipe
mounting
Wall mounting
Mass (weight):
2.8kg (6.1lb)
Accuracy:
±0.5% of span
Linearity: ±0.2% of span
Hysteresis: 0.2% of span
Repeatability: 0.1% of span
Table 2.1
Output Signals
Output
Signal
Standard Output
Doubled Output
Recomended
Supply Air
Pressure
*1
Supply Air
Pressure
Gauge Scale
*1
Output Signal
Pressure
Gauge Scale
Output Signal
Pressure
Gauge Scale
Pa
calibration
20 to 100kPa
0 to 200kPa
40 to 200kPa
0 to 400kPa
130 to 150kPa
0 to 200kPa
230 to 260kPa
0 to 400kPa
kgf/cm
2
calibration
0.2 to 1.0kgf/cm
2
0 to 2kgf/cm
2
0.4 to 2.0kgf/cm
2
0 to 4kgf/cm
2
1.3 to 1.5kgf/cm
2
0 to 2kgf/cm
2
2.3 to 2.6kgf/cm
2
0 to 4kgf/cm
2
Bar
calibration
0.2 to 1.0bar
0 to 2bar
0.4 to 2.0bar
0 to 4bar
1.3 to 1.5bar
0 to 2bar
2.3 to 2.6bar
0 to 4bar
P calibration 3 to 15psi
0 to 30psi
6 to 30psi
3 to 27psi
0 to 60psi
19 to 22psi
0 to 30psi
*2
0 to 60psi
*1: Set supply air pressure in the range given in the upper column for standard output and in the range given in the lower column for
multiplied pressure output.
*2:
6 to 30psi output signal; 34 to 37psi, 3 to 27psi output signal; 34 to 36psi.