IM 05P01F31-11EN   page 9/10

Operation Parameters

Hold down the PARA key for 3 seconds to move from the Operation Display to the Op-

eration Parameter Setting Display. Press the DISP key once to return to the Operation 

Display.

Menu

Hold down PARA key for 3 sec.

DISP key

SET/ENTER key

PARA key

key

key

key

key

key

The parameter groups can be switched using     ,      keys.

Operation Dsipaly

Parameter

Parameter

Parameter

Parameter

Parameter

Parameter

END

Menu

END

Menu

END

END

Menu Display and 

Parameter Setting 

Display are changed 

in a circular pattern.

Move to the Setup Parameter Setting Display: 

     Hold down the PARA key and the Left arrow key simultaneously for 3 sec.

Operation for Setting

·  To select the parameter setting displayed as the initial value, press the Down arrow 

key to move to the next parameter.

·  To change and set the parameter setting, press the SET/ENTER key to start the set-

point blinking. The blinking state allows you to make changes (setting mode). Use the 

Up/Down/Left/Right arrow keys to change the setpoint. Press the SET/ENTER key to 

register the setting.

Note that there are some parameters which are not displayed depending on the model 

and suffix codes, control type (CNT), etc. The parameters for professional setting mode 

(LEVL: PRO) are not described in this manual. See User’s Manual (IM 05P01F31-

01EN).

 Operation Mode

Menu symbol: 

 

(MODE)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(S.R)

STOP/RUN switch

STOP: Stop mode

 

RUN: Run mode

 

Preset output (PO) is generated in 

STOP mode.

RUN

EASY

(R.L)

REMOTE/LOCAL switch

LCL: Local mode

 

REM: Remote mode

(Displayed only in cases where the 

communication is specified.)

LCL

(AT)

AUTO-tuning switch

OFF: Disable

 

1 to 4: Perform auto-tuning. Tuning 

result is stored in the specified num-

bered PID.

 

R: Tuning result is stored in the PID 

for reference deviation.

OFF

(SPNO.)

SP number selection

1 to 4 (Depends on the setup param-

eter SPGR. setting.)

1

(PID)

PID number

The PID group number being selected 

is displayed. 

1 to 4, R: PID group for reference 

deviation

1

 SELECT Parameter

Menu symbol: 

 (CS)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

Registered 

parameter 

symbol

SELECT parameter 10 

to 19

Setting range of a registered param-

eter.

For details, see User's Manual (IM 

05P01F31-01EN).

Table 

below

EASY

Parameter 

n=10

n=11

n=12

n=13

n=14

n=15

n=16

n=17

n=18

n=19

CSn

For the registration of SELECT parameters, see User's Manual (IM 05P01F31-01EN).

 SP and Alarm Setpoint Setting Parameter

Menu symbol: 

 (SP)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(SP)

Target setpoint

0.0 to 100.0% of PV input range 

(EU) (Setting range: SPL to SPH)

SPL

Table 

below

EASY

(SUB)

Sub-target setpoint (in 

Two-position two-level 

control)

Set the offset from SP.

 

-100.0 to 100.0% of PV input 

range span (EUS)

0.0 % of 

PV input 

range span

(PIDN)

PID number selection

Set a PID group number to use.

 

1 to 4 (Depends on the setup 

parameter PIDG. setting.)

1 to 4

 to 

(A1 to A4)

Alarm-1 to -4 setpoint

Set a display value of setpoint of PV 

alarm, SP alarm, deviation alarm, 

output alarm, or velocity alarm.

 

-19999 to 30000 (Set a value within 

the input range.)

 

Decimal point position depends on 

the input type

0

For the parameter SP (target setpoint), 4 groups are displayed for the factory default. 

The number of groups can be changed by the setup parameter SPGR. (number of SP 

groups). For the alarm setpoint parameter, alarm-1 to -4 are displayed for the factory 

default. The number of alarms can be changed using the setup parameter ALNO. 

(number of alarms). To change the number of SP groups or alarms, see User's Manual 

(IM 05P01F31-01EN).

Use the following table to record SP and alarm setpoints.

Parameter

n=1

n=2

n=3

n=4

SP

SUB

PIDN

A1
A2
A3
A4

n: group number

 SP-related Setting Parameter 

Menu symbol: 

 (SPS)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(RT)

Remote input ratio

SP = Remote input x RT + Remote input bias

 

0.001 to 9.999

(Displayed only in cases where the 

communication is specified.)

1.000

STD

(RBS)

Remote input bias

-100.0 to 100.0% of PV input range 

span (EUS)

(Displayed only in cases where the 

communication is specified.)

0.0 % of 

PV input 

range 

span

(UPR)

SP ramp-up rate

Used to prevent SP from changing suddenly.

 

Set a ramp-up rate or ramp-down rate per 

hour or minute. Set a time unit using the 

parameter TMU.

 

OFF, 0.0 + 1 digit to 100.0% of PV input 

range span (EUS)

OFF

EASY

(DNR)

SP ramp-down rate

OFF

(TMU)

SP ramp-rate time unit

HOUR: Ramp-up rate or ramp-down 

rate per hour 

MIN: Ramp-up rate or ramp-down 

rate per minute

HOUR

(SPT)

SP tracking selection

Tracking is performed when the mode 

changes from Remote to Local. (The local 

setpoint keeps track of the remote setpoint.)

OFF, ON

ON

STD

(PVT)

PV tracking selection

Causes the setpoint to keep track of the PV 

so the setpoint automatically reverts to its 

original value at a preset rate of change. 

The UPR, DNR, and TMU are used in 

combination. Operating conditions: 1) MAN 

→ AUTO, 2) STOP → AUTO, 3) Power-on, 

4) SP number change, 5) SP change

OFF, ON

OFF

 Alarm Function Setting Parameter

Menu symbol: 

 (ALRM)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

 to 

(AL1 to AL4)

Alarm-1 to 4 type

Example: Alarm-1

Stand-by 

action

Latch action

Energized/

De-energize

Alarm 

type

Set a 5-digit value in the following order.

[Latch action (0/1/2/3/4)] + [Energized 

(0) or De-energized (1)] + [Without (0) 

or With (1) Stand-by action] + [Alarm 

type: 2 digits (see below)]

For latch action, see User's Manual 

(IM 05P01F31-01EN). 

AL1, 

 

AL3: 

 

Latch 

action (0) 

 

PV high 

limit (01)

 

Without 

Stand-by 

action (0)

 

Ener-

gized (0) 

AL2, 

AL4: 

Latch 

action 

(0)

Ener-

gized (0) 

Without 

Stand-

by action

 

(0)

 

PV low 

limit (02) 

Table 

below

EASY

Alarm type: 2 digits

00: Disable

01: PV high limit, 02: PV low limit

03: SP high limit, 04: SP low limit

05: Deviation high limit

06: Deviation low limit

07: Deviation high and low limits

08: Deviation within high and low limits

09: Target SP high limit

10: Target SP low limit

11: Target SP deviation high limit

12: Target SP deviation low limit

13: Target SP deviation high and low limits

14: Target SP deviation within high 

and low limits

15: OUT high limit, 16: OUT low limit

19: Analog input PV high limit

20: Analog input PV low limit

29: PV velocity

30: Fault diagnosis

31: FAIL

 to 

(VT1 to VT4)

PV velocity alarm time 

setpoint 1 to 4

0.01 to 99.59 (minute.second)

1.00

Table 

below

EASY

 to 

(HY1 to HY4)

Alarm-1 to -4 hysteresis

Set a display value of setpoint of hystere-

sis. 

-19999 to 30000 (Set a value within 

the input range.)

 

Decimal point position depends on 

the input type.

When the decimal point position for 

the input type is set to "1", the initial 

value of the hysteresis is "1.0".

10

 to 

(DYN1 to DYN4)

Alarm-1 to -4 On-delay 

timer

An alarm output is ON when the 

delay timer expires after the alarm 

setpoint is reached. 

0.00 to 99.59 (minute.second)

0.00

STD

(AMD)

Alarm mode

0: Always active

1: Not active in STOP mode

2: Not active in STOP or MAN mode

0

For the alarm function setting parameter, 4 alarms are displayed for the factory default. 

The number of alarms can be changed by the setup parameter ALNO. (number of 

alarms). To change the number of alarms, see User's Manual (IM 05P01F31-01EN).

Parameter

n=1

n=2

n=3

n=4

ALn
VTn

HYn

DYNn

n: alarm number

 PV-related Setting Parameter 

Menu symbol: 

 (PVS)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(BS)

PV input bias

-100.0 to 100.0% of PV input range 

span (EUS)

0.0 % 

of PV 

input 

range 

span

EASY

(FL)

PV input filter

OFF, 1 to 120 s

OFF

 PID Setting Parameter

Menu symbol: 

 (PID)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(P)

Proportional band

0.0 to 999.9%

 

When 0.0% is set, it operates as 

0.1%.

5.0%

EASY

(I)

Integral time

OFF: Disable

 

1 to 6000 s

240 s

(D)

Derivative time

OFF: Disable

 

1 to 6000 s

60 s

(OH)

Control output high limit

-4.9 to 105.0%, (OL<OH)

 

In Heating/cooling control: 0.1 to 

105.0% (OL<OH)

100.0%

(OL)

Control output low limit

-5.0 to 104.9%, (OL<OH), SD: Tight 

shut

0.0%

(MR)

Manual reset

Enabled when integral time is OFF.

 

The manual reset value equals the 

output value when PV = SP.

 

-5.0 to 105.0%

50.0%

(HYS)

Hysteresis (in ON/OFF 

control)

In ON/OFF control: 0.0 to 100.0% of 

PV input range span (EUS)

In 

ON/OFF 

control: 

0.5 % of 

PV input 

range 

span 

EASY

(HY.UP)

Upper-side hysteresis 

(in ON/OFF control)

0.0 to 100.0% of PV input range 

span (EUS)

0.5 % 

of PV 

input 

range 

span

(HY.LO)

Lower-side hysteresis 

(in ON/OFF control)

0.5 % 

of PV 

input 

range 

span

(DR)

Direct/reverse action 

switch

RVS: Reverse action

DIR: Direct action

RVS

STD

(PO)

Preset output

In STOP mode, fixed control output 

can be generated.

0.0%

EASY

For the PID setting parameter, 4 groups are displayed for the factory default. 

The number of groups can be changed by the setup parameter PIDG. (number of PID 

groups). To change the number of PID groups, see User's Manual (IM 05P01F31-01EN).

If you are using two or more groups of PID parameters, use the following table to record their setting values.

Parameter

n=2

n=3

n=4

R

P

I

D

OH

OL

MR

HYS

HY.UP
HY.LO

DR
PO

n: group number

 Tuning Parameter 

Menu symbol: 

 

(TUNE)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(SC)

Super function

OFF: Disable

1: Overshoot suppressing function 

(normal mode)

2: Hunting suppressing function 

(stable mode)

 

Enables to answer the wider 

characteristic changes compared 

with response mode.

3: Hunting suppressing function 

(response mode)

 

Enables quick follow-up and short 

converging time of PV for the 

changed SP.

4: Overshoot suppressing function 

(strong suppressing mode)

 

Note: Setpoints 2 and 3 must be 

used in PID control or PI control. 

Disabled in the following controls:

 

1) ON/OFF control, 2) PD control, 

3) P control.

 

Do not use the function for the 

control processes with response 

such as flow or pressure control.

OFF

EASY

(AT.TY)

Auto-tuning type

0: Normal

 

1: Stability

0

STD

(AR)

Anti-reset windup 

(excess integration 

prevention)

AUTO, 50.0 to 200.0%

AUTO

(OPR)

Output velocity limiter

OFF: Disable

 

0.1 to 100.0%/s

OFF

(MPON)

Manual preset output 

number selection

Select the output used in MAN mode 

when switched from AUTO to MAN 

mode.

OFF: Hold the control output in AUTO          

mode (bumpless)

1: Use manual preset output 1 (output 

bump)

2: Use manual preset output 2 (output 

bump)

3: Use manual preset output 3 (output 

bump)

4: Use manual preset output 4 (output 

bump)

5: Use manual preset output 5 (output 

bump)

OFF

 to

(MPO1 to MPO5)

Manual preset output 1 

to 5

-5.0 to 105.0% 

 

However, output is limited to the 

output high limit and low limit.

0.0%

Table 

below

Use the following table to record the manual preset output setting value.

Parameter

n=1

n=2

n=3

n=4

n=5

MPOn

 Zone Control Parameter

Menu symbol: 

 (ZONE)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

 to

(RP1 to RP3)

Reference point 1 to 3

Set reference points at which switch

-

ing is carried out between groups of 

PID constants according to the given 

temperature zone.

 

0.0 to 100.0% of PV input range (EU) 

 

(RP1 ≤ RP2 ≤ RP3)

100.0% 

of PV 

input 

range

Table 

below

STD

(RHY)

Zone PID switching 

hysteresis

Hysteresis can be set for switching at 

a reference point. 

0.0 to 10.0% of PV input range span 

(EUS)

0.5 % 

of PV 

input 

range 

span

(RDV)

Reference deviation

Set a deviation from SP. The PID for 

reference deviation is used if there 

is a larger deviation than the preset 

reference deviation.

 

OFF: Disable

 

0.0 + 1 digit to 100.0% of PV input 

range span (EUS)

OFF

For Zone control, set the setup parameter ZON (zone PID selection) to Zone PID se-

lection.

Use the following table to record the reference point setting value.

Parameter

n=1

n=2

n=3

RPn

Operation

Guide

UT32A-V, -C, -R 

Digital Indicating Controller

Operation Guide

Yokogawa Electric Corporation

Parameters

For details of the each function, refer to the electronic manual. Manuals can be 

downloaded or viewed at the following URL.

Functional

Enhancement

http://www.yokogawa.com/ns/ut/im/

This operation guide describes the functions of parameters briefly. The parameter 

symbols listed are in the order shown on the display in each group of menu symbols. In 

addition, each parameter table has a “User Setting” column, where you can record your 

setpoints when setting them in the controller. The scrolling guide is displayed on PV 

display in the Parameter Setting Display. This guide can be turned on/off with the Fn key.

«Entry Model»

Содержание UT32A-R

Страница 1: ...umented panel Mount the instrument in a location where its terminals will not inadvertently be touched Well ventilated locations Mount the instrument in well ventilated locations to prevent the instru...

Страница 2: ...e set manually Reference junction compensation error 1 0 C 15 to 35 C 1 5 C 10 to 15 C and 35 to 50 C Applicable standards JIS IEC DIN ITS 90 for TC and RTD Analog Output Specifications Suffix code C...

Страница 3: ...urrent as a spark removal surge suppression circuit into the line in parallel with the load After completing the wiring the terminal cover is recommended to use for the instrument Recommended Crimp on...

Страница 4: ...IM 05P01F31 11EN page 4 10 Intentionally blank Intentionally blank...

Страница 5: ...to easily set the basic function of the controller Turn on the controller to start the Quick setting function This function allows you to easily set the control type and input and quickly start the c...

Страница 6: ...nt Open unlit SP or Target SP Alarm setpoint Hysteresis SP or Target SP Hysteresis Alarm setpoint Alarm setpoint Output Hysteresis Closed lit Hysteresis Alarm setpoint Output Alarm setpoint Hysteresis...

Страница 7: ...arrow keys to display the required setpoint Blinks during the change The setpoint has been registered This starts auto tuning The limiter can be set to the output during auto tuning For details see U...

Страница 8: ...Contact us for repair ERR SYS System data error System data is corrupted Faulty Contact us for repair PAR 0004 for user default value error only Setup parameter PA ER User parameter default value erro...

Страница 9: ...13 Target SP deviation high and low limits 14 Target SP deviation within high and low limits 15 OUT high limit 16 OUT low limit 19 Analog input PV high limit 20 Analog input PV low limit 29 PV velocit...

Страница 10: ...Ladder communication CO M Coordinated master station CO S Coordinated slave station MBASC Modbus ASCII MBRTU Modbus RTU CO S1 Coordinated slave station Loop 1 mode CO S2 Coordinated slave station Loo...

Отзывы: