IM 05P01F31-11EN  page 5/10

Contents

1.   Names and Functions of Display Parts

2.   Setup  Procedure

3.   Quick Setting Function (Setting of Input and Output)

4.   Setting Alarm Type

5.   Setting Alarm Setpoint

1.  Names and Functions of Display Parts

(2) + (3) + (4) : Setpoint display

(1)

(8)

(10)

(9)

(7)

(2)

(3)

(4)
(5)
(6)

No. in figure

Name

Description

(1)

PV display 

 

(white or red)

Displays PV.

Displays an error code if an error occurs.

Displays the scrolling guide in the Menu Display and Parameter 

Setting Display when the guide display ON/OFF is set to ON.

(2)

Group display (green)

Displays a group number (1 to 4 or R) and terminal area (E1 to E4).

1 to 4 represent SP numbers in the Operation Display.

R and E1 to E4 are displayed in the Parameter Setting Display.

(3)

Symbol display (orange) Displays a parameter symbol.

(4)

Data display (orange) Displays a parameter setpoint and menu symbol.

(5)

Bar-graph display 

(orange)

Displays control output value (OUT) and measured input value (PV).

The data to be displayed can be set by the parameter.

Initial value: Deviation, Heating-side control output (in Heating/

cooling control)

(6)

Event indicator 

 

(orange)

Lit when the alarms 1 to 4 occur.

Event displays other than alarms can be set by the parameter.

(7)

Key navigation indica-

tor (green)

Lit or blinks when the Up/Down or Left/Right arrow key operation 

is possible.

(8)

Parameter display level 

indicator (green)

Displays the setting conditions of the parameter display level func-

tion.

Parameter display level

EASY

PRO

Easy setting mode

Lit

Unlit

Standard setting mode

Unlit

Unlit

Professional setting mode

Unlit

Lit

(9)

Status indicator 

(green and red)

Displays the operating conditions and control status.

Indicator

Description 

REM

Lit when in remote mode (REM).

STOP

Lit when in stop mode (STOP).

MAN

Lit when in manual mode (MAN). 

Blinks during auto-tuning.

(10)

Security indicator (red) Lit if a password is set. The setup parameter settings are locked.

(3)

(4)

(5)

(6)

(1)

(2)

No. in figure

Name

Description

(1)

DISP key

Used to switch the Operation Displays.

Press the key in the Operation Display to switch the provided 

Operation Displays.

Press the key in the Menu Display or Parameter Setting Display 

to return to the Operation Display.

(2)

PARA key

Hold down the key for 3 seconds to move to the Operation 

Parameter Setting Display.

Hold down the key and the Left arrow key simultaneously for 3 

seconds to move to the Setup Parameter Setting Display.

Press the key in the Parameter Setting Display to return to the 

Menu Display. Press the key once to cancel the parameter set-

ting (setpoint is blinking).

(3)

SET/ENTER key

Up/Down/Left/Right 

arrow keys

SET/ENTER key

Press the key in the Menu Display to move to the Parameter 

Setting Display of the Menu. Press the key in the Parameter 

Setting Display to transfer to the parameter setting mode (setpoint 

is blinking), and the parameter can be changed.

Press the key during parameter setting mode to register the setpoint.

Up/Down/Left/Right arrow keys

Press the Left/Right arrow keys in the Menu Display to switch 

the Displays.

Press the Up/Down/Left/Right arrow keys in the Parameter 

Setting Display to switch the Displays.

Press the Up/Down arrow keys during parameter setting mode 

(setpoint is blinking) to change a setpoint.

Press the Left/Right arrow keys during parameter setting mode 

(setpoint is blinking) to move between digits according to the parameter.

(4)

Light-loader interface

It is the communication interface for the adapter cable used when 

setting and storing parameters from a PC. The LL50A Parameter 

Setting Software (sold separately) is required.

(5)

A/M key

Used to switch between AUTO and MAN modes.

The setting is switched between AUTO and MAN each time the 

key is pressed.

(6)

User function keys

The UT32A has only the Fn key. The user can assign a function 

to the key. The function is set by the parameter. 

Note:  The communication connector (maintenance port) for LL50A Parameter Setting Software is 

on the top of the unit. 

2.  Setup Procedure

The following flowchart shows the setup procedure for UT32A. 

Install and wire a controller.

Monitoring and control of regular operations

Adjust PID using auto-tuning or manually for PID control.

 

Other setup

Operation

NO

NO

NO

YES

YES

YES

Set the other parameters as needed.

PID tuning

Input setup

Output setup

Installation

and wiring

Power ON

Control type setup

Control type setup

Input/output setup

Valve position

adjustment

Use

Quick setting

function?

Position

proportional

type?

Position

proportional

type?

For Position proportional type

3.  Quick Setting Function (Setting of Input and Output)

The Quick setting function is a function to easily set the basic function of the controller.

Turn on the controller to start the Quick setting function.

This function allows you to easily set the control type and input, and quickly start the 

control action. For time proportional output, you can set the cycle time.

The items (parameters) to be set by Quick setting function are as follows.

(1) Control type (PID control, ON/OFF control)

(2) Input function (PV input type, range, scale (at voltage input), etc.)

(3) Output function (cycle time)

After turning on the controller, first decide whether or not to use the Quick setting function.

Operation in Initial Display

·  Press the SET/ENTER key while YES is displayed to start the Quick setting function.

·  If you change YES to NO and press the SET/ENTER key, Operation Display will 

appear without starting the Quick setting function.

Operation

Guide

Initial Settings

UT32A-V, -C, -R

Digital Indicating Controller

Operation Guide

This operation guide describes basic settings and operations of the UT32A.

For details of each function, see the electronic manual.

The scrolling guide is displayed on PV display in the Parameter Setting Display.

This guide can be turned on/off with the Fn key. 

For details of the each function, refer to the electronic manual. Manuals can be 

downloaded or viewed at the following URL.

Functional

Enhancement

http://www.yokogawa.com/ns/ut/im/

«Entry Model»

Operation for Setting

·  To select the parameter setting displayed as the initial value, press the Down arrow 

key to move to the next parameter.

·  To change and set the parameter setting, press the SET/ENTER key to start the 

setpoint blinking. The blinking state allows you to make changes (setting mode). 

Use the Up/Down/Left/Right arrow keys to change the setpoint. Press the SET/EN-

TER key to register the setting.

  Making Settings Using Quick Setting Function

Example:  Setting to PID control and thermocouple type K (range of 0.0 to 

500.0

0

C)

For the detailed procedure and switching of displays, see "Flow of Quick Setting 

Function" below. For the parameters to set, see the next page. 

(1) Press the SET/ENTER key while YES for QSM (Quick setting mode) is displayed.

(2) Set the control type parameter (CNT) to PID (PID control).

(3) Set the PV input type parameter (IN) to K1 (-270.0 to 1370.0 

0

C). 

(4) Set the PV input unit parameter (UNIT) to C (Degree Celsius).

(5) Set the maximum value of PV input range parameter (RH) to 500.0.

(6) Set the minimum value of PV input range parameter (RL) to 0.0.

(7) Finally, EXIT is displayed. Change NO to YES and press the SET/ENTER key to 

complete the setup. Operation Display appears. 

■  Flow of Quick Setting Function

In Quick setting mode, the parameter guide appears on PV display.

This guide can be turned on/off with the Fn key.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

Power-on

Quick setting starts

Press the SET/ENTER key while YES 

is displayed to start the Quick setting.

[NO]

Select NO with the Down 

arrow key and press the 

SET/ENTER key.

Select NO to return to

 the Operation Display.

First, the control type 

parameter (CNT) is 

displayed.

Initial value: PID (PID 

control)

 

Press the Down arrow key.

The PV input type 

parameter (IN) is 

displayed.

Initial value: OFF

Press the SET/ENTER key.

OFF blinks.

Blinking allows you to 

change the setting.

 

Press the Up arrow key.

K1 is displayed.

K1 has been registered.

Press the SET/ENTER key.

 

Press the Down arrow key.

[YES]

The last digit of the upper limit value blinks.

The parameter RH (maximum value of PV 

input range) has been changed to 500.0.

The setpoint for the parameter RH has 

been registered.

Press the Down arrow key.

Operation Display

The PV input unit parameter (UNIT) 

is displayed.

Initial value: C (Degree Celsius)

Press the Down arrow key.

Displays the measured 

input value (PV).

Displays the target 

setpoint (SP).

Press the SET/ENTER key.

Press the SET/ENTER key.

The upper limit value of the setting 

range is displayed for the param-

eter RH (maximum value of PV 

input range). 

Change the setpoint using the Up/Down 

arrow keys to increase and decrease the 

value and the Left/Right arrow keys to 

move between digits.

When the suffix code of basic control is the voltage pulse output type or 

relay output tyoe, the cycle time (CT) parameter can be set.

Finally, EXIT is displayed.

Press the SET/ENTER key to swtich to the 

setting mode.

Change NO to YES and press the SET/ENTER 

key to complete the setup of the basic function. 

Operation Display appears. The Quick setting 

function continues in the NO state. 

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

Power-on

Quick setting starts

Press the SET/ENTER key while YES 

is displayed to start the Quick setting.

[NO]

Select NO with the Down 

arrow key and press the 

SET/ENTER key.

Select NO to return to

 the Operation Display.

First, the control type 

parameter (CNT) is 

displayed.

Initial value: PID (PID 

control)

 

Press the Down arrow key.

The PV input type 

parameter (IN) is 

displayed.

Initial value: OFF

Press the SET/ENTER key.

OFF blinks.

Blinking allows you to 

change the setting.

 

Press the Up arrow key.

K1 is displayed.

K1 has been registered.

Press the SET/ENTER key.

 

Press the Down arrow key.

[YES]

The last digit of the upper limit value blinks.

The parameter RH (maximum value of PV 

input range) has been changed to 500.0.

The setpoint for the parameter RH has 

been registered.

Press the Down arrow key.

Operation Display

The PV input unit parameter (UNIT) 

is displayed.

Initial value: C (Degree Celsius)

Press the Down arrow key.

Displays the measured 

input value (PV).

Displays the target 

setpoint (SP).

Press the SET/ENTER key.

Press the SET/ENTER key.

The upper limit value of the setting 

range is displayed for the param-

eter RH (maximum value of PV 

input range). 

Change the setpoint using the Up/Down 

arrow keys to increase and decrease the 

value and the Left/Right arrow keys to 

move between digits.

When the suffix code of basic control is the voltage pulse output type or 

relay output tyoe, the cycle time (CT) parameter can be set.

Finally, EXIT is displayed.

Press the SET/ENTER key to swtich to the 

setting mode.

Change NO to YES and press the SET/ENTER 

key to complete the setup of the basic function. 

Operation Display appears. The Quick setting 

function continues in the NO state. 

Содержание UT32A-R

Страница 1: ...umented panel Mount the instrument in a location where its terminals will not inadvertently be touched Well ventilated locations Mount the instrument in well ventilated locations to prevent the instru...

Страница 2: ...e set manually Reference junction compensation error 1 0 C 15 to 35 C 1 5 C 10 to 15 C and 35 to 50 C Applicable standards JIS IEC DIN ITS 90 for TC and RTD Analog Output Specifications Suffix code C...

Страница 3: ...urrent as a spark removal surge suppression circuit into the line in parallel with the load After completing the wiring the terminal cover is recommended to use for the instrument Recommended Crimp on...

Страница 4: ...IM 05P01F31 11EN page 4 10 Intentionally blank Intentionally blank...

Страница 5: ...to easily set the basic function of the controller Turn on the controller to start the Quick setting function This function allows you to easily set the control type and input and quickly start the c...

Страница 6: ...nt Open unlit SP or Target SP Alarm setpoint Hysteresis SP or Target SP Hysteresis Alarm setpoint Alarm setpoint Output Hysteresis Closed lit Hysteresis Alarm setpoint Output Alarm setpoint Hysteresis...

Страница 7: ...arrow keys to display the required setpoint Blinks during the change The setpoint has been registered This starts auto tuning The limiter can be set to the output during auto tuning For details see U...

Страница 8: ...Contact us for repair ERR SYS System data error System data is corrupted Faulty Contact us for repair PAR 0004 for user default value error only Setup parameter PA ER User parameter default value erro...

Страница 9: ...13 Target SP deviation high and low limits 14 Target SP deviation within high and low limits 15 OUT high limit 16 OUT low limit 19 Analog input PV high limit 20 Analog input PV low limit 29 PV velocit...

Страница 10: ...Ladder communication CO M Coordinated master station CO S Coordinated slave station MBASC Modbus ASCII MBRTU Modbus RTU CO S1 Coordinated slave station Loop 1 mode CO S2 Coordinated slave station Loo...

Отзывы: