IM 05P01F31-11EN page 10/10
Setup Parameters
Hold down the PARA key and Left arrow key simultaneously for 3 seconds to move
from the Operation Display or Operation Parameter Setting Display to the Setup Pa-
rameter Setting Display.
Press the DISP key once to return to the Operation Display.
Menu
DISP key
SET/ENTER key
PARA key
key
key
key
key
key
Operation Dsipaly
Parameter
Parameter
Parameter
Parameter
Parameter
Parameter
END
Menu
END
Menu
END
END
Menu Display and
Parameter Setting
Display are changed
in a circular pattern.
Move to the Operation Parameter Setting Display:
Hold down the PARA key for 3 sec.
Hold down PARA key and
Left arrow key simultaneously for 3 sec.
Operation for Setting
· To select the parameter setting displayed as the initial value, press the Down arrow
key to move to the next parameter.
· To change and set the parameter setting, press the SET/ENTER key to start the set-
point blinking. The blinking state allows you to make changes (setting mode). Use the
Up/Down/Left/Right arrow keys to change the setpoint. Press the SET/ENTER key to
register the setting.
Note that there are some parameters which are not displayed depending on the Model
and Suffix codes, control type (CNT), etc. The parameters for professional setting mode
(LEVL: PRO) are not described in this manual. See User’s Manual (IM 05P01F31-
01EN).
■
Control Function Setting Parameter
Menu symbol:
(CTL)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(CNT)
Control type
PID: PID control
ONOF: ON/OFF control (1 point of
hysteresis)
ONOF2: ON/OFF control (2 points of
hysteresis)
PID
EASY
(SPGR.)
Number of SP groups
Set a number of SP groups to use.
1 to 4
4
STD
(ZON)
Zone PID selection
If set to “SP group number selection,”
allows PID constants to be selected
for each SP group.
If set to “Zone PID selection,”
automatically selects PID constants
according to the range set in the
Reference point.
0: SP group number selection 1
1: Zone PID selection (selection by PV)
2: Zone PID selection (selection by
target SP)
3: SP group number selection 2
4: Zone PID selection (selection by SP)
0
(PIDG.)
Number of PID groups
Set a number of PID groups to use.
1 to 4
4
■
PV Input Setting Parameter
Menu symbol:
(PV)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(IN)
PV input type
OFF: Disable
K1: -270.0 to 1370.0
0
C / -450.0 to 2500.0
0
F
K2: -270.0 to 1000.0
0
C / -450.0 to 2300.0
0
F
K3: -200.0 to 500.0
0
C / -200.0 to 1000.0
0
F
J: -200.0 to 1200.0
0
C / -300.0 to 2300.0
0
F
T1: -270.0 to 400.0
0
C / -450.0 to 750.0
0
F
T2: 0.0 to 400.0
0
C / -200.0 to 750.0
0
F
B: 0.0 to 1800.0
0
C / 32 to 3300
0
F
S: 0.0 to 1700.0
0
C / 32 to 3100
0
F
R: 0.0 to 1700.0
0
C / 32 to 3100
0
F
N: -200.0 to 1300.0
0
C / -300.0 to 2400.0
0
F
E: -270.0 to 1000.0
0
C / -450.0 to 1800.0
0
F
L: -200.0 to 900.0
0
C / -300.0 to 1600.0
0
F
U1: -200.0 to 400.0
0
C / -300.0 to 750.0
0
F
U2: 0.0 to 400.0
0
C / -200.0 to 1000.0
0
F
W: 0.0 to 2300.0
0
C / 32 to 4200
0
F
PL2: 0.0 to 1390.0
0
C / 32.0 to 2500.0
0
F
P2040: 0.0 to 1900.0
0
C / 32 to 3400
0
F
WRE: 0.0 to 2000.0
0
C / 32 to 3600
0
F
JPT1: -200.0 to 500.0
0
C / -300.0 to 1000.0
0
F
JPT2: -150.0 to 150.0
0
C / -200.0 to 300.0
0
F
PT1: -200.0 to 850.0
0
C / -300.0 to 1560.0
0
F
PT2: -200.0 to 500.0
0
C / -300.0 to 1000.0
0
F
PT3: -150.00 to 150.00
0
C / -200.0 to 300.0
0
F
0.4-2V: 0.400 to 2.000 V
1-5V: 1.000 to 5.000 V
4-20: 4.00 to 20.00 mA
0-2V: 0.000 to 2.000 V
0-10V: 0.00 to 10.00 V
0-20 : 0.00 to 20.00 mA
-1020: -10.00 to 20.00 mV
0-100: 0.0 to 100.0 mV
OFF
EASY
(UNIT)
PV input unit
-: No unit, C: Degree Celsius
-: No unit, - -: No unit, - - -: No unit,
F: Degree Fahrenheit
C
(RH)
Maximum value of PV
input range
Depends on the input type.
- For temperature input -
Set the temperature range that is
actually controlled. (RL<RH)
- For voltage / current input -
Set the range of a voltage / current
signal that is applied.
The scale across which the voltage/
current signal is actually controlled
should be set using the maximum
value of input scale (SH) and mini-
mum value of input scale (SL).
(Input is always 0% when RL = RH.)
Depends
on the
input type
EASY
(RL)
Minimum value of PV
input range
Depends
on the
input type
(SDP)
PV input scale decimal
point position
0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places
Depends
on the
input type
(SH)
Maximum value of PV
input scale
-19999 to 30000, (SL<SH),
| SH - SL | ≤ 30000
Depends
on the
input type
(SL)
Minimum value of PV
input scale
Depends
on the
input type
(BSL)
PV input burnout action
OFF: Disable
UP: Upscale
DOWN: Downscale
Depends
on the
input type
STD
(A.BS)
PV analog input bias
-100.0 to 100.0% of each input range
span (EUS)
0.0 % of
PV input
range
span
(A.FL)
PV analog input filter
OFF, 1 to 120 s
OFF
W: W-5% Re/W-26% Re(Hoskins Mfg.Co.). ASTM E988, WRE: W97Re3-W75Re25
■
Input Range, SP Limiter Setting Parameter
Menu symbol:
(MPV)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(P.UNI)
Control PV input unit
-: No unit
C: Degree Celsius
-: No unit, - -: No unit, - - -: No unit
F: Degree Fahrenheit
Same
as PV
input
unit
STD
(P.DP)
Control PV input decimal
point position
0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places
Depends
on the
input type
(P.RH)
Maximum value of
control PV input range
-19999 to 30000, (P.RL<P.RH),
| P.RH - P.RL | ≤ 30000
Depends
on the
input type
(P.RL)
Minimum value of control
PV input range
Depends
on the
input type
(SPH)
SP high limit
0.0 to 100.0% of PV input range (EU),
(SPL<SPH)
100.0 %
of PV
input
range
(SPL)
SP low limit
0.0 % of
PV input
range
■
Output Setting Parameter
Menu symbol:
(OUT)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(CT)
Control output cycle time 0.5 to 1000.0 s
30.0 s
EASY
(OU.A)
OUT current output
range
4-20: 4 to 20 mA, 0-20: 0 to 20 mA
20-4: 20 to 4 mA, 20-0: 20 to 0 mA
4-20
STD
■
RS-485 Communication Setting Parameter (E1-terminal Area)
Menu symbol:
(R485)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(PSL)
Protocol selection
PCL: PC link communication
PCLSM: PC link communication (with
checksum)
LADR: Ladder communication
CO-M: Coordinated master station
CO-S: Coordinated slave station
MBASC: Modbus (ASCII)
MBRTU: Modbus (RTU)
CO-S1: Coordinated slave station
(Loop-1 mode)
CO-S2: Coordinated slave station
(Loop-2 mode)
P-P: Peer-to-peer communication
MBRTU
EASY
(BPS)
Baud rate
600: 600 bps, 1200: 1200 bps
2400: 2400 bps, 4800: 4800 bps
9600: 9600 bps, 19200: 19.2k bps
38400: 38.4k bps
19200
(PRI)
Parity
NONE: None
EVEN: Even
ODD: Odd
EVEN
(STP)
Stop bit
1: 1 bit, 2: 2 bits
1
(DLN)
Data length
7: 7 bits, 8: 8 bits
8
(ADR)
Address
1 to 99
1
■ Key Action Setting Parameter
Menu symbol:
(KEY)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(Fn)
User function key-n
action setting
OFF: Disable
A/M: AUTO/MAN switch
R/L1: REM/LCL switch
S/R: STOP/RUN switch
AUTO: Switch to AUTO
MAN: Switch to MAN
REM1: Switch to REM
LCL1: Switch to LCL
STOP: Switch to STOP
RUN: Switch to RUN
AT: Auto-tuning
LTUP: LCD brightness UP
LTDN: LCD brightness DOWN
BRI: Adjust LCD brightness
LCD: LCD backlight ON/OFF switch
LAT: Latch release
PID: PID tuning switch
PID
EASY
■ Display Function Setting Parameter
Menu symbol:
(DISP)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(PCMD)
Active color PV display
switch
0: Fixed in white
1: Fixed in red
2: Link to alarm 1 (Alarm OFF: white,
Alarm ON: red)
3: Link to alarm 1 (Alarm OFF: red,
Alarm ON: white)
4: Link to alarm 1 or 2 (Alarm OFF:
white, Alarm ON: red)
5: Link to alarm 1 or 2 (Alarm OFF:
red, Alarm ON: white)
6: PV limit (Within range: white, Out
of range: red)
7: PV limit (Within range: red, Out of
range: white)
8: SP deviation (Within deviation:
white, Out of deviation: red)
9: SP deviation (Within deviation: red,
Out of deviation: white)
0
EASY
(PCH)
PV color change high
limit
Set a display value when in PV limit
or SP deviation.
-19999 to 30000 (Set a value within
the input range.)
Decimal point position depends on
the input type.
0
(PCL)
PV color change low limit
0
(BAR1)
Bar-graph display regis-
tration
0: Disable
1: OUT, 3: PV, 4: SP
5: Deviation
6 to 16: Disable
18: PV terminals analog input
27: TSP, 28: TSP deviation
5
STD
(BDV)
Bar-graph deviation
display band
0.0 to 100.0% of PV input range span
(EUS)
1.0 %
of PV
input
range
span
(GUID)
Guide display ON/OFF
OFF: Nondisplay, ON: Display
ON
(ECO)
Economy mode
OFF: Disable
1: Economy mode ON (All indications
except PV display OFF)
2: Economy mode ON (All indications OFF)
3: Brightness 10 % (whole indication)
OFF
(BRI)
Brightness
(Dark) 1 to 5 (Bright)
3
EASY
(MLSD)
Least significant digital
mask of PV display
OFF: With least significant digit
ON: Without least significant digit
OFF
STD
(MKTP)
Method for least signifi-
cant digital mask of PV
display
0: Rounding, 1: Rounding-off
0
STD
■ SELECT Display Setting Parameter
Menu symbol:
(CSEL)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
to
(CS1 to CS5)
SELECT Display-1 to -5
registration
Register the operation parameter
(except the Operation Mode) that is
frequently modified to display it in the
Operation Display.
OFF, 2301 to 5000
For the setting range, see User's Manual
(IM 05P01F31-01EN).
OFF
Table
below
STD
Use the following table to record SELECT Display setting value.
Parameter
n=1
n=2
n=3
n=4
n=5
CSn
■ Key Lock Setting Parameter
Menu symbol:
(KLOC)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(COM.W)
Communication write
enable/disable
OFF: Enable, ON: Disable
OFF
STD
(DATA)
Front panel parameter
data (▼,▲) key lock
OFF: Unlock, ON: Lock
OFF
(A/M)
Front panel A/M key lock
OFF
■ AL1-AL2 Function Registration Parameter
Menu symbol:
(ALM)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(AL1.S)
AL1 function selection
Set an I relay number. For the items
other than below, see User's Manual
(IM 05P01F31-01EN).
Ex.) Set the number 4353 for AL1.S
to use the alarm 1.
Set “OFF” to disable the function.
No function: OFF
Alarm 1: 4353, Alarm 2: 4354
Alarm 3: 4355, Alarm 4: 4357
AUTO (OFF) / MAN (ON) status: 4193
REM (ON) / LCL (OFF) status: 4194
STOP (ON) / RUN (OFF) status: 4195
FAIL (Normally ON) output: 4256
4353
STD
(AL2.S)
AL2 function selection
4354
■ System Setting Parameter
Menu symbol:
(SYS)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(R.MD)
Restart mode
Set how the controller should recover from
a power failure of 5 seconds or more.
CONT: Continue action set before
power failure.
MAN: Start from MAN.
AUTO: Start from AUTO.
CONT
STD
(R.TM)
Restart timer
Set time between power on and the in-
stant where controller starts computation.
0 to 10 s
0
(EPO)
Input error preset output
Set preset output value when the
input burnout or ADC error occurs.
Manual output is prioritized when
the input burnout occurs in MAN.
0: Preset output
1: 0% output
2: 100% output
0
(FREQ)
Power frequency
AUTO, 60: 60 Hz, 50: 50 Hz
AUTO
EASY
(QSM)
Quick setting mode
OFF: Disable
ON: Enable
ON
(LANG)
Guide display language
ENG: English, FRA: French
GER: German, SPA: Spanish
Depe-nds on
the model and
suffix codes
(PASS)
Password setting
0 (No password) to 65535
0
■ Error and Version Confirmation Parameter (for display only)
Menu symbol:
(VER)
Parameter
symbol
Name of Parameter
Status record
Display
level
(PA.ER)
Parameter error status
EASY
(OP.ER)
Option error status
(AD1.E)
A/D converter error status 1
(PV1.E)
PV input error status
(MCU)
MCU version
(DCU)
DCU version
(ECU1)
ECU-1 version (E1-terminal area)
(PARA)
Parameter version
(H.VER)
Product version
(
SER1
)
Serial number 1
(SER2)
Serial number 2
■ Parameter Display Level Parameter
Menu symbol:
(LVL)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(LEVL)
Parameter display level
EASY: Easy setting mode
STD: Standard setting mode
PRO: Professional setting mode
STD
EASY
* For Professional setting mode, see User’s Manual (IM 05P01F31-01EN).
Trademarks
● Our product names or brand names mentioned in this manual are
the trademarks or registered trademarks of Yokogawa Electric Corporation.
● Adobe, Acrobat, and Postscript are either registered trademarks or trademarks