IM 05P01F31-11EN   page 10/10

Setup Parameters

Hold down the PARA key and Left arrow key simultaneously for 3 seconds to move 

from the Operation Display or Operation Parameter Setting Display to the Setup Pa-

rameter Setting Display.

Press the DISP key once to return to the Operation Display.

Menu

DISP key

SET/ENTER key

PARA key

key

key

key

key

key

Operation Dsipaly

Parameter

Parameter

Parameter

Parameter

Parameter

Parameter

END

Menu

END

Menu

END

END

Menu Display and 

Parameter Setting 

Display are changed 

in a circular pattern.

Move to the Operation Parameter Setting Display: 

          Hold down the PARA key for 3 sec.

Hold down PARA key and 

Left arrow key simultaneously for 3 sec.

Operation for Setting

·  To select the parameter setting displayed as the initial value, press the Down arrow 

key to move to the next parameter.

·  To change and set the parameter setting, press the SET/ENTER key to start the set-

point blinking. The blinking state allows you to make changes (setting mode). Use the 

Up/Down/Left/Right arrow keys to change the setpoint. Press the SET/ENTER key to 

register the setting.

Note that there are some parameters which are not displayed depending on the Model 

and Suffix codes, control type (CNT), etc. The parameters for professional setting mode 

(LEVL: PRO) are not described in this manual. See User’s Manual (IM 05P01F31-

01EN).

 Control Function Setting Parameter

Menu symbol: 

 (CTL)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(CNT)

Control type

PID: PID control

ONOF: ON/OFF control (1 point of 

hysteresis)

ONOF2: ON/OFF control (2 points of 

hysteresis)

PID

EASY

(SPGR.)

Number of SP groups

Set a number of SP groups to use.

1 to 4

4

STD

(ZON)

Zone PID selection

If set to “SP group number selection,” 

allows PID constants to be selected 

for each SP group.

 

If set to “Zone PID selection,” 

automatically selects PID constants 

according to the range set in the 

Reference point. 

0: SP group number selection 1

1: Zone PID selection (selection by PV)

2: Zone PID selection (selection by 

target SP)

3: SP group number selection 2

4: Zone PID selection (selection by SP) 

0

(PIDG.)

Number of PID groups

Set a number of PID groups to use. 

 

1 to 4

4

 PV Input Setting Parameter

Menu symbol: 

 (PV)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(IN)

PV input type

OFF: Disable

K1: -270.0 to 1370.0 

0

C / -450.0 to 2500.0

 

0

F

K2: -270.0 to 1000.0 

0

C / -450.0 to 2300.0

 

0

F

K3: -200.0 to 500.0 

0

C / -200.0 to 1000.0

 

0

F

J: -200.0 to 1200.0 

0

C / -300.0 to 2300.0

 

0

F

T1: -270.0 to 400.0 

0

C / -450.0 to 750.0

 

0

F

T2: 0.0 to 400.0 

0

C / -200.0 to 750.0

 

0

F

B: 0.0 to 1800.0 

0

C / 32 to 3300

 

0

F

S: 0.0 to 1700.0 

0

C / 32 to 3100

 

0

F

R: 0.0 to 1700.0 

0

C / 32 to 3100

 

0

F

N: -200.0 to 1300.0 

0

C / -300.0 to 2400.0

 

0

F

E: -270.0 to 1000.0 

0

C / -450.0 to 1800.0

 

0

F

L: -200.0 to 900.0 

0

C / -300.0 to 1600.0

 

0

F

U1: -200.0 to 400.0 

0

C / -300.0 to 750.0

 

0

F

U2: 0.0 to 400.0 

0

C / -200.0 to 1000.0

 

0

F

W: 0.0 to 2300.0 

0

C / 32 to 4200

 

0

F

PL2: 0.0 to 1390.0 

0

C / 32.0 to 2500.0

 

0

F

P2040: 0.0 to 1900.0 

0

C / 32 to 3400

 

0

F

WRE: 0.0 to 2000.0 

0

C / 32 to 3600

 

0

F

JPT1: -200.0 to 500.0 

0

C / -300.0 to 1000.0

 

0

F

JPT2: -150.0 to 150.0 

0

C / -200.0 to 300.0

 

0

F

PT1: -200.0 to 850.0 

0

C / -300.0 to 1560.0

 

0

F

PT2: -200.0 to 500.0 

0

C / -300.0 to 1000.0

 

0

F

PT3: -150.00 to 150.00 

0

C / -200.0 to 300.0

 

0

F

0.4-2V: 0.400 to 2.000 V

1-5V: 1.000 to 5.000 V

4-20: 4.00 to 20.00 mA

0-2V: 0.000 to 2.000 V

0-10V: 0.00 to 10.00 V

0-20 : 0.00 to 20.00 mA

-1020: -10.00 to 20.00 mV

0-100: 0.0 to 100.0 mV

OFF

EASY

(UNIT)

PV input unit

-: No unit, C: Degree Celsius

 

-: No unit, - -: No unit, - - -: No unit, 

F: Degree Fahrenheit

C

(RH)

Maximum value of PV 

input range

Depends on the input type.

- For temperature input -

Set the temperature range that is 

actually controlled. (RL<RH)

- For voltage / current input -

Set the range of a voltage / current 

signal that is applied.

The scale across which the voltage/

current signal is actually controlled 

should be set using the maximum 

value of input scale (SH) and mini-

mum value of input scale (SL).

(Input is always 0% when RL = RH.)

Depends 

on the 

input type

EASY

(RL)

Minimum value of PV 

input range

Depends 

on the 

input type

(SDP)

PV input scale decimal 

point position

0: No decimal place

1: One decimal place

2: Two decimal places

3: Three decimal places

4: Four decimal places

Depends 

on the 

input type

(SH)

Maximum value of PV 

input scale

-19999 to 30000, (SL<SH),

| SH - SL | ≤ 30000

Depends 

on the 

input type

(SL)

Minimum value of PV 

input scale

Depends 

on the 

input type

(BSL)

PV input burnout action

OFF: Disable

UP: Upscale

DOWN: Downscale

Depends 

on the 

input type

STD

(A.BS)

PV analog input bias

-100.0 to 100.0% of each input range 

span (EUS)

0.0 % of 

PV input 

range 

span

(A.FL)

PV analog input filter

OFF, 1 to 120 s

OFF

W: W-5% Re/W-26% Re(Hoskins Mfg.Co.). ASTM E988, WRE: W97Re3-W75Re25

 Input Range, SP Limiter Setting Parameter

Menu symbol: 

 (MPV)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(P.UNI)

Control PV input unit

-: No unit

C: Degree Celsius

-: No unit, - -: No unit, - - -: No unit

F: Degree Fahrenheit

Same 

as PV 

input 

unit

STD

(P.DP)

Control PV input decimal

point position

0: No decimal place

1: One decimal place

2: Two decimal places

3: Three decimal places

4: Four decimal places

Depends 

on the 

input type

(P.RH)

Maximum value of

control PV input range

-19999 to 30000, (P.RL<P.RH),

| P.RH - P.RL | ≤ 30000

Depends 

on the 

input type

(P.RL)

Minimum value of control

PV input range

Depends 

on the 

input type

(SPH)

SP high limit

0.0 to 100.0% of PV input range (EU), 

(SPL<SPH)

100.0 % 

of PV 

input 

range

(SPL)

SP low limit

0.0 % of 

PV input 

range

 

Output Setting Parameter

Menu symbol: 

 (OUT)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(CT)

Control output cycle time 0.5 to 1000.0 s

30.0 s

EASY

(OU.A)

OUT current output 

range

4-20: 4 to 20 mA, 0-20: 0 to 20 mA

20-4: 20 to 4 mA, 20-0: 20 to 0 mA

4-20

STD

 RS-485 Communication Setting Parameter (E1-terminal Area)

Menu symbol: 

 (R485)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(PSL)

Protocol selection

PCL: PC link communication

PCLSM: PC link communication (with               

checksum)

LADR: Ladder communication

CO-M: Coordinated master station

CO-S: Coordinated slave station

MBASC: Modbus (ASCII)

MBRTU: Modbus (RTU)

CO-S1: Coordinated slave station 

(Loop-1 mode)

CO-S2: Coordinated slave station 

(Loop-2 mode)

P-P: Peer-to-peer communication

MBRTU

EASY

(BPS)

Baud rate

600: 600 bps, 1200: 1200 bps

2400: 2400 bps, 4800: 4800 bps

9600: 9600 bps, 19200: 19.2k bps

38400: 38.4k bps

19200

(PRI)

Parity

NONE: None

 

EVEN: Even

 

ODD: Odd

EVEN

(STP)

Stop bit

1: 1 bit, 2: 2 bits

1

(DLN)

Data length

7: 7 bits, 8: 8 bits

8

(ADR)

Address

1 to 99

1

■ Key Action Setting Parameter

Menu symbol: 

 (KEY)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(Fn)

User function key-n 

 

action setting

OFF: Disable

A/M: AUTO/MAN switch

R/L1: REM/LCL switch

S/R: STOP/RUN switch

AUTO: Switch to AUTO

MAN: Switch to MAN

REM1: Switch to REM

LCL1: Switch to LCL

STOP: Switch to STOP

RUN: Switch to RUN

AT: Auto-tuning

LTUP: LCD brightness UP

LTDN: LCD brightness DOWN

BRI: Adjust LCD brightness

LCD: LCD backlight ON/OFF switch

LAT: Latch release

PID: PID tuning switch

PID

EASY

■ Display Function Setting Parameter 

Menu symbol: 

 (DISP)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(PCMD)

Active color PV display 

switch

0: Fixed in white

1: Fixed in red

2: Link to alarm 1 (Alarm OFF: white, 

Alarm ON: red)

3: Link to alarm 1 (Alarm OFF: red, 

Alarm ON: white)

4: Link to alarm 1 or 2 (Alarm OFF: 

white, Alarm ON: red)

5: Link to alarm 1 or 2 (Alarm OFF: 

red, Alarm ON: white)

6: PV limit (Within range: white, Out 

of range: red)

7: PV limit (Within range: red, Out of 

range: white)

8: SP deviation (Within deviation: 

white, Out of deviation: red)

9: SP deviation (Within deviation: red, 

Out of deviation: white)

0

EASY

(PCH)

PV color change high 

limit

Set a display value when in PV limit 

or SP deviation.

 

-19999 to 30000 (Set a value within 

the input range.)

 

Decimal point position depends on 

the input type.

0

(PCL)

PV color change low limit

0

(BAR1)

Bar-graph display regis-

tration

0: Disable

1: OUT, 3: PV, 4: SP

5: Deviation

6 to 16: Disable

18: PV terminals analog input

27: TSP, 28: TSP deviation

5

STD

(BDV)

Bar-graph deviation 

display band

0.0 to 100.0% of PV input range span 

(EUS)

1.0 % 

of PV 

input 

range 

span

(GUID)

Guide display ON/OFF

OFF: Nondisplay, ON: Display

ON

(ECO)

Economy mode

OFF: Disable

1: Economy mode ON (All indications 

except PV display OFF)

2: Economy mode ON (All indications OFF)

3: Brightness 10 % (whole indication)

OFF

(BRI)

Brightness

(Dark) 1 to 5 (Bright)

3

EASY

(MLSD)

Least significant digital 

mask of PV display

OFF: With least significant digit

 

ON: Without least significant digit

OFF

STD

(MKTP)

Method for least signifi-

cant digital mask of PV 

display

0: Rounding, 1: Rounding-off

0

STD

■ SELECT Display Setting Parameter

Menu symbol: 

 (CSEL)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

 to 

(CS1 to CS5)

SELECT Display-1 to -5 

registration

Register the operation parameter 

(except the Operation Mode) that is 

frequently modified to display it in the 

Operation Display.

 

OFF, 2301 to 5000

 

For the setting range, see User's Manual 

(IM 05P01F31-01EN).

OFF

Table 

below

STD

Use the following table to record SELECT Display setting value.

Parameter

n=1

n=2

n=3

n=4

n=5

CSn

■ Key Lock Setting Parameter 

Menu symbol: 

 (KLOC)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(COM.W)

Communication write 

enable/disable

OFF: Enable, ON: Disable

OFF

STD

(DATA)

Front panel parameter 

data (▼,▲) key lock

OFF: Unlock, ON: Lock

OFF

(A/M)

Front panel A/M key lock

OFF

■ AL1-AL2 Function Registration Parameter

Menu symbol: 

 (ALM)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(AL1.S)

AL1 function selection

Set an I relay number. For the items 

other than below, see User's Manual 

(IM 05P01F31-01EN).

Ex.) Set the number 4353 for AL1.S 

to use the alarm 1.

Set “OFF” to disable the function.
No function: OFF

Alarm 1: 4353, Alarm 2: 4354

Alarm 3: 4355, Alarm 4: 4357

AUTO (OFF) / MAN (ON) status: 4193

REM (ON) / LCL (OFF) status: 4194

STOP (ON) / RUN (OFF) status: 4195

FAIL (Normally ON) output: 4256

4353

STD

(AL2.S)

AL2 function selection

4354

■ System Setting Parameter

Menu symbol: 

 (SYS)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(R.MD)

Restart mode

Set how the controller should recover from 

a power failure of 5 seconds or more.

CONT: Continue action set before 

power failure.

MAN: Start from MAN.

AUTO: Start from AUTO.

CONT

STD

(R.TM)

Restart timer

Set time between power on and the in-

stant where controller starts computation. 

0 to 10 s

0

(EPO)

Input error preset output

Set preset output value when the 

input burnout or ADC error occurs. 

Manual output is prioritized when 

the input burnout occurs in MAN.

0: Preset output

 

1: 0% output

 

2: 100% output

0

(FREQ)

Power frequency

AUTO, 60: 60 Hz, 50: 50 Hz

AUTO

EASY

(QSM)

Quick setting mode

OFF: Disable

 

ON: Enable

ON

(LANG)

Guide display language

ENG: English, FRA: French

GER: German, SPA: Spanish

Depe-nds on 

the model and 

suffix codes

(PASS)

Password setting

0 (No password) to 65535

0

■ Error and Version Confirmation Parameter (for display only)

Menu symbol: 

 (VER)

Parameter 

symbol

Name of Parameter

Status record

Display 

level

(PA.ER)

Parameter error status

EASY

(OP.ER)

Option error status

(AD1.E)

A/D converter error status 1 

(PV1.E)

PV input error status

(MCU)

MCU version

(DCU)

DCU version

(ECU1)

ECU-1 version (E1-terminal area)

(PARA)

Parameter version

(H.VER)

Product version

(

SER1

)

Serial number 1

(SER2)

Serial number 2 

■ Parameter Display Level Parameter

Menu symbol: 

 (LVL)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(LEVL)

Parameter display level

EASY: Easy setting mode

STD: Standard setting mode

PRO: Professional setting mode

STD

EASY

* For Professional setting mode, see User’s Manual (IM 05P01F31-01EN).

Trademarks

● Our product names or brand names mentioned in this manual are 

  the trademarks or registered trademarks of Yokogawa Electric Corporation.

● Adobe, Acrobat, and Postscript are either registered trademarks or trademarks

  of Adobe Systems Incorporated.

● Modbus is a registered trademark of Schneider Electric.

● We do not use the TM or ® mark to indicate these trademarks or 

  registered trademarks in this manual.

● All other product names mentioned in this manual are trademarks

  or registered trademarks of their respective companies.

Содержание UT32A-R

Страница 1: ...umented panel Mount the instrument in a location where its terminals will not inadvertently be touched Well ventilated locations Mount the instrument in well ventilated locations to prevent the instru...

Страница 2: ...e set manually Reference junction compensation error 1 0 C 15 to 35 C 1 5 C 10 to 15 C and 35 to 50 C Applicable standards JIS IEC DIN ITS 90 for TC and RTD Analog Output Specifications Suffix code C...

Страница 3: ...urrent as a spark removal surge suppression circuit into the line in parallel with the load After completing the wiring the terminal cover is recommended to use for the instrument Recommended Crimp on...

Страница 4: ...IM 05P01F31 11EN page 4 10 Intentionally blank Intentionally blank...

Страница 5: ...to easily set the basic function of the controller Turn on the controller to start the Quick setting function This function allows you to easily set the control type and input and quickly start the c...

Страница 6: ...nt Open unlit SP or Target SP Alarm setpoint Hysteresis SP or Target SP Hysteresis Alarm setpoint Alarm setpoint Output Hysteresis Closed lit Hysteresis Alarm setpoint Output Alarm setpoint Hysteresis...

Страница 7: ...arrow keys to display the required setpoint Blinks during the change The setpoint has been registered This starts auto tuning The limiter can be set to the output during auto tuning For details see U...

Страница 8: ...Contact us for repair ERR SYS System data error System data is corrupted Faulty Contact us for repair PAR 0004 for user default value error only Setup parameter PA ER User parameter default value erro...

Страница 9: ...13 Target SP deviation high and low limits 14 Target SP deviation within high and low limits 15 OUT high limit 16 OUT low limit 19 Analog input PV high limit 20 Analog input PV low limit 29 PV velocit...

Страница 10: ...Ladder communication CO M Coordinated master station CO S Coordinated slave station MBASC Modbus ASCII MBRTU Modbus RTU CO S1 Coordinated slave station Loop 1 mode CO S2 Coordinated slave station Loo...

Отзывы: