< 1. Overview >
5
TI 34P02K71-01E
4th Edition: Jun. 6, 2018-00
1.2 Migrating the Control Application
This section
describes procedure of migrate the control applications (project
on the Logic Designer) for NFCP100 and NFJT100 to NFCP501/NFCP502.
In Section 2 or later describes the procedure of the case you do not extend
retain data area fundamentally.
● Not expanding the retain data area (Migration)
- If the PLC type is IPC_40, this control application (project) can be used by re-compiling
without changing itself.
- If the PLC type is IPC_32 or IPC_33, re-create the resource with IPC_40, and re-
compile.
● Expanding the retain data area (Extend function)
- If the PLC type is IPC_40, re-create the resource with “FCFX_B”/ “FCFX_C”, and
re-compile.
- If the PLC type is “IPC_32” or “IPC_33”, re-create the resource with “IPC_40” and
“FCFX_B”, and re-compile.
PLC type
Processer
type
Migration Procedure
Remark
IPC_40
FCX
FCX_A
Re-compile
Create resource for IPC_40,
FCX_B/FCX_C, and re-compile
If expand the retain data
area
(refer to IMPORTANT)
IPC_32
IPC_33
Create resource for IPC_40,
and re-compile
SH_40
Create resource for IPC_40,
and re-compile
IMPORTANT
If retain data area is extended, it is careful in clearing retained data.