3-2
IM 04P03B01-01E
3.2
Setting the Filter (Pen Model)
A filter can be set on the measurement channels on the pen model.
Procedure
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Carry out the procedure shown in the figure below.
Press the
or
key to select the value.
If you press the
key, the operation is cancelled, and the display returns to a
higher level menu.
Select the channel number.
Select “FILTR.”
Select the filter time constant.
The settings are activated.
Select the “AUX.”
(AUX)
(FILTR)
(CH1)
(OFF)
(OK)
Channel number
3.
Press the
key to set other channels.
If you are done, press the
key.
4.
Hold down the
MENU
key for 3 seconds to return to Operation mode.
Explanation
Filter Time Constant
The time constant is selectable from 2 s, 5 s, and 10 s. Select OFF when not using the
filter.
<Related Topics>
Enabling the filter function: Section 4.11