IM 12D08N05-01E
5-9
<5. MENU STRUCTURE COMMISSIONING>
S2, S3, S4 Similar structure to S1
Enter
PI-control S1
Range
(proportional)
Direction
Setpoint
I-time
250.0μS/cm
50.00μS/cm
Reverse
3600 s
Alarm
Control
Hold
USP
Fail
Off
Simulate
Menu
Parameter
Default values
Range
min.
max.
PID-control S1
Setpoint
250.0 μS/cm
-inf
+inf
Range
50.0 μS/cm
-inf
+inf
Manual Reset
0%
0%
100%
I-time
3600 s
1 s
3600 s
D-time
0 s
0 s
60 s
Duty cycle
DC period time
10 s
1 s
1800 s
Pulse freq.
Max. pulse freq.
70 p/min
1 p/m
120 p/m
mA1 (simulate) Expire time
0.0 s
0 s
1800 s
Alarm S1
Setpoint
450.0 μS/cm (high)
-inf
+inf
Alarm S2
Setpoint
50.0 μS/cm (low)
-inf
+inf
Alarm S1
Hysteresis
4.500 μS/cm
0.0 μS/cm
+inf
Alarm S1
Delay time
0.2 s
0 s
+inf
Alarm S1
Expire Time
0.0 s
0 s
1800 s
Hold
Fixed value mA1
12 mA
3.6 mA
21 mA
Fixed value mA2
12 mA
3.6 mA
21 mA