3. Cabling
3-87
TI 32P01J10-01EN
Oct. 25, 2016-00
3.8.5
F-SB Bus (for N-IO Node)
The following figure shows a conne.
F030813.ai
F-SB bus cable (S2KLF10)
BUS2
BUS1
F-SB bus cable connector (BUS1)
F-SB bus cable connector (BUS2)
F-SB bus cable connector (BUS1)
F-SB bus cable connector (BUS2)
F-SB bus cable connector (BUS1)
F-SB bus cable connector (BUS2)
Connector
fixing screws
Connector
fixing screws
Node interface unit side
N-IO I/O unit side
N-IO I/O unit
N-IO I/O unit
Node interface unit
Figure F-SB Bus Connection
CAUTION
NIU and N-IO I/O Units can be installed in only the same cabinet.
When connecting a F-SB bus cable to N-IO node, ensure to keep the minimum bending radius of
the cable.
The minimum bending radius of the F-SB bus cable is six-fold of the diameter of the cable.