2. Transportation, Storage and Installation
2-24
TI 32P01J10-01EN
Node 7
Node 8
Node 9
Node 10
Node 11
F020519.ai
Node 1
(
S2SC70
-S
)
Node 2
Node 3
Node 4
Node 5
Node 6
≧
3U
≧
3U
≧
5U
Front
Rear
SNB10D/SNT10D
:
5 units maximum
Cabinet size
W: 800 mm
D: 800 mm
H: 2000 mm
1U = 1UNIT = 44.45 mm
Door fan
Primary power
supply bus unit
Roof vent
S2SC70
-S/SSC60
-S/SSC50
-S/SSC57
-S
:
1 unit
SNB10D/SNT10D
:
5 units maximum
Roof vent
Figure Installation of S2SC70
/SSC60
/SSC50
/SSC57
for Rittal cabinet (without Fan Unit)
·
Fan specifications
Door fan (on one side): Maximum air flow rate 230 m
3
/h or more
The roof vent must be larger than the opening area of the door fan.
·
I/O module installation restrictions
Refer to and follow the installation restrictions specified in “
NODE UNIT MOUNTING
RESTRICTIONS” in the “ProSafe-RS Outline of I/O Modules” (GS 32Q06K20-31E).
Installation Guideline for Rittal Cabinet (Up to 14 Nodes)
The following shows examples and notes for installing a safety control unit and up to 13 safety
node units in the Rittal TS8 cabinet. If the units are installed under the following conditions, the
temperature rise in the cabinet compared to the ambient temperature of the cabinet is 10°C or
lower.
Applicable Cabinet
Rittal TS8 cabinet (W: 800 mm D: 800 mm H: 2000 mm)
Temperature Conditions
·
Ambient temperature of the cabinet must be 50°C or lower.
·
Ambient temperature of the safety control unit and safety node units in the cabinet must
satisfy the temperature values specified in GS (General Specifications).
Oct. 25, 2016-00