iv
TI 30A30A10-01EN
n
Cautions for Safely Applying the Device
l
Wiring Power Cable
WARNING
Connect the power cables according to the procedure in this document.
Power cables must conform to the safety standards of the country where the device is installed.
SEE
ALSO
For wiring power cable, refer to 3.2, “Connecting power cable.”
l
Earth Wiring
WARNING
This equipment requires a protective grounding defined by the safety standard.
Ground the device following the procedure in this document to prevent from electric shock and to
minimize the noise.
SEE
ALSO
For earth wiring, refer to 3.3, “Connecting grounding cable.”
l
Tightening Torque of Screws
IMPORTANT
The tightening torque that the product recommends is showed in the following table. However,
if the tightening torque of the screw is specified in the User’s Manuals, follow the instructions
described in the User’s Manuals.
Table Recommended tightening torque
Nominal diameter of a screw
M2.6
M3
M3.5
M4
M5
M6
M8
M10
Recommended tightening torque
(N•m)
0.35
0.6
0.8
1.2
2.8
3.0
12.0
24.0
Feb. 26, 2018-00