4. Installation specifications
4-3
TI 30A30A10-01EN
l
Limited-life parts of the N-IO field enclosure for CENTUM VP
Table Periodic replacement parts having defined life spans
Part names
Part numbers
Recommended
replacement
cycle
Replacement
by user
Remarks
Field power supply
S9201UD
8 years
Yes
Average ambient temperature 40
°C
or less (*1)
Power supply unit
(100-240 V AC)
A2PW503-S0
30/NCBL
8 years
Yes
Average ambient temperature 40 °C
or less (*2)
N-ESB bus module
A2EN501-S1
3
A2EN501-S2
3
A2EN501-S
1
3
A2EN501-S
2
3
4 years
Yes
—
*1: This ambient temperature means the temperature inside the enclosure. Estimate the ambient temperature around the field power supply by
roughly 20 ° C higher than the outside of the enclosure.
*2: This ambient temperature means the temperature inside the enclosure. Estimate the ambient temperature around the power supply unit by
roughly 10 ° C higher than the outside of the enclosure.
l
Limited-life parts of the N-IO field enclosure for ProSafe-RS
Table Periodic replacement parts having defined life spans
Part names
Part numbers
Recommended
replacement
cycle
Replacement
by user
Remarks
Field power supply
S9201UD
8 years
Yes
Average ambient temperature 40
°C
or less (*1)
Power supply unit
(100-240 V AC)
S2PW503-S0
30
8 years
Yes
Average ambient temperature 40 °C
or less (*2)
N-ESB bus module
S2EN501-S1
3
S2EN501-S2
3
S2EN501-S
1
3
S2EN501-S
2
3
4 years
Yes
—
*1: This ambient temperature means the temperature inside the enclosure. Estimate the ambient temperature around the field power supply by
roughly 20 ° C higher than the outside of the enclosure.
*2: This ambient temperature means the temperature inside the enclosure. Estimate the ambient temperature around the power supply unit by
roughly 10 ° C higher than the outside of the enclosure.
Feb. 26, 2018-00