5-8. Fail
A fail contact is energized when a fail situation
occurs. Fail situations are configured in secton
5-11. For SOFT Fails the contact and the dis
-
play on LCD are pulsating. For HARD Fails the
contact and the display on LCD are energized
continuously.
Hard fail only
The contact reacts to Hard Fails Only
Hard + soft fail
The contact reacts to Hard and Soft Fails
Only contact S4 is programmed as a fail-safe
contact. This means that contact S4 wil be
de-energized when a fail situation occurs.
5-9. Simulate
The contact can be switched on/off or a
percentage of output can be simulated. On/Off
enables the user to manually switch a contact
on or off. The percentage is an analogue value
and represents the on time per period.
The Duty cyde Period time (see figure 5-4) is
used as a period for percentage simulation.
Note that the (simulated) settings of the con-
tacts become visible in measuring mode and
after HOLD has ended c.q. has been overruled.
A warning is activated in case of a simulated
output contact.
5-10. Input contacts
The terminal of the ISC450G provides for an in
-
put contact (see Figure 3-7). This input contact
can be used to switch the range of the outputs.
The range can be increased by 1 decade.
Содержание ISC450G
Страница 1: ...IM 12D06D05 01E 4th Edition User s Manual Model ISC450G Style S2 Inductive Conductivity Converter...
Страница 8: ...vi...
Страница 23: ...15 IM 12D06D05 01E 3 INSTALLATION AND WIRING Figure 3 11 a Figure 3 11 b Figure 3 11 c...
Страница 54: ...46 IM 12D06D05 01E...
Страница 55: ...47 IM 12D06D05 01E 10 SPARE PARTS 10 SPARE PARTS See Customer Maintenance Parts List...
Страница 66: ...58 IM 12D06D05 01E APPENDIX 6 Control drawing for FM approval...