9-1
IM 34M6H33-01E
1st Edition : July 1.2004-00
9.
Monitor Port Function
9.1 Monitor
Port
Connecting the monitor port on the ASi Master module to a PC using an RS-232C cable
allows a user to change the operating mode of the module, as well as display and
register slaves to the list of projected list on the module.
Monitor Port
MODE
MONITOR
Figure 9.1 Monitor Port
CAUTION
Do not connect to the monitor port during production operation, as this will affect normal
module operation.
By running a monitoring or configuration program, operations can be performed from a
standard terminal emulator such as a PC.
Use a RS-232C cross cable (with a D-SUB 9-pin connector at the F3LA01-0N end) to
connect to the monitor port.
PC
Figure 9.2 Connecting the ASi Master Module to a PC
Start a terminal emulator software application on the PC.
You may use the HyperTerminal application, which is included as a standard accessory
software application in the Microsoft windows operating system.
Set the parameters of Hyperterminal as follows.
Setup Item
Setup Value
Connection method
Direct to Com1
Bits per second
38400
Data bits
8
Parity None
Stop bits
1
Flow control
Xon/Xoff
Содержание FA-M3 Vitesse
Страница 2: ......
Страница 26: ...Blank Page...
Страница 38: ...Blank Page...
Страница 44: ...Blank Page...
Страница 54: ...Blank Page...
Страница 62: ...Blank Page...
Страница 64: ...Blank Page...
Страница 70: ...Blank Page...
Страница 72: ...Blank Page...
Страница 74: ...Index 2 IM 34M6H33 01E 1st Edition July 1 2004 00 Blank Page...
Страница 76: ...Blank Page...