B2-12
IM 34M06H63-01E
2nd Edition : Jul.16,2015-00
Two-input Changeover Function Settings
Use these parameters to perform setup when using Two-input Changover mode, as
required.
They can be used for setting the changeover mode and changeover temperature.
Table B2.14 Two-input Changeover Function Settings
Data Position Number
Symbol
Description
Unit
Data Range
Default
Value Attribute Stored
See
Also
CH1 CH2 CH3 CH4
361
761 SELMD Two-input
changeover
mode
None
0: Automatic changeover using
temperature range
1: Automatic changeover using
upper limit
2: Manual changeover using input
selection
0
RW
C2.11
362
762 SELH Two-input
changeover
upper limit
Industrial
unit
PRL to PRH if SELL < SELH. If
SELL
SELH, changeover occurs
with respect to SELH.
PRL+1
RW
363
763 SELL Two-input
changeover
lower limit
PRL
RW
Input Function Settings
Use these parameters to configure processing of input values of individual channels, as
required. They can be used for setting input correction, square root extraction and input
filtering of the input.
Table B2.15 Input Function Settings
Data Position Number
Symbol Description Unit
Data
Range
Default
Value
Attribute Stored See
Also
CH1 CH2 CH3 CH4
171 371 571 771 BS Input
correction
(biasing)
Industrial
unit
-(SH - SL) to (SH - SL)
0
RW
C2.8
172 372 572 772 FL Input
filter
Seconds 0:
OFF
1 to 120 seconds
0 RW
C2.10
173 373 573 773 X1 Broken-line
input
1
Industrial
unit
-5.0% to 105.0% of
(SH – SL)
SL RW
C2.7
174 374 574 774 Y1 Broken-line
bias
1 Industrial
unit
-(SH-SL) to (SH-SL)
0
RW
175 375 575 775 X2 Broken-line
input
2
Industrial
unit
-5.0% to 105.0% of
(SH – SL)
SL RW
176 376 576 776 Y2 Broken-line
bias
2 Industrial
unit
-(SH-SL) to (SH-SL)
0
RW
177 377 577 777 X3 Broken-line
input
3
Industrial
unit
-5.0% to 105.0% of
(SH – SL)
SL RW
178 378 578 778 Y3 Broken-line
bias
3 Industrial
unit
-(SH-SL) to (SH-SL)
0
RW
179 379 579 779 SR Square
root
extraction
None 0: OFF (no square root
extraction)
1: ON (square root
extraction)
0 RW
C2.9
180 380 580 780 LC Low
cut
Industrial
unit
0.0-5.0% of (SH-SL)
1.0% of
(SH-SL)
RW
Содержание FA-M3 VITESSE F3CX04-0N
Страница 2: ...Blank Page...
Страница 16: ...Blank Page...
Страница 18: ...Blank Page...
Страница 32: ...Blank Page...
Страница 44: ...Blank Page...
Страница 68: ...Blank Page...
Страница 80: ...Blank Page...
Страница 82: ...Blank Page...
Страница 90: ...Blank Page...
Страница 110: ...Blank Page...
Страница 111: ...C3 1 IM 34M06H63 01E 1st Edition July 2003 00 C3 Alarm Function This chapter describes the alarm functions of the module...
Страница 118: ...Blank Page...
Страница 126: ...Blank Page...
Страница 128: ...Blank Page...
Страница 132: ...Blank Page...
Страница 142: ...Blank Page...
Страница 144: ...Blank Page...