B2-5
IM 34M06H63-01E
2nd Edition : Jul.16,2015-00
For details on the procedure for enabling settings, see Section B2.3, “How to Enable
Settings”.
B2.2.3 Function Control Parameters
Use these parameters to define the operation of module functions on a module-wide
basis.
Table B2.6 Function Control Parameters
Data
Position
Number
Symbol
Description
Unit
Data Range
Default
Value
Attribute Stored
See
Also
75
NBKUP Disable backup
function
None 0: Enable backup to the EEPROM
1: Disable backup to the EEPROM
0
RW
C4.
B2.2.4 Monitoring Parameters
Use these parameters to set up the basic operation of the module, such as Input Sampling
Period and Monitoring Mode, on a module-wide basis.
Table B2.7 Monitoring Parameters
Data
Position
Number
Symbol
Description
Unit
Data Range
Default
Value
Attribute Stored
See
Also
81
FREQ Power supply
frequency selection
*1
None 0: 50Hz, 1: 60Hz
0
RW
C2.2
82
SMP Input Sampling period
*2
None 0: 100ms, 1: 200ms
1
RW
B3.1.2
83
MD12 Monitoring mode
None 0: Single-input mode ×2
1: Two-input changeover mode
3: Single-input mode
(Odd channel disabled)
4: Both channels disabled
0
RW
C1.
84
MD34
0
RW
*1
The power supply frequency can also be selected using a hardware switch selector. For details on how to do so, see
Section A4.1, “Selecting Input Types and Power Supply Frequency”. If the power supply frequency is set using the
hardware switch selector, the setting cannot be changed by software.
*2
This preset value imposes some restrictions on the number of channels that can be used. A value of 100ms allows up to
2 channels to be used, whilst a value of 200ms allows up to 4 channels to be used.
Monitoring parameters must be enabled before any written content can take effect. For
details on how to enable these parameters, see Section B2.3, “How to Enable Settings.”
Changing a monitoring parameter initializes other related parameters. Always set
monitoring parameters before setting input parameters and operation parameters.
You must observe some precautions when writing to the module. For details, see Section
B1.3, “Writing and Reading after Powering on.”
CAUTION
CAUTION
CAUTION
CAUTION
Содержание FA-M3 VITESSE F3CX04-0N
Страница 2: ...Blank Page...
Страница 16: ...Blank Page...
Страница 18: ...Blank Page...
Страница 32: ...Blank Page...
Страница 44: ...Blank Page...
Страница 68: ...Blank Page...
Страница 80: ...Blank Page...
Страница 82: ...Blank Page...
Страница 90: ...Blank Page...
Страница 110: ...Blank Page...
Страница 111: ...C3 1 IM 34M06H63 01E 1st Edition July 2003 00 C3 Alarm Function This chapter describes the alarm functions of the module...
Страница 118: ...Blank Page...
Страница 126: ...Blank Page...
Страница 128: ...Blank Page...
Страница 132: ...Blank Page...
Страница 142: ...Blank Page...
Страница 144: ...Blank Page...