C3-5
IM 34M06H63-01E
1st Edition : July, 2003-00
C3.2
Wait Function
When the wait function is specified, the alarm function is temporarily disabled (enters wait
state) for a specified period after the following events:
- Power up
- Change in SP number (SPNO)
Figure C3.2 below shows an example of the alarm function when the alarm type is set to
Lower Limit with Waiting.
Normal
Normal
Alarm
Power up
▲
Time
▲
Lower limit
ALM
ALMW
ON
ON
°C
Figure C3.2 Operation of the Wait Function
TIP
After an alarm condition is detected, the module again enters wait state if one of the following event
occurs:
- Power up
- Change in SP number (SPNO)
- Change in alarm type