A2-4
IM 34M06H63-01E
2nd Edition:Jul.16,2015-00
Table A2.4 Instrument Range and Accuracy (for low resolution operation with SW1-1 set to OFF) 2/4
Input
Cat
eg
o
ry
Input
Type
*1
Instrument Default
Range
Input Type Selector Switch
*3
Software
Setting
Accuracy
*4
Resolution
*2
SW1-3
SW1-4
SW5
Software setting
ON
OFF
0
Instrument default ranges may be specified
by software using one of the following codes.
Thermoco
uple
K
*5
-200 to1370
C
ON OFF
1 33
($21)
2
C
*5
1
C
*5
-200 to1000
C 2
34
($22)
-200 to500
C 3
35
($23)
2
C 1
C
J
-200 to 1200
C 4
36
($24)
-200 to 500
C 5
37
($25)
T
-270 to 400
C 6
38
($26)
2
C
*6
1
C
B
*7
0
to
1600
C 7
39
($27)
2
C
*7
1
C
*7
S
*8
0 to 1600
C 8
40
($28)
2
C 1
C
R
*9
0
to
1600
C 9
41
($29)
N
-200 to 1300
C A
42
($2A)
2
C
*9
1
C
E
-270 to 1000
C B
43
($2B)
2
C
*10
1
C
*10
L
-200 to 900
C C
44
($2C)
2
C 1
C
U
-200 to 400
C D
45
($2D)
W
*11
0
to
1600
C E
46
($2E)
Platinel 2
0 to 1390
C F
47
($2F)
RT
D
JPt100
-200 to 500
C
ON ON
0 48
($30)
2
C 1
C
-200 to 200
C 1
49
($31)
0 to 300
C 2
50
($32)
0.0 to 150.0
C 3
51
($33)
0.3
C 0.1
C
Pt100
-200 to 850
C 4
52
($34)
2
C 1
C
-200 to 500
C 5
53
($35)
-200 to 200
C 6
54
($36)
0 to 300
C 7
55
($37)
0.0 to 150.0
C 8
56
($38)
0.3
C 0.1
C
*1:
Applicable standard is JIS/IEC/DIN (ITS-90) for thermocouples and RTD.
*2:
For thermocouples K, B, S, R, and W, instrument default ranges may be changed to wider ranges (see the notes below). Furthermore,
the actual range for acceptable input is instrument range
5%.
*3:
Data stored in the EEPROM is initialized to follow the hardware switch when power is turned on.
*4:
This accuracy applies if the ambient temperature is 25
5
C and the input value is within the instrument range. If the input type is
thermocouple and reference junction compensation is used, you should also take into consideration the accuracy of the reference
junction compensation.
*5:
For K-type thermocouples, the upper and lower range limits may be set from -270 to 1370
C. The accuracy and resolution depend on
measured temperatures as follows:
-270
to
-200
C: Neither accuracy nor resolution is guaranteed.
*6:
For T-type thermocouples, the accuracy and resolution depend on measured temperatures as follows:
-270
to
-200
C:
4
C accuracy, 1
C resolution
*7:
For B-type thermocouples, the upper and lower range limits may be set from 0 to 1800
C. The accuracy and resolution depend on
measured temperatures as follows:
0 to 300
C: Neither accuracy nor resolution is guaranteed.
300 to 900
C:
3
C accuracy, 1
C resolution
*8:
For S-type and R-type thermocouples, the upper and lower range limits may be set from 0 to 1700
C.
*9:
For N-type thermocouples, the accuracy and resolution depend on measured temperatures as follows:
-200
to
0
C:
3
C accuracy, 1
C resolution
*10: For E-type thermocouples, the detailed accuracy and resolution are as follows:
-270
to
-200
C:
8
C accuracy, 2
C resolution
-200
to
1000
C:
2
C accuracy, 1
C resolution
*11: For W-type thermocouples, the upper and lower range limits may be set from 0 to 2300
C.
Содержание FA-M3 VITESSE F3CX04-0N
Страница 2: ...Blank Page...
Страница 16: ...Blank Page...
Страница 18: ...Blank Page...
Страница 32: ...Blank Page...
Страница 44: ...Blank Page...
Страница 68: ...Blank Page...
Страница 80: ...Blank Page...
Страница 82: ...Blank Page...
Страница 90: ...Blank Page...
Страница 110: ...Blank Page...
Страница 111: ...C3 1 IM 34M06H63 01E 1st Edition July 2003 00 C3 Alarm Function This chapter describes the alarm functions of the module...
Страница 118: ...Blank Page...
Страница 126: ...Blank Page...
Страница 128: ...Blank Page...
Страница 132: ...Blank Page...
Страница 142: ...Blank Page...
Страница 144: ...Blank Page...