9. General Specifications
>
9-2
IM 01C25F01-01E
Output “◊”
For 4 to 20 mA output
(Output signal code D, E and J)
Two wire 4 to 20 mA DC output with digital
communications, linear or square root
programmable. BRAIN or HART FSK protocol
are superimposed on the 4 to 20 mA signal.
Output range: 3.6 mA to 21.6 mA
Output limits conform to NAMUR NE43 can be
pre-set by option C2 or C3.
For 1 to 5 V output
(Output signal code Q)
Three or four wire low power 1 to 5 V DC output
with HART, linear or square root programmable.
HART protocol is superimposed on the 1 to 5 V
DC signal.
Output range: 0.9 V to 5.4 V DC
Failure Alarm “◊”
For 4 to 20 mA output
(Output signal code D, E and J)
Analog output status at CPU failure and
hardware error;
Up-scale: 110%, 21.6 mA DC or more
(standard)
Down-scale: –5%, 3.2 mA DC or less
For 1 to 5 V output
(Output signal code Q)
Analog output status at CPU failure and
hardware error;
Up-scale: 110%, 5.4 V DC or more
(standard)
Down-scale: −5%, 0.8 V DC or less
Damping Time Constant (1st order)
Amplifier damping time constant is adjustable
from 0 to 100.00 seconds and added to
response time.
Note: For BRAIN protocol type, when amplifier damping
is set to less than 0.5 seconds, communication
may occasionally be unavailable during the
operation, especially while output changes
dynamically. The default setting of damping
ensures stable communication.
Update Period “◊”
45 ms
Zero Adjustment Limits
Zero can be fully elevated or suppressed, within
the lower and upper range limits of the capsule.
External Zero Adjustment “◊”
External Zero is continuously adjustable with
0.01% incremental resolution of span. Re-range
can be done locally using the digital indicator
with range-setting switch.
Integral Indicator (LCD display)
5-digit Numerical Display, 6-digit Unit Display
and Bar graph.
The indicator is configurable to display one or
up to four of the following variables periodically.;
Pressure in %, Scaled pressure, pressure in
Engineering unit.
See “Setting When Shipped” for factory setting.
Burst Pressure Limits
EJ
510
and EJ
530
Capsule
Pressure
A, B, C
30 MPa (4350 psi)
D *
132 MPa (19100 psi)
*: 182 MPa (26300 psi) for EJA510E and EJA530E when
/HG is specified.
EJX610A and EJX630A
Capsule
Pressure
A, B, C
50 MPa (7200 psi)
D
182 MPa (26300 psi)
Normal Operating Condition
(Selected features may affect limits.)
Ambient Temperature Limits
–40 to 85°C (–40 to 185°F)
–30 to 80°C (–22 to 176°F) with LCD display
Process Temperature Limits
–40 to 120°C (–40 to 248°F)
Ambient Humidity Limits
0 to 100% RH
Working Pressure Limits (Silicone oil)
Maximum Pressure Limits
Pressure
Capsule
EJ
510
EJ
530
A
200 kPa abs (29 psia)
200 kPa (29 psig)
B
2 MPa abs (290 psia)
2 MPa (290 psig)
C
10 MPa abs (1450 psia)
10 MPa (1450 psig)
D*
50 MPa abs (7200 psia)
50 MPa (7200 psig)
*: 70 MPa(10150 psi) for EJA510E and EJA530E when
/HG is specified.
Pressure
Capsule
EJX610A
EJX630A
A
200 kPa abs (29 psia)
200 kPa (29 psi)
B
2 MPa abs (290 psia)
2 MPa (290 psi)
C
10 MPa abs (1450 psia)
10 MPa (1450 psi)
D
70 MPa abs (10150 psia) 70 MPa (10150 psi)
Minimum Pressure Limit
See graph below