CONNECT REFRIGERANT PIPES BETWEEN INDOOR AND OUTDOOR UNITS
Seal Copper Line Set/Wire and Cable/Drain Hose Line Combination
•
Run cables along with the refrigerating copper line sets and secure them with tape, 6 feet apart.
•
Wrap tape tight (cover a third of the width of the wrapping tape applied early) to ensure a good seal.
•
Tape and seal the end of the wrapping tape.
•
Shape the pipe combination gently, without causing kinking, sharp bends, or other damage to it.
•
Fix the pipe combination securely on the external wall with proper clamps, 6 feet apart.
•
Fill the gap between the wall hole and wall sleeve with putty to keep rain or dust entering inside.
PIPING GUIDE
Set the packed pipes in a vertical
position and then unwind them
slowly.
Do not unwind only one end of the
coiled pipes.
Use pulley or a bending tool to
ensure a safe bending radius.
Do not make any sharp or small
radius bends.
May also use rolling wheel to
reduce internal pipe tension and
avoid possible deformation.
Do not bend long sections of pipe
without using bending tools.
Use an elbow tool for consistent
bending radius.
Do not make bends that are less
than 90 degrees.
Maintain the minimum bending
radius.
Do not bend shot pipes.