Functions
Set Capacity Dip Switch
Set the capacity of the outdoor unit through the four dip switches of the outdoor unit main control board.
Specific dip switch definition, the first dip switch distinguishes the capacity.
Capacity
24K
36K
48K
60K
Dip Switches
Set Defrost Mode
The second dip switch is selecting the defrost mode.
The second dip switch is used to change the defrost setting, factory default setting is standard defrost. Under extremely
low environment temperature, if the standard defrost does not have the condenser defrosted completely, please set the
second dip switch to Strong Defrost. Under strong defrost, the defrosting time will run longer, and enable the condenser to
be defrosted completely.
Defrost mode
Outdoor unit dip switches
Standard Defrost
(Default)
Strong Defrost
Set Operating Mode
The third dip switch and the fourth dip switch select the operating mode.
Standard mode is the conventional mode.
By setting the strong mode dip switches of the condensing unit, the air conditioner can quickly increase the capacity
output and ensure reliable operation in a short time, so as to meet the user's demand for the indoor temperature to
quickly reach the set temperature.
Energy saving mode is achieved by setting the condensing unit operating mode to operate the air conditioner within
a small load range.
Operating mode
Outdoor unit dip switches
Standard mode (Default)
Strong mode
Energy saving mode