“E3” Compressor Low-pressure Protection, Refrigerant Shortage
Protection, Refrigerant Recovery Mode
Error display:
ODU mainboard LED displayer
Error judgment condition and method:
It is judged through the action of low pressure switch. If the low pressure switch is cut off, it is judged that low pressure is
too low and the system stops operation for protection.
Possible reason
:
Cut-off valve of ODU is not fully opened
Low pressure sensor is abnormal
Outdoor or indoor fan is not working properly
IDU filter or air duct is blocked (cooling mode)
Ambient temperature is too low
Refrigerant charging amount is insufficient
System pipeline is blocked
Troubleshooting: