1. Tighten the power wires respectively on the terminal boards using the screws. Faulty connections can
result in a fire.
2. If the power supply wires are connected incorrectly the air conditioner may be damaged.
3. Connect the indoor unit connection cord properly based on the corresponding marks as shown in the
illustrations on the previous page.
4. Ground both the indoor and outdoor units using a ground wire.
5.
The unit should be grounded in compliance with the applicable local and national codes.
Installation of Controllers
Refer to the Installation Manual of the controller for more details.
Test Running
Trial Operation and Testing
1. The error codes and definitions:
Number
Error Code
Error
1
E1
Compressor high pressure protection
2
E2
Indoor anti-freeze protection
3
E3
Compressor low pressure protection, refrigerant lack protection and refrigerant
collecting mode
4
E4
Compressor high discharge temperature protection
5
E5
AC over-current protection
6
E6
Communication error
7
E7
Mode conflict
8
E8
Anti-high temperature protection
9
E9
Full water protection
10
F1
Indoor ambient temperature sensor is open/short circuited
11
F2
Indoor evaporator temperature sensor is open/short circuited
12
F3
Outdoor ambient temperature sensor is open/short circuited
13
F4
Outdoor condenser temperature sensor is open/short circuited
14
F5
Outdoor discharge temperature sensor is open/short circuited
15
C5
Jumper cap malfunction protection
16
EE
Loading EEPROM malfunction
Notes:
If you see an error code not listed, please contact qualified professionals for service.
When the unit is connected to the wired controller, the error code will be simultaneously shown on it.