TROUBLESHOOTING

TROUBLESHOOTING

Change capacitor. And connect the circuit
diagram correctly

Check with a multimeter if the enclosed 
motor windings of compressor is with short 
or broken circuit or earthing. If so replace 
with the same type and specifications.

Knock the compressor housing with a rubber 
or with a tap the compressor housing with 
rubber mallet or block of wood. This may 
loosen compressor and ran. If not change 
compressor wood, the compressor might be 
shocked and run. If not, change the compressor.

Breakage of compressor capacitor or wrong
wire connection

The motor of compressor is damaged.

The compressor is jammed or blocked.

The compressor is not
running (controller
with output)

Check leakage, carry out vacuum-pumping 
after repairing leakage and charge refrigerant 
according to requirements

Observe the condensation condition of 
evaporator or the reading of high pressure 
meter to judge if the system is blocked; deal 
with the system accordingly

Charge excess refrigerant in the system

Replace it with a new compressor

Clear the obstacle

1. Connecting wire is loose
2. Fuse is off
3. Thermostat or is broken
4. Electric heater is broken
5. Correct wire connection or replace broken 
    parts

It is available to install a shade guarding 
against sun and rain..If the maximum cooling 
capacity still could not ,replace the unit.

Check the forecasted load of cooling
(heating).

Keep a proper sealing for the room and it is
recommended not to use electric appliance 
with too much heating when cooling.

Check the reason and correct it.

Insufficiency or leakage of refrigerant

Blockage in cooling system

Excess refrigerant

Low efficiency of compressor itself

Condensate can not be smoothly discharged

During heating, electric heater does not work

Outdoor temperature is too high

If cooling (heating) load is proper

The room is not properly sealed and there is
frequent passage of personnel, or when
cooling, there is heating device in the room

The voltage is not stale

Air conditioning unit 
is running but there 
is no cooling effect
(or no heating effect)

Protector is activated
due to too overheat
of compressor.

Adjust the volume of refrigerant

Change capillary

Change compressor

Check with a multimeters and see if the 
contacts of compressor are normal when 
they are not overheated. If not, change the 
protector

Shortage or too much of refrigerant

The capillary is block and the sucfiun
temperature pressure is increased

Compressor does not run, jammed or blocked,
and the discharge valve is damaged

Failure exists in the protector

Check if the ground leg is stable.

Adjust the location of the unit.

Fix the stand or install again.

Take out the foreign object.

Tighten the screw.

The installation of compressor is not proper
and the ground leg is not stable.

The system is not level

The system stand is not stable

Foreign object exists in the unit

Screw loose

Abnormal noise and 
vibration

Check for the circuit with the circuit diagram

Change fan capacitor of same model and
specification

Replace the failed components

Replace the controller

Wrong wire connection

Damage of fan capacitor

The motor winding is of broken circuit or 
short circuit or the built in temperature limiter 
device in open circuit due to over heat

Malfunction of controller

Fan doesn't run
during air supply

Replace the battery

Replace the battery

Fix the LED frame properly

Shortage of battery capacity

Shortage of battery capacity

The LED frame is not properly fixed

Receiving distance of 
remote control is 
short

LED display flashes 
or when pressing
the transmit button 
the entire screen is
displayed.

LED display is found 
short of stroke

The compressor is
frequently ON/OFF

Abnormal power voltage

The system is of a bad heat sinking and the
ventilation is poor

The air conditioner capability does not match 
the area of the room, i.e. so called "Big 
system, small room"

Check for the causes. Improve the power 
supply conditions, and add voltage regulated 
power supply

Clean the dust deposited on the system and 
remove obstacles at the aid discharge vent

Select an air conditioner meeting the area of 
the room

YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World !

YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World !

Содержание PTAC Series

Страница 1: ...ONDITIONER PTAC PACKAGED TERMINAL HEAT PUMP PTHP INSTALLATION OPERATION MANUALS Literature Part No Lit PTAC 0201 20140505 Subject to Continuous Engineering Change and Product Improvement without Notic...

Страница 2: ...cident or consequence of improper or faulty transportation installation operation maintenance or service Damage caused by frozen or broken water hoses or refrigeration pipes in the event of equipment...

Страница 3: ...it for condensate leakage and refrigerant leakage before and after connecting them 28 Do you list the working details in the invoice and leave a copy to the customer 19 Did you charge the inter connec...

Страница 4: ...roperly can be more expensive than spending the little extra money that hiring the right contractor will cost Protect your investment and warranty eligibility by doing it right the first time THE FOLL...

Страница 5: ...ity to claim freight damage is lost and YMGI will not replace the unit on this basis Contact the distributor or YMGI report the damage by forwarding the marked delivery receipt copy and pictures Only...

Страница 6: ...ip Products to YMGI Service Center for Inspection and Repair and Authorization to Charge form 2 You will review the form and fill all fields appropriately sign and send back to the YMGI Group 3 Once t...

Страница 7: ...Instructions for Removal and Repairs If the unit needs to be removed to somewhere else or needs repair contact your dealer or an authorized technician In the case of occurrence of abnormal operation b...

Страница 8: ...e Weight Net Gross Weight Refrigerant Name Charge Outdoor Side Loading Quantity Fan Type Fan Wheel Dia x Length Fan Motor Speed H ML Output of Fan Motor Fan Motor RLA Fan Motor Capacitor Input of Heat...

Страница 9: ...ed Limit the Set point Range The unit can be configured to limit the controlling set point range The display will always show the complete set point range but the controlling set point will be limited...

Страница 10: ...lure to follow this warning could result in personal injury or death Disconnect all power to unit to avoid possible electrical shock during installation Remove any existing foam baffles that are insta...

Страница 11: ...owing electrical safety data carefully ELECTRICAL SHOCK AND OR UNIT OPERATION AND DAMAGE HAZARD Failure to follow this warning could result in personal injury or death and or unit operation and damage...

Страница 12: ...eating and cooling modes regardless of what the real temperature is in the room If AA mode is selected the room temperature will be displayed during heating cooling and fan only modes If the mode butt...

Страница 13: ...required for digital thermostats NOTE Any illegal input combinations will be captured as thermostat wiring failures and will light the STATUS LED indicator on main board see Intelligent Self Checking...

Страница 14: ...d Room humidity will decrease and moisture will evaporate NOTE In case of a power failure the unit will remember the last programmed settings and will restart to those settings 1 TEMP CONTROL Temp Con...

Страница 15: ...TAC 07K 12B 43 PTAC 09K 12B 43 PTAC 12K 12B 43 PTAC 07K 12D 43 PTAC 09K 12D 43 PTAC 12K 12D 43 PTHP 07K 14B 43 PTHP 09K 14B 43 PTHP 12K 14B 43 PTHP 07K 14D 43 PTHP 09K 14D 43 PTHP 12K 14D 43 Symbol Sy...

Страница 16: ...connected and check if power supply failed or cut off Replace fuse Check power voltage If it is 10 below rated voltage inspect and repair line Check if option switch ON OFF is disconnected with line h...

Страница 17: ...is running but there is no cooling effect or no heating effect Protector is activated due to too overheat of compressor Adjust the volume of refrigerant Change capillary Change compressor Check with...

Страница 18: ...0 577 0 561 0 547 0 532 0 519 0 505 0 492 0 48 0 467 0 456 0 444 0 433 0 422 0 412 0 401 0 391 0 382 AMBIENT AIR TEMPERATURE SENSOR S INDOOR AND OUTDOOR TUBE TEMPERATURE SENSOR S 19 18 17 16 15 14 13...

Страница 19: ...ler or current service contractor should be contacted first of all since they installed the unit and or know more details than anybody else They will check the unit and find out the problems with the...

Отзывы: