Yingli Solar PV Modules, Installation and User Manual 

page 5

Installation of grounding lugs must be in accordance with the specified 
instructions of the respective manufacturers. A grounding lug must be attached 
at a designated grounding hole location using #10 stainless steel hardware. 
A stainless steel toothed lock washer or KEPS nut is required to adequately 
engage the frame and penetrate the nonconductive coating. The screw holding 
the appropriately sized EGC in place must firmly clamp the EGC in order to 
establish a reliable electrical bond.

 

Figure 8: Grounding lug detail

Option B: Screw Assembly

1.  A grounding screw assembly must be attached at a designated grounding hole 

location using only stainless steel hardware. Insert a #10 stainless steel screw 
first through the stainless steel cup washer, and then through the grounding 
hole. 

2.  Loosely engage a stainless steel backing nut and toothed lock washer to the 

screw. 

3.  Bend the EGC into an omega (Ω) shape to tightly fit between the partially 

installed screw head and cup washer. The EGC shall be exclusively in contact 
with stainless steel. 

4.  Tighten the screw to 35 in-lbf (4 N∙m) torque. The toothed lock washer 

should be visibly engaged to the frame. 

5.  Route the appropriately sized EGC in such a way as to avoid contact with the 

aluminum module frame. 

 

 
 
 
 
 
 
 
 

Figure 9: Grounding screw assembly detail

Option C: Racking Manufacturer Integrated  

Grounding Methods

Yingli Solar PV modules can be grounded by bonding PV modules to a grounded 
racking system. Integrated grounding methods must be certified to UL 1703 or 
2703 for grounding PV modules and must be installed in accordance with the 
specified instructions of their respective manufacturers. 

A.Where common grounding hardware (nuts, bolts, star washers, spilt-ring lock 
washers, flat washers and the like) is used to attach a listed grounding/bonding 
device, the attachment must be made in conformance with the grounding 
device manufacturer’s instructions.

B.Common hardware items such as nuts, bolts, star washers, lock washers 
and the like have not been evaluated for electrical conductivity or for use 
as grounding devices and should be used only for maintaining mechanical 
connections and holding electrical grounding devices in the proper position 
for electrical conductivity. Such devices, where supplied with the module and 
evaluated through the requirements in UL 1703, may be used for grounding 
connections in accordance with the instructions provided with the module.

M E C H A N I C A L   I N S TA L L AT I O N

Mounting structures and other mechanical parts must be designed and approved 
to withstand the design wind and snow loads applicable for a particular site. 
Yingli Solar PV modules must not be subjected to forces from the substructure, 
including forces caused by thermal expansion. 

The mounting method must not result in the direct contact of dissimilar 
metals with the aluminum frame of the PV module that will result 

 

in galvanic corrosion. An addendum to UL 1703 recommends metal 
combinations not exceed an electrochemical potential difference of 

 

0.5 Volts.

Yingli Solar PV modules can be mounted in landscape or portrait orientation, as 
illustrated in Figure 10, provided that the mounting method follows one of the 
acceptable methods listed below. 

Figure 10: Landscape and portrait mounting

In order to maintain the fire class rating, the distance between the PV module 
bottom surface and the roof surface shall be at least 2.48 inches (6.3 cm). This 
spacing also allows air flow to cool the PV module. Install PV modules with a 
minimum spacing of 0.4 inches (1 cm) between neighboring frames to allow for 
thermal expansion.

 

Mounting Methods

The PV module is considered to be in compliance with UL 1703 only when the 
PV module is mounted in the manner specified by the mounting instructions PV 
module below.

Option A: Bolts or clamps

Refer to the Module Supplement at the end of this manual to determine how 
many connection points are required for a specific module series. The locations 
of mounting holes and clamp tolerances are illustrated in the drawings located 
in the Module Supplement. Do not modify the existing mounting holes or drill 
new holes. The minimum tightening   force of the following mounting methods 
are both 4N.m.

Landscape Orientation

Portrait Orientation

PV Laminate

Backing Nut

Toothed Lock Washer or KEPS Nut

Cup Washer

Aluminum 

Frame

Screw

Equipment 

Grounding 

Conductor

PV Laminate

Backing Nut

Toothed Lock Washer or KEPS Nut

Grounding Lug

Equipment 

Grounding 

Conductor

Aluminum 

Frame

Screw

Содержание PANDA 48 Cell Series

Страница 1: ...ngli Solar at the time of sale to the direct customer Additional recommendations are provided to enhance safety practices and performance results Please provide a copy of this manual to the PV system...

Страница 2: ...PV module surfaces and do not apply paint or adhesive to any of the surfaces including the frame For your safety do not disassemble or modify Yingli Solar PV modules in any way Doing so may degrade pe...

Страница 3: ...m2 AM 1 5 and 25 C cell temperature As required by the US National Electric Code NEC the short circuit current Isc should be multiplied by a factor of 1 25 and the open circuit voltage Voc should be m...

Страница 4: ...rts of fixed equipment that are able to become energized by the PV system must be connected to the equipment grounding conductor in order to prevent electrical shock Refer to section 250 of the NEC fo...

Страница 5: ...for maintaining mechanical connections and holding electrical grounding devices in the proper position for electrical conductivity Such devices where supplied with the module and evaluated through the...

Страница 6: ...ds that PV systems be periodically inspected by the installer or other qualified person ThepurposeofthePVsysteminspectionistoensurethatallsystemcomponents are functioning properly At a minimum this in...

Страница 7: ...The fifth 2014 Installation Manual_UL_ EN_201404_v02 1 August 6 2014 The sixth 2014 Installation Manual_UL_ EN_201408_v02 2 March 18 2015 The seventh 2015 Installation Manual_UL_ EN_201503_v02 3 June...

Страница 8: ...t of the indicated values of Isc Voc and Pmax under Standard Test Conditions irradiance of 1000 W m2 AM 1 5 spectrum and a cell temperature of 25 C Refer to module datasheets for specific power output...

Страница 9: ...YL240C 30b 240 30 3 7 93 38 0 8 47 1000 15 YL235C 30b 235 29 9 7 87 37 6 8 41 1000 15 YL230C 30b 230 29 6 7 76 37 0 8 40 1000 15 YL225C 30b 225 29 4 7 66 36 4 8 39 1000 15 PANDA 48 Cell Series YL215C...

Страница 10: ...0 38 07 967 43 31 1100 3 94 100 2 17 55 3 94 100 3 94 100 A A A A 38 98 990 37 24 946 1 97 50 22 72 577 16 02 408 77 56 1970 22 72 577 77 56 1970 47 24 1200 3 94 100 Grounding holes 6 0 236 6 Mounting...

Страница 11: ...AR AND SIDE VIEW DIMENSIONS OF MODULE SERIES UNITS INCH mm PANDA 48 Cell SERIES PANDA 60 Cell SERIES Legend Legend Grounding holes Mounting holes Drainage holes Mounting tolerance PANDA 48 Cell PANDA...