Yingli Solar PV Modules, Installation and User Manual 

page 4

damage of the cable and/or the module is avoided. Maintain a minimum cable 
bending radius greater or equal than five times the cable diameter. Route 
the cable in a way that the tensile stress on the conductor or connections is 
prevented. For fixing, use appropriate means, such as sunlight resistant cable 
ties and/or wire management clips specifically designed to attach to the PV 
module frame. While the cables are sunlight resistant and waterproof, where 
possible, avoid direct sunlight exposure and water immersion of the cables.

Connectors

Protect unplugged connectors against moisture, dust 
and any environmental pollution. Only clean and dry 
plugged connectors fulfill their ingress protection (IP) 
class. Ensure that connector caps are hand tight before 
connecting the modules. Do not attempt making an 
electrical connection with wet, soiled, or otherwise 

faulty connectors. Avoid sunlight exposure and water immersion of the 
connectors. Avoid connectors resting on the ground or roof surface. 

Faulty connections can result in arcs and electrical shock. Check that all electrical 
connections are securely fastened. Make sure that all locking connectors are 
fully engaged and locked.

Connectors of different manufacturers must not be mated. If necessary the 
connection of modules can be made by technical personnel after the connector 
has been exchanged for one of the same manufacturer. Guarantee and warranty 
claims are not affected by a professional exchange. 

Figure 5: Series interconnection of a male (-) and female (+) connector

The junction boxes used with Yingli Solar PV modules contain bypass diodes 
wired in parallel with the PV cell strings. In the case of partial shading, the 
diodes bypass the current generated by the non-shaded cells, thereby limiting 
module heating and performance losses. Bypass diodes are not overcurrent 
protection devices. 

Bypass diodes divert current from the cell strings in the event of partial 
shading. See Figure 6 for a diagram showing how the cell strings are electrically 
connected with the diodes.

Figure 6: Electrical circuitry of cells and bypass diodes

In the event of a known or suspected diode failure, installers or maintenance 
providers should contact the company the PV modules were purchased from. 
Never attempt to open the junction box of a Yingli Solar PV module yourself; 
replacing diodes inside the junction box is not permitted.

 

Equipment Grounding

The frame of the PV module, as well as any exposed non-current-carrying metal 
parts of fixed equipment that are able to become energized by the PV system, 
must be connected to the equipment grounding conductor in order to prevent 
electrical shock. Refer to section 250 of the NEC for specific instructions on 
grounding. Even when applicable regulations, code requirements, and standards 
do not require safety-related grounding, Yingli Solar recommends grounding all 
PV module frames in order to ensure the voltage between electrically conductive 
equipment and earth ground is zero in all circumstances. A PV module with 
exposed conductive parts is considered to be in compliance with UL 1703 only 
when it is electrically grounded in accordance with the instructions presented 
below and the requirements of the National Electrical Code.

Proper equipment grounding is achieved by bonding all exposed non-current-
carrying metal equipment continuously to one another using an appropriately 
sized equipment grounding conductor (EGC) or racking system that can be used 
for integrated grounding (see Option C in Grounding Methods below). 

Yingli Solar PV modules employ a coated aluminum frame for corrosion 
resistance. In order to properly ground the module frame, the coating must be 
penetrated. 

Grounding wire use copper wire with minimum 12 AWG insulated for a 
minimum 90 ºC.

The potential for corrosion due to the electrochemical action between dissimilar 
metals in contact is minimized if the electrochemical voltage potential between 
the dissimilar metals is low. The grounding method must not result in the direct 
contact of dissimilar metals with the aluminum frame of the PV module that 
will result in galvanic corrosion. An addendum to UL 1703 recommends metal 
combinations not exceed an electrochemical potential difference of 0.5 Volts.

The frame rails have pre-drilled holes marked with a grounding sign, as 
illustrated in Figure 7. These holes should be used for grounding purposes and 
must not be used for mounting the PV modules. Do not drill additional holes 
into the frame rails. 

Where common grounding hardware (nuts, bolts, star washers, spilt-ring lock 
washers, flat washers and the like) is used to attach a listed grounding/bonding 
device, the attachment must be made in conformance with the grounding 
device manufacturer’s instructions.

 
 
 
 
 
 
 
 
 
 

 

Figure 7: Grounding hole detail

The following grounding methods are available:

Option A: Grounding Lugs

Manufacturer

Part Number

Material

Tightening Torque

ILSCO

GBL-4DBT

Tin-plated copper

20 to 25 in-lbf 
(2.3 to 2.6 N∙m)

Burndy

®

CL501-TN

Tin-plated copper

20-25 in-lbf 
(2.3 to 2.6 N∙m)

Tyco Electronics

SolKlip 
1954381-4

Nickel and  
tin-plated copper

15 +4.4/-1.7 in-lbf 
(1.7+0.5/-0.2 N∙m)

Table 2: Grounding lug specifications

Grounding Holes

ø0.236in (6mm)

Fully engage and lock

Cap

+

Содержание PANDA 48 Cell Series

Страница 1: ...ngli Solar at the time of sale to the direct customer Additional recommendations are provided to enhance safety practices and performance results Please provide a copy of this manual to the PV system...

Страница 2: ...PV module surfaces and do not apply paint or adhesive to any of the surfaces including the frame For your safety do not disassemble or modify Yingli Solar PV modules in any way Doing so may degrade pe...

Страница 3: ...m2 AM 1 5 and 25 C cell temperature As required by the US National Electric Code NEC the short circuit current Isc should be multiplied by a factor of 1 25 and the open circuit voltage Voc should be m...

Страница 4: ...rts of fixed equipment that are able to become energized by the PV system must be connected to the equipment grounding conductor in order to prevent electrical shock Refer to section 250 of the NEC fo...

Страница 5: ...for maintaining mechanical connections and holding electrical grounding devices in the proper position for electrical conductivity Such devices where supplied with the module and evaluated through the...

Страница 6: ...ds that PV systems be periodically inspected by the installer or other qualified person ThepurposeofthePVsysteminspectionistoensurethatallsystemcomponents are functioning properly At a minimum this in...

Страница 7: ...The fifth 2014 Installation Manual_UL_ EN_201404_v02 1 August 6 2014 The sixth 2014 Installation Manual_UL_ EN_201408_v02 2 March 18 2015 The seventh 2015 Installation Manual_UL_ EN_201503_v02 3 June...

Страница 8: ...t of the indicated values of Isc Voc and Pmax under Standard Test Conditions irradiance of 1000 W m2 AM 1 5 spectrum and a cell temperature of 25 C Refer to module datasheets for specific power output...

Страница 9: ...YL240C 30b 240 30 3 7 93 38 0 8 47 1000 15 YL235C 30b 235 29 9 7 87 37 6 8 41 1000 15 YL230C 30b 230 29 6 7 76 37 0 8 40 1000 15 YL225C 30b 225 29 4 7 66 36 4 8 39 1000 15 PANDA 48 Cell Series YL215C...

Страница 10: ...0 38 07 967 43 31 1100 3 94 100 2 17 55 3 94 100 3 94 100 A A A A 38 98 990 37 24 946 1 97 50 22 72 577 16 02 408 77 56 1970 22 72 577 77 56 1970 47 24 1200 3 94 100 Grounding holes 6 0 236 6 Mounting...

Страница 11: ...AR AND SIDE VIEW DIMENSIONS OF MODULE SERIES UNITS INCH mm PANDA 48 Cell SERIES PANDA 60 Cell SERIES Legend Legend Grounding holes Mounting holes Drainage holes Mounting tolerance PANDA 48 Cell PANDA...

Отзывы: