Cause: The cable may be cut or the socket may be disconnected. The indoor temperature sensor may
have failed.
Device Response: When the device sees the error, it wants to switch to stop mode.
Troubleshooting:
* Check the internal temperature sensor cable and sockets.
* Remove the internal temperature sensor and check by applying resistance test.
If the internal resistance is > 15KΩ değiştir, replace the internal temperature sensor.
* If the resistance test is OK, replace the YHC.
* Reset the device from the button or disconnect the system from the power supply and connect again.
E 07 : Indoor Temperature Sensor Open Circuit
Cause: The cable may be cut or the socket may be disconnected. The flame monitoring sensor may
have failed.
Device Response: When the device sees the error, it wants to switch to stop mode.
Troubleshooting:
* Check the internal temperature sensor cable and sockets.
* Remove the internal temperature sensor and check by applying resistance test.
If the internal resistance is > 70KΩ, replace the flame monitoring sensor. @ 20 ° C
* If the resistance test is OK, replace the YHC.
* Reset the device from the button or disconnect the system from the power supply and connect again.
E 08 : Flame Monitoring Sensor Open Circuit
Cause: The cable may be cut or the socket may be disconnected. The overheating sensor may have
failed.
Device Response: When the device sees the error, it wants to switch to stop mode.
Troubleshooting:
* Check the internal temperature sensor cable and sockets.
* Remove the internal temperature sensor and check by applying resistance test.
If the ohmic resistance is> 1200 Ω, replace the overheating sensor. @ 20 ° C
* If the resistance test is OK, replace the YHC.
* Reset the device from the button or disconnect the system from the power supply and connect again.
E 09 : Overheating Sensor Open Circuit
Cause: Cable may be cut or short-circuited.
Device Response: When the device sees the error, it wants to switch to stop mode. If the system is
hot, it will operate cooling mode before stopping.
Troubleshooting:
* Check the internal temperature sensor cable and sockets.
* Disconnect the internal temperature sensor connector, and reset the device from the button. If the
fault code E07 (Internal Temperature Sensor Open Circuit) is displayed, the internal temperature
sensor is faulty. Replace the internal temperature sensor.
* Or remove the internal temperature sensor and check by applying resistance test.
If the internal resistance is too low (about 0), there is a short circuit. Replace the internal
temperature sensor.
* If the resistance test is OK, replace the YHC.
*Reset the device from the button or disconnect the power supply and then connect again.
E 10 : Indoor Air Temperature Sensor High Current
24