Adjusting Sensitivity Levels
To choose another sensitivity level, press the Sensitivity button.
The LED below each level will change indicating the new setting.
The Leak Detector will default to the Norm sensitivity level
automatically once the unit comes out of the warm up cycle and
the green LED will turn on.
To change sensitivity levels, press the Sensitivity button once for
HI sensitivity (red LED will turn on) and again for LO sensitivity
(yellow LED will turn on).
Leak Standard Bottle
The leak detector comes with a Leak Test Vial that allows the
user to make sure the detector is performing properly. To test:
1. Remove the plastic seal cap on top of the Leak Test Vial
by pulling it off (see fig. below).
2. Turn on the detector and allow the unit to complete the
warm up cycle.
3. Place the sensor close to the small hole in the top of the
Leak Test Vial. The beep rate should increase indicating
that the sensor and electronics are working properly.
4. Replace plastic cap seal after leak test.
Note: Replace the leak standard when the green color is
no longer visible.
Chemical Has Green Color
Remove Seal Cap to test
Leak Test Vial