A.9 H Parameters: Multi-Function Terminals
H parameters assign functions to the multi-function input and output terminals.
u
H1: Multi-Function Digital Inputs
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
H1-01
(438)
Multi-Function Digital
Input Terminal S1
Function Selection
Term S1 Func Sel
Assigns a function to the multi-function digital inputs.
Refer to pages
for descriptions of setting values.
Note:
Set unused terminals to F.
Default: 40 (F)
Min.: 1
Max.: B2
H1-02
(439)
Multi-Function Digital
Input Terminal S2
Function Selection
Term S2 Func Sel
Assigns a function to the multi-function digital inputs.
Refer to pages
for descriptions of setting values.
Note:
Set unused terminals to F.
Default: 41 (F)
Min.: 1
Max.: B2
H1-03
(400)
Multi-Function Digital
Input Terminal S3
Function Selection
Term S3 Func Sel
Assigns a function to the multi-function digital inputs.
Refer to pages
for descriptions of setting values.
Note:
Set unused terminals to F.
Default: 24
Min.: 0
Max.: B2
H1-04
(401)
Multi-Function Digital
Input Terminal S4
Function Selection
Term S4 Func Sel
Assigns a function to the multi-function digital inputs.
Refer to pages
for descriptions of setting values.
Note:
Set unused terminals to F.
Default: 14
Min.: 0
Max.: B2
H1-05
(402)
Multi-Function Digital
Input Terminal S5
Function Selection
Term S5 Func Sel
Assigns a function to the multi-function digital inputs.
Refer to pages
for descriptions of setting values.
Note:
Set unused terminals to F.
Min.: 0
Max.: B2
H1-06
(403)
Multi-Function Digital
Input Terminal S6
Function Selection
Term S6 Func Sel
Assigns a function to the multi-function digital inputs.
Refer to pages
for descriptions of setting values.
Note:
Set unused terminals to F.
Min.: 0
Max.: B2
H1-07
(404)
Multi-Function Digital
Input Terminal S7
Function Selection
Term S7 Func Sel
Assigns a function to the multi-function digital inputs.
Refer to pages
for descriptions of setting values.
Note:
Set unused terminals to F.
Min.: 0
Max.: B2
H1 Multi-Function Digital Input Selections
H1-
oo
Setting
Function
LCD Display
Description
Page
0
3-Wire sequence
3-Wire Control
Closed: Reverse rotation (only if the drive is set up for 3-Wire sequence)
Terminals S1 and S2 are automatically set up for the Run command and Stop
command.
3
Multi-Step Speed
Reference 1
Multi-Step Ref 1
When input terminals are set to Multi-Step Speed References 1 through 3,
switching combinations of those terminals will create a multi-step speed sequence
using the frequency references set in d1-01 through d1-08.
4
Multi-Step Speed
Reference 2
Multi-Step Ref 2
When input terminals are set to Multi-Step Speed References 1 through 3,
switching combinations of those terminals will create a multi-step speed sequence
using the frequency references set in d1-01 through d1-08.
6
Jog reference selection
jog Freq Ref
Closed: Jog frequency reference (d1-17) selected. Jog has priority over all other
reference sources.
7
Accel/decel time
selection 1
Multi-Acc/Dec 1
Used to switch between accel/decel time 1 (set in C1-01, C1-02) and accel/decel
time 2 (set in C1-03, C1-04).
8
Baseblock command
(N.O.)
Ext BaseBlk N.O.
Closed: No drive output
9
Baseblock command
(N.C.)
Ext BaseBlk N.C.
Open: No drive output
A
Accel/decel ramp hold
Acc/Dec RampHold
Open: Accel/decel is not held
Closed: The drive pauses during acceleration or deceleration and maintains the
output frequency.
B
Drive overheat alarm
(oH2)
OH2 Alarm Signal
An external device has triggered an oH2 alarm.
C
Analog terminal input
selection
Term AI Enable
Open: Function assigned by H3-14 is disabled.
Closed: Function assigned by H3-14 is enabled.
A.9 H Parameters: Multi-Function Terminals
204
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual